Technical data
6 — English
Reflex Fillsoft — 20.01.2017-Rev. B
2
Technical data
Fittings
Fitting
Fitting group
Type
Fitting
Fitting group
Recommended range of application in heating
systems
20 kW – 300 kW
301 kW – 600 kW
Length
260 mm
380 mm
Width
130 mm
130 mm
Height
600 mm
600 mm
Weight
3.0 kg
5.8 kg
Permissible gauge operating pressure
8 bar
8 bar
Permissible operating temperature
5 °C – 40 °C
5 °C – 40 °C
Connections, inlet/outlet
Internal thread Rp ½
Internal thread Rp ½
Maximum continuous flow rate
0,4 m
3
/h
0,4 m
3
/h
2.1
Calculating the cartridge capacity
Use the regional overall water hardness to calculate the cartridge's capacity to treat the water. The cartridge must be replaced when this
capacity is reached.
Cartridge capacity for treating water
Variant
Fillsoft for softening
Fillsoft Zero for desalinating
Capacity with one cartridge
•
Fillsoft 1
6,000 [litres x °dH]
3,000 [litres x °dH]
Overall water
hardness [°dH]
Overall water hardness [°dH]
Capacity with two cartridges
•
Fillsoft 2
12,000 [litres x °dH]
6,000 [litres x °dH]
Overall water
hardness [°dH]
Overall water hardness [°dH]
Notes
•
To calculate the soft water capacity, you require the value of the relevant regional overall water hardness [°dH].
– Degree of German water hardness [°dH].
•
Contact the local water supplier for the regional overall water hardness.
– Optionally use the measuring equipment for determining the regional overall water hardness.