Regada REMATIC ULR 1PA-Ex Installation, Service And Maintenance Instructions Download Page 30

28 

 

ULR 1PA-Ex, ULR 2PA-Ex 

 

Warning 1:

 W

hen the input control signal is set to the value 0 

÷

 20 mA 

(0 to 10 V)

, or 20 

÷

 0 mA 

(10 to 0 V)

 and 

the input control signal fails, then the EA keeps the position as with a 0 mA 

(0 V) 

input signal (EA doesn’t 

recognise between input signal fail and 0 mA 

(0 V)

 input signal). 

 

Warning 2: Auto-calibration process doesn’t run if triggered in time when the EA is in error state, e.g. EA is 
overloaded (EA is switched -off from torque). In such case is necessary to resolve issue, e.g. the EA must be 
moved in a position in which is not switch-off from torque and to start the auto-calibration again.

 

 

Warning 3: Calibration process must be performed at any change of the operating angle value of more than 
10%. 

 

Warning 4: Operate adjusting button 

on the control to activate the calibration process or start it from 

MENU 4

 

in the version with local control (use the buttons on local control) or from the programme once the EA is 
connected to the PC. All calibration start methods have been equal. 

Note No. 5: In case that EA with supply voltage 3x400V AC after calibration start shows the error „rotation 
direction“ (error No. 7), it is necessary to stop EA by switching-off the supply voltage and change the 
phases sequence on the terminals 2 and 3 (change mutually phases wires) and after switching-on the 
supply voltage run n the calibration again.      

Rotation direction definition of the electric actuator´s output element 

The output rod of the actuator while rotating in the direction “Close“ protrudes from the actuator. It means that 
the direction of rotation of the actuator is set as clockwise.   
 

In case the direction of rotation shall be changed the parater „Direction of rotation of the actuator“ must je 

adjusted as anticlockwise. This parameter can be adjusted through the PC only by use of the EHL Explorer SW. 
The PC must be connected to the actuator via communication cable and the window “Parameters“ used for 
direction adjustment.

 

 

4.3  Putting an EA into operation when the EA is set up and connected with the 

armature already in the production plant (starting the calibration) 

 

If EA is delivered from manufacturing plant joined with valve, or with control device, 

calibration

 must 

be performed to ensure correct operation, under actual pipeline conditions.  
The procedure is as follows: 

fit the given assembly into the specified technology complex 

connect  the  EA  on  the  supply  voltage  electrically  according  to  the  wiring  diagram  and  chapter 
Electric connection and checking of function. 

introduce the EA into an mid-position (see 

Note 2

 presented above) 

switch on the supply voltage 

start the EA calibration

 by pressing the 

P

 button on the control unit 

for 2 seconds as minimum

 

until LED ERROR (red), LED MENU (green) and LED PAR (red) light up – see also the procedure in 
the separate attachment 

No.74 1053 02

 

release the 

P

 setting button 

after releasing the 

P

 button the calibration procedure starts – inertia measuring 

after the calibration procedure is finished, the EA is prepared for its operation and starts to response 
to control inputs 

if  changes  to  some  parameters  would  be  necessary,  proceed  please  according  to  the  instructions 
given in the separate attachment 

No. 74 1053 02

 

4.4 

Putting an EA into operation when the stroke and parameter setting done by the 
producer suit to your needs

  

When  an  EA  is  delivered  from  the  producer  without  armature  and  the  setting  of  stroke  (stroke  end 
positions) and other parameters done by the producer suit Your needs, please proceed as follows: 

connect  the EA  with  the armature  to be  controlled  (

according  to  chapter 2

)  and  fit  this  assembly 

into the specified technology complex 

connect  the  EA  electrically  according  to  the  wiring  diagram  and  chapter  Electrical  connection  and 
checking of function 

introduce the EA into an mid- position (see 

Note 2

 presented above) 

switch on the supply voltage 

start the EA calibration by pressing the 

P

 button on the control unit 

for 2 seconds as minimum

 until 

LED ERROR (red), LED MENU (green) and LED PAR (red) light up – see also the procedure in the 
separate attachment No. 74 1053 02 

release the 

P

 setting button 

Summary of Contents for REMATIC ULR 1PA-Ex

Page 1: ...INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS 74 1063 52 1026 Explosion proof electric linear actuators REMATIC ULR 1PA Ex ULR 2PA Ex...

Page 2: ...ECEx FTZU 11 0002X FTZ 09 ATEX 0185X Design and type tests are in accordance with the following standards EN IEC 60 079 0 Explosive atmospheres Part 0 Equipment general requirements General requiremen...

Page 3: ...rs and the register of errors and warnings 26 4 3 Putting an EA into operation when the EA is set up and connected with the armature already in the production plant starting the calibration 28 4 4 Put...

Page 4: ...standard EN IEC 61010 1 within valid edition assigned for installation category II overvoltage category In order to demonstrate the compliance with the requirements of the European Council directive o...

Page 5: ...ification consists of the following characters Ex electric equipment complies with standard EN IEC 60 079 0 and related standards for the corresponding types of explosion protection d identification o...

Page 6: ...or to the level of protection IP of the electric device Flameproof enclosure d type of protection where in the parts capable of igniting an explosive atmosphere are located within the enclosure in ca...

Page 7: ...actuator by additional construction in order to maintain ambient temperature max 55 C and also to stop temperature transmitting through junction component 5 Cable glands blinds are assigned only for...

Page 8: ...number of 1 million start ups Switching frequency max 1 200 h 1 1 000 h 1 500 h 1 250 h 1 125 h 1 Minimal lifetime expectancy number of operating hours 850 1 000 2 000 4 000 8 000 Time of net operatio...

Page 9: ...ea type IV sea industrial According to IEC 60364 3 1993 EA have to resist external influences and work for a certainty In conditions of external environment marked as warm mild to very hot dry with te...

Page 10: ...signed for automatic regulation via analogue signals are designed for intermitted operation S4 25 with min number of starts according to table Thrust ranges kN On Off cycles per hour a Inching starts...

Page 11: ...sories are not immediately installed they have to be stored in dry well ventilated sheltered rooms protected against dirt dust soil humidity with placing onto shelves or onto pallets chemical impacts...

Page 12: ...n chapter 5 1 Service Basic modules of DMS3 electronic control system for ULR PA Ex Control unit 2 main part of system DMS3 it contains microprocessor 6 signal LED and 4 buttons for simple adjustment...

Page 13: ...ULR 1PA Ex ULR 2PA Ex 11 Fig 1 2 1 7 6 5 4 8 3...

Page 14: ...12 ULR 1PA Ex ULR 2PA Ex Fig 1A 8 2 4 6 5 5 3 7 1...

Page 15: ...12 5 20 24 40 48 6 4 10 80 96 4 8 3 2 8 Single phase 115 60Hz 40 1500 0 67 9 0 10 20 7 5 5 12 5 40 6 4 10 ULR 1PA Ex type number 546 80 4 up to 80 without transmitter 4 8 3 2 8 16 22 Three phase 3x400...

Page 16: ...on O Position Notes C Torque shutting off at end limit thrust Closed O Torque shutting off at end limit thrust Opened C Position shutting off at end limit position Closed O Position shutting off at en...

Page 17: ...4 mA 10 2 V according to version 20 12 mA 12 4 mA Input resistor for signal 0 4 12 up to 20 mA 4 up to 12 mA Rin 120 Input resistor for signal 0 2 up to 10 V Rin 30 k Tolerance of controller s linear...

Page 18: ...max 0 08 2 5 mm2 screw less terminal 2 terminals OP CL for version with 3 phase electric motor with intersection of connection wire max 0 08 2 5 mm2 screw less terminal 2 terminals 0 V 24V with inter...

Page 19: ...16s PX2K M16 3 1 8 7 6 1 11 5 X 16 PX2K M16 M16x1 5 6 5 14 0 12 5 20 9 X 20s 16 PX2K M20 3 1 8 6 6 1 13 4 X 20s PX2K M20 6 1 11 6 9 5 15 9 CMP Stahl X 20 PX2K M20 x a 6 5 13 9 12 5 20 9 12 20 13CR ex...

Page 20: ...er supply board is installed with power supply fuse F3 Location of the fuse on the power supply board can be seen in Fig 1d Product protection We recommend to use fuses for protection of product Fuse...

Page 21: ...ULR 1PA Ex ULR 2PA Ex 19 OUTSIDE GROUNDING TERMINAL FOR EA ULR 2PA Ex OUTSIDE GROUNDING TERMINAL FOR EA ULR 1PA Ex Fig 1c INSIDE GROUNDING TERMINAL Fig 1d Fuse F3...

Page 22: ...en the screws equally in cross At the end check the correctness of the fixture with the valve with rotating the handwheel 3 1 2 Cable routing and connection Direct entry to flameproof enclosure compou...

Page 23: ...ng on the leads assure protection enclosure up to IP 68 9 The face areas of the control part cover have to be before re mounting clean coated with grease without any acid e g vaseline and sealing not...

Page 24: ...ore dismantling it is required to disconnect the EA from mains Do not connect and disconnect live connectors Disconnect the EA from mains Disconnect the leads from the EA terminal boards and loosen th...

Page 25: ...ed in the ON OFF mode it lights with a control action for the closing direction eventually blinks besides the chosen parameter in the menu and lights up at writing the parameter into the memory LED I1...

Page 26: ...f or the end position is reached 2P PULSE CONTROL Setting up 2P control STOP function on I1 The EA moves either to the OPEN direction or closes with 24V DC voltage pulse supplied on connectors OPEN or...

Page 27: ...N or OFF as per I2 function set up to ACTIVE or supplied on I2 connector The EA is allowed to move either to the OPEN or CLOSE direction with 24V DC voltage supplied to terminals OPEN or CLOSE The EA...

Page 28: ...ble seat valves 3 TORQUE BLOCKING 2 sec blocking time 5 blocking position for OPEN CLOSE direction 4 RELAY READY errors READY COM NO relay contacts closed in error free conditions 5 RELAY 1 RE5 positi...

Page 29: ...REACT STOP 17 SAFE POSIT 0 18 FUNCTION I1 ESD 19 ACTIVE I1 high level 20 FUNCTION I2 DISABLED 21 ACTIVE I2 high level 22 THERMO FAIL THERMAL FUSE FAIL functionless with this EA type 23 THERMO RESET T...

Page 30: ...Putting an EA into operation when the EA is set up and connected with the armature already in the production plant starting the calibration If EA is delivered from manufacturing plant joined with val...

Page 31: ...and LED PAR red come on the opened end position is thus recorded in memory see description in separate annex No 74 1053 02 release the O setting button introduce the EA into an mid position see Note 2...

Page 32: ...lated member using the handwheel While rotating the handwheell clockwisely the output element moves in the direction CLOSING Electric local control additional equipment Fig 7 If necessary in the case...

Page 33: ...sp GLEITMO 585 K in versions for climate with temperatures 50 C till 40 C grease ISOFLEX TOPAS AK 50 linear adapter grease GLEIT HP 520M to 25 C resp HP 520S to 40 C Lubrication of the valve stem is i...

Page 34: ...and requirements Reparation of EA basically the parts the resisting closures consist with have substantial influence on safety is allowed perform only by producer witch according to certificated docu...

Page 35: ...pply voltage recovery EA is prepared for operation In case of a failure of a part of the EA the part can be replaced by a new one The exchange is to be committed by the producer or a contracted servic...

Page 36: ...dule X Power Supply Relay module type X Notes X the error or warning flag is activated With the error flag the EA takes the positron defined for the FAILURE REACTION function eventually stops dependin...

Page 37: ...Ex Electric motor components 2 1 Capacitor 9 F ULR 1PA Ex Electric motor components 2 1 DMS3 ZS switch mode power supply for 230 V AC and 115 V AC 64 051 103 3 1 1A Position scanning unit DMS3 SM4 64...

Page 38: ...36 ULR 1PA Ex ULR 2PA Ex 7 Enclosures 7 1 Wiring diagrams ULR 1PA Ex and ULR 2PA Ex...

Page 39: ...ULR 1PA Ex ULR 2PA Ex 37...

Page 40: ...38 ULR 1PA Ex ULR 2PA Ex...

Page 41: ...ULR 1PA Ex ULR 2PA Ex 39...

Page 42: ...40 ULR 1PA Ex ULR 2PA Ex...

Page 43: ...analogue input 0 2 10 V and output signal 4 20 mA Z537b wiring diagram of EA ULR 2PA Ex with 3 phase electric motor with contactors for the ON OFF control Z532c wiring diagram of EA with wired 3 phase...

Page 44: ...N L on terminal board of power supply X are fed by power supply 220 respectively 230 V AC Note 2 Three phase electric motor in the electric actuators ULR 1PA Ex do not have thermal protection of the...

Page 45: ...ULR 1PA Ex ULR 2PA Ex 43 7 2 Dimensional drawings Explosion proof electric linear actuator Rematic ULR 1PA Ex...

Page 46: ...44 ULR 1PA Ex ULR 2PA Ex...

Page 47: ...ULR 1PA Ex ULR 2PA Ex 45...

Page 48: ...46 ULR 1PA Ex ULR 2PA Ex Explosion proof electric linear actuator Rematic ULR 2PA Ex...

Page 49: ...ULR 1PA Ex ULR 2PA Ex 47 Explosion proof electric linear actuator Rematic ULR 1PA Ex version with local control Explosion proof electric linear actuator Rematic ULR 2PA Ex version with local control...

Page 50: ...ice check report Service center Date of repair Guarantee repair no User of actuator Claim applied by Actuator type number Actuator production number Product claim fault Detected product fault Used spa...

Page 51: ...Post guarantee service check report Service center Date of repair User of actuator Actuator operating place Actuator type number Actuator production number Detected product fault Used spare parts Rema...

Page 52: ...50 ULR 1PA Ex ULR 2PA Ex 7 5 Commercial representation Slovak Republic Regada s r o Strojn cka 7 080 01 Pre ov Tel 421 0 51 7480 460 Fax 421 0 51 7732 096 E mail regada regada sk...