22
R
56. Use
to set
Delay
and press
to confirm.
57. Press
, the display will show the Digital Input B6 screen:
Digital Input B6
Water pump disch. sw.
Active if Status
CLOSED OPEN
Delay time= 03secs.
Digital input B6 (Water pump discharge switch, B6): signal from a high-pressure switch reading the pump outlet. If the
input is active, after the delay shown here, an alarm is raised and the system stops. This input is used on systems with a
Modulating Pump. Note: Analog input 6 converted by software to digital input.
58. Press
and use
to set to
Water pump disch. sw.
(if installed).
59. Press
to confirm your selection.
60. Use
to set “Active if” to OPEN or CLOSED and press
to confirm.
Example: If when pump outlet pressure is normal, the status is CLOSED, then set the “Active if” condition to OPEN. Then,
when pressure is abnormal (high), the contact will open and the controller will trigger an alarm and stop the system after the
delay shown here.
61. Use
to set
Delay
and press
to confirm.
62. Press
to return to the
FACTORY SETUP MENU
. The display will read:
FACTORY SETUP MENU
SYSTEM SPECIFICATIONS
DIGITAL INPUTS
DELAYS
63. Use
to select
DELAYS
.
64. Press
to confirm your selection. The display will read:
DELAYS
ON/OFF:
015secs
Fact. pass. enab: 10mins
Drain if no dem: 0072hs
Air vent valve: 030secs
Set 0.23S per feet of
5/8” pipe & 3.1 GPM.
65. Press
.
66. Use
to enter the
ON/OFF
value. The
ON/OFF
value is the delay to start the adiabatic control once set to ON.
67. Press
to confirm your selection
.
68. Use
to enter the
Fact. pass. enab
value.