background image

 

8541468 • 15/12/2021 • Rev.0

 

 

1

 

 

 

Guida Rapida d’Installazione 
Quick Installation Guide 

 

 

 

 

 

 

 

MOSAIC M1S COM Modulo Master - Controllore Modulare di Sicurezza  

MOSAIC M1S COM Master Module - Modular Safety Controller 

Summary of Contents for 8046967

Page 1: ...8541468 15 12 2021 Rev 0 1 Guida Rapida d Installazione Quick Installation Guide MOSAIC M1S COM Modulo Master Controllore Modulare di Sicurezza MOSAIC M1S COM Master Module Modular Safety Controller...

Page 2: ...I RJ45 7 RESTART_FBK 8 USCITE 8 OUT STATUS 8 OUT TEST 8 OSSD 9 CHECKLIST DOPO L INSTALLAZIONE 9 CARATTERISTICHE TECNICHE 10 MOSAIC M1S COM MASTER MODULE 11 IMPORTANT SAFETY INSTRUCTIONS 11 OVERVIEW 12...

Page 3: ...il paragrafo Elenco delle Normative applicabili Effettuare una accurata analisi dei rischi per determinare il livello di sicurezza necessario alla vostra applicazione facendo riferimento a tutte le n...

Page 4: ...ersi alle autorit preposte in materia di sicurezza del proprio paese o alla associazione industriale competente Questa informazione riguarda l utilizzo e la parametrizzazionedi MOSAIC ReeR non si assu...

Page 5: ...ssare quindi i moduli alla barra ponendo attenzione a inserire la contattiera posta sul fondo del modulo sul rispettivo connettore Premere il modulo delicatamente fino a sentire lo scatto del bloccagg...

Page 6: ...tart 2 Input secondo EN 61131 2 Output di segnalazione programmabile PNP attivo alto 9 OSSD3 Output Uscita statica di sicurezza 3 PNP attivo alto 10 OSSD4 Output Uscita statica di sicurezza 4 PNP atti...

Page 7: ...type C per consentire il collegamento ad un Personal Computer sul quale risiede il SW di configurazione MSD MOSAIC Safety Designer MOSAIC CONFIGURATION MEMORY MCM MOSAIC master MOSAIC M1S COM ha la p...

Page 8: ...losa e l intera area di lavoro interessata risultino ben visibili Non deve essere possibile raggiungere il comando dall interno dell area pericolosa USCITE OUT STATUS Il segnale OUT STATUS pin 7 8 11...

Page 9: ...tivo ingresso di feedback 1 canale doppio e 2 singoli CHECKLIST DOPO L INSTALLAZIONE MOSAIC in grado di rilevare autonomamente i guasti che avvengono in ciascun modulo Tuttavia al fine di garantire il...

Page 10: ...C Max lunghezza cavo 3m Connettori di rete n descrizione 2 RJ45 per bus di campo e o connessione da remoto Cavo cat 5 o superiore Caratteristiche connessione di rete Velocit 10 100 Mbit autenticazion...

Page 11: ...heir parameters and the connections that are made as per the risk analysis Read the Applicable Standards section carefully Perform an in depth risk analysis to determine the appropriate safety level f...

Page 12: ...ety authorities or the competent trade association This information is about the usage and parametrisation of MOSAIC ReeR takes no responsibility for the solutions adopted by customers concerning the...

Page 13: ...t between them the connectors just mounted 3 Fasten the units to the rail arranging the contacts on the base of the unit on the respective connector Press the unit gently until you feel it snap into p...

Page 14: ...131 2 Programmable signal output PNP active high 9 OSSD3 Output Solid State Safety Output 3 PNP active high 10 OSSD4 Output Solid State Safety Output 4 PNP active high 11 RESTART_FBK3 STATUS3 Input Ou...

Page 15: ...type C connector for the connection to a PC that is hosting the configuration software MSD Safety MOSAIC Designer MOSAIC CONFIGURATION MEMORY MCM A backup memory called MCM optional can be installed...

Page 16: ...rea and the entire work area concerned are clearly visible It must not be possible to reach the control from inside the danger area OUTPUTS OUT STATUS The OUT STATUS signal pin 7 8 11 12 is a programm...

Page 17: ...puts per channel with their relative feedback input 1 dual channel and 2 single channels CHECKLIST AFTER INSTALLATION The MOSAIC system is able to detect the faults that occurs in each own module Anyw...

Page 18: ...for fieldbus and or remote connection remote connection Cable cat 5 or higher Network connection Speed 10 100 Mbit RSA encrypted authentication and AES 128 bit encrypted communication TCP port 300 Ava...

Page 19: ...8541468 15 12 2021 Rev 0 19 DICHIARAZIONE DI CONFORMIT DECLARATION OF CONFORMITY...

Page 20: ...20 8541468 15 12 2021 Rev 0 All REER product manuals are available at URL https www reersafety com it en download manuals...

Reviews: