Installation
10
—
English
Variomat Basic
—
22.07.2020 - Rev.
A
6.2
Tanks
Primary tank
Secondary tank
Note!
Optional heat insulation is available for primary tanks, see
chapter 4.6 "Optional equipment and accessories" on page 5 .
Connection: G1"/ 6 bar
Type
Ø "D"
[mm]
Weight
[mm]
H
[mm]
h
[mm]
200
634
37
1060
146
300
634
54
1360
146
400
740
65
1345
133
500
740
78
1560
133
600
740
94
1810
133
800
740
149
2275
133
1000 / 740
740
156
2684
133
1000 / 1000
1000
320
2130
350
1500
1200
465
2130
350
2000
1200
565
2590
350
3000
1500
795
2590
380
4000
1500
1080
3160
380
5000
1500
1115
3695
380
7
Installation
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
•
Ensure that the system is voltage-free before installing the
device.
•
Ensure that the system is secured and cannot be reactivated by
other persons.
•
Ensure that installation work for the electric connection of the
device is carried out by an electrician, and in compliance with
electrical engineering regulations.
CAUTION
Risk of injury due to pressurised liquid
If installation, removal or maintenance work is not carried out
correctly, there is a risk of burns and other injuries at the connection
points, if pressurised hot water or hot steam suddenly escapes.
•
Ensure proper installation, removal or maintenance work.
•
Ensure that the system is de-pressurised before performing
installation, removal or maintenance work at the connection
points.
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
•
Wear protective gloves.
•
Please place appropriate warning signs in the vicinity of the
device.
CAUTION
Risk of injury due to falls or bumps
Bruising from falls or bumps on system components during
installation.
•
Wear personal protective equipment (helmet, protective
clothing, gloves, safety boots).
Note!
Confirm that installation and start-up have been carried out
correctly using the installation and commissioning certificate.
This action is a prerequisite for the making of warranty claims.
–
Have the Reflex Customer Service carry out commissioning
and the annual maintenance.
7.1
Installation conditions
Prior to shipping, this device was carefully inspected and packed.
Damages during transport cannot be excluded.
Proceed as follows:
1.
Upon receipt of the goods, check the shipment for
•
completeness and
•
possible transport damage.
2.
Document any damage.
3.
Contact the forwarding agent to register your complaint.
7.2
Preparatory work
Condition of the delivered device:
•
Check all screw connections of the device for tight seating. Tighten
the screws as necessary.
Preparing the device installation:
•
No access by unauthorised personnel.
•
Frost-free, well-ventilated room.
–
Room temperature 0 °C to 45 °C (32 °F to 113 °F).
•
Level, stable flooring.
–
Ensure sufficient bearing strength of the flooring before filling
the tanks.
–
Ensure that the control unit and the tanks are installed on the
same level.
•
Filling and dewatering option.
–
Provide a DN 15 filling connection according to
DIN 1988 - 100 and En 1717.
–
Provide an optional cold water inlet.
–
Prepare a drain for the drain water.
•
Electric connection, see chapter 6 "Technical data" on page 9 .
•
Use only approved transport and lifting equipment.
–
The load fastening points at the tanks must be used only as
installation resources.
7.3
Execution
ATTENTION
Damage due to improper installation
Additional device stresses may arise due to the connection of pipes
or system equipment.
•
Ensure that pipes are connected from the device to the system
without them being stressed or strained.
•
If necessary, provide support structures for the pipes or
equipment.
For installation, proceed as follows: