Instructions for setting up a new
REFUsol 20K-2T, REFUsol 33K-2T & REFUsol 50K-3T
Page 1: ...Instructions for setting up a new REFUsol 20K 2T REFUsol 33K 2T REFUsol 50K 3T...
Page 2: ...the commissioning of an inverter the following parameters need to be set Date Time Country Code This is done through the display and following specific steps SetUp a new REFUsol 20K 2T 33K 2T 50K 3T_...
Page 3: ...seconds 6 At each field and by using button and navigation arrows you can set up date and time Example Set date 04 February 2021 and time 12 45 20 Year Up arrow 2 times 2 Up arrow 1 time 1 year 21 ap...
Page 4: ...ss 5 You will be asked to confirm again by pressing to Set Country 6 A field with 3 appears and you need to add the country code based on list Example for Germany VDE AR N4105 Up arrow 0 Up arrow 0 Up...
Page 5: ...ompleted inverter with go into activation mode At the display message Check appears and countdown until connection Once inverter goes into successful operation the message Normal appears SetUp a new R...
Page 6: ...ter s characteristics and the Activation Code for portal REFUlog www refu log com its serial number and firmware version Example Activation Code 7CBDFF11FF11 6BFC SL1ES033L3L958 Seral Number SL1ES033L...