Operation
16
—
English
Vacuum spray degassing
—
18.12.2019
–
Rev. A
8.1.2
M a nual mode
Manual mode is intended for test and service tasks.
Press "Manual" at the controller. The Auto LED at the operator panel flashes to
visually indicate that manual mode is active. Manually activate or deactivate the
"SE" system degassing or the "NE" make-up degassing.
" S E" system degassing of the system water
The system degassing process corresponds to the continuous degassing in
Automatic mode. The degassing time, however,
is not automatically limited. This setting is required for the vacuum test during
commissioning (see chapter 7.6 "Vacuum test" on page 13 )) and test runs during
service work (see chapter 9.3 "Inspecting system degassing and make-up
degassing" on page 19 ).
" NE" make-up degassing of the fill and make-up water
The make-up degassing is required for test runs during service work (see
chapter 9.3 "Inspecting system degassing and make-up degassing" on page 19 )
and in the "Magcontrol" mode when filling the entire system with water.
•
"Next" and "Back" buttons
–
Selecting "NE" or "SE".
•
"Auto" button
–
Return to Automatic mode.
2.5 bar
NE
▼*
SE
▲*
010 h
*
Flashing mode "NE
▼
"
or "SE
▲
" is activated
8.1.3
S top mode
Stop mode is intended for commissioning of the Servitec.
Press "Stop" on the controller. The Auto LED at the operator panel extinguishes.
Except for the display of information, the Servitec is non-functional in Stop
mode. Function monitoring is stopped. The "PU" pump is switched off. The
system returns an alarm if the Stop mode is activated for more than 4 hours. If
"Floating alarm contact?" in the Customer menu is set to "Yes", the system
outputs the alarm to the group alarm contact.
8.1.4
S ummer operation
The degassing of the network water is not assured if the circulating pumps of the
system are shut down during Summer because gas-rich water cannot reach the
Servitec. In order to save energy, use the Customer menu to set the degassing
programme to make-up degassing. If the Servitec is operated with make-up
degassing during Summer, you must switch to interval or continuous degassing
after the circulating pumps have been activated.
Setting in the Customer menu, see chapter 8.2.1 "Customer menu" on page 16 .
S election from 3 degassing programmes.
•
Continuous degassing
–
For commissioning and repairs.
•
Interval degassing
–
For continuous operation (time-
controlled).
•
Make-up degassing
–
Only for make-up water. The machine
is not degassed.
Degassing
programme
Make-up degassing
Note!
For a detailed description of the selection of degassing programmes, see
chapter 9.3 "Inspecting system degassing and make-up degassing" on
page 19 .
8.1.5
Restarting
CAUTION
Risk of injury due to pump start-up
Hand injuries may occur when the pump starts up if you turn the pump motor at
the impeller using a screwdriver.
•
Switch the pump to a zero-volts state before turning the pump at the fan
wheel with a screwdriver.
ATTENTION
Device damage due to pump start-up
Pump damage may occur when the pump starts up if you turn the pump motor
at the impeller using a screwdriver.
•
Switch the pump to a zero-volts state before turning the pump at the fan
wheel with a screwdriver.
After an extended standstill time (the device is de-energised or in Stop mode),
the "PU" pump may jam. For this reason, use a screwdriver to rotate the pump at
the fan wheel of the pump motor before restarting.
Note!
A jamming of the "PU" pump is prevented during operation thanks to
forced starting action (after 24 hours).
8.2
Co ntroller
8.2.1
Customer menu
Use the Customer menu to set the device controller during commissioning. You
can then correct or retrieve system-specific values during operation, see
chapter 8.2.1 "Customer menu" on page 16 .
8.2.2
S ervice menu
This menu is protected with a password. It can be accessed only by the Reflex
Customer Service. A partial summary of the settings stored in the Service menu is
proved in the Chapter Default settings, see chapter 8.2.3 "Default settings" on
page 16 .
8.2.3
Default settings
The Servitec controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.
Customer menu
Pa rameter
S etting
Remarks
Language
EN
Display language
Time
Date
Servitec
Magcontrol
For systems with diaphragm-
type expansion vessel
Minimum operating
pressure p0
1.5 bar
Only Magcontrol
Safety valve, pressure
3.0 bar
Actuating pressure of the
system’s heat generator safety
valve
Degassing
Degassing programme
Continuous
degassing
Continuous degassing time 24 hours
Make-up
Maximum make-up
quantity
0 Litres
Only if controller with "With
water meter yes"
Maximum make-up time
20 minutes
Magcontrol and Levelcontrol
Maximum make-up cycles 3 cycles within 2
hours
Magcontrol and Levelcontrol
Softening (only if "Water treatment" with "Softening")
Shut off make-up
No
In the case of soft water
residual capacity = 0
Hardness reduction
8°dH
= Target
–
Actual
Maximum make-up
quantity
0 Litres
Attainable make-up quantity
Soft water capacity
0 Litres
Attainable water capacity
Cartridge replacement
18 months
Replace cartridge
Desalination (only if "Water treatment" with "Desalination")
Conductivity monitoring
No
Shut off make-up
No
In the case of soft water
residual capacity = 0
Hardness reduction
8°dH
= Target
–
Actual
Maximum make-up
quantity
0 Litres
Attainable make-up quantity
Soft water capacity
0 Litres
Attainable water capacity