9
5 Wiring
The VGreen 085 controller must be wired according to the locally adopt-
ed version of the NEC. A licensed, qualified electrician should complete
the wiring for this product.
The controller is designed to operate with 115 Vrms, single phase
power.
The VGreen 085 is designed to handle either a bare wire connection or
a quick disconnect connection. The quick disconnect tab is 0.250” and
will handle any commonly available mating connectors. For a direct wire
connection, the wire insulation should be stripped to a length of approxi-
mately 0.33.” The terminal block is capable of handling solid or stranded
wire up to 12 AWG in size. The screw for the mains connections should
be properly tightened to a torque value of 10 in-lb.
Pin #
Wire Color
Description
L1
Black
Hot 1
L2
Red or White
Hot 2
Green screw
Green
Earth
Table 1: Mains Connection
Pin #
Wire Color
Description
J201 - 1
Red
+12V
J201 - 2
Black
A
J201 - 3
Yellow
B
J201 - 4
Green
COM
Table 2: Communication Connection
The VGreen 085 controller must be wired according to the locally adopted version of the
NEC. A licensed, qualified electrician should complete the wiring for this product. Failure
to comply with this may result in death, serious personal injury or property damage.