Redring 10.8kW Powerstream-Eco Installation And User Manual Download Page 14

 

14 

 

 

 

Water comes in through the inlet, via a flow switch. 

The flow switch measures how much water is passing through the unit.                                                                        
If it detects more than the preset level of:- 
2.7 litres/minute for the 9.5kW model and 3.3 litres/minute for the 10.8kW. 

 

The units heating elements are switched on.  This is shown by the neon light glowing. 

 

The water is heated instantly as it passes through the copper heat exchanger tube. 

 

The temperature of the water coming out of the unit depends on:- 

 

The temperature of the mains water supply 

 

The water flow rate 

 

The power consumption of the unit (power level selected) 

 

The temperature of the main supply can vary from 5°C in winter up to about 20°C in summer, with 

an average of about 12°C.  The charts below show the water temperature (°C) you can expect from 
the unit, at the different power settings for different flow rates in litres/minute. 

 

9.5kW Powerstream-Eco 

 

Flow rate 
(litres/min.) 

3.0 

4.0 

6.0 

Power level 

High  Eco  Low  High  Eco  Low  High  Eco  Low 

Summer temp °C  65°  46°  40°  54°  39°  35°  43°  33°  30° 

Winter temp °C 

50°  31°  25°  39°  24°  20°  28°  18°  15° 

 
 

10.8kW Powerstream-Eco 

 

Flow rate 
(litres/min.) 

4.0 

5.0 

6.0 

Power level 

High  Eco  Low  High  Eco  Low  High  Eco  Low 

Summer temp °C  58°  41°  37°  51°  37°  34°  46°  34°  31° 

Winter temp °C 

43°  26°  22°  36°  22°  19°  31°  19°  16° 

 

 

The unit includes a dual thermal cut-out (diagram 10) which is attached to the heat exchanger tube. 
It will switch off the heater elements if the water flow is reduced too much and the temperature goes 
above a set limit. 

 

The first stage cut-out is cyclic and will automatically                                       

reset as the water temperature falls.                                                                              
The unit will then function normally again. 

 

The second stage cut-out when triggered needs to be re-set 
manually inside the unit (diagram 10).                                                                         

This cut-out will only operate in exceptional circumstances. 

 

The unit can supply two outlets,                                                                          
For example, a shower and a basin, or up to two basins                                             
– but water from the unit will be shared between the outlets.                                                                                 
This is particularly important if a unit supplies a shower and a basin,                                                           

as the basin should not be used while someone is using the shower.                                                               
The unit is NOT to be fitted to a bath or kitchen sink other than for hand-washing purposes.                                                                                                        

HOW YOUR 

POWERSTREAM-ECO  

WORKS 

 

On average on “high” 
(12°C main water supply 
at 4 litres/minute) 

an outlet temperature of 
46°C will be achieved. 

 

 

On average on “high” 
(12°C main water supply 

at 5 litres/minute) an 
outlet temperature of 
43°C will be achieved.

 

Diagram 10 

Thermal Cut-Out 

Summary of Contents for 10.8kW Powerstream-Eco

Page 1: ... after installation and demonstration It should be kept in a safe place as you may need to refer to it for general instructions or future maintenance REDRING POWERSTREAM ECO UNVENTED INSTANTANEOUS WATER HEATER Installation and User Guide Powerstream Eco ...

Page 2: ...ail us on Service request redringxpelair com Remember to quote the exact type of unit as written on the front of the unit and on this leaflet The model and serial number are located on the bottom face of the unit Make a note of those numbers here and be sure to quote them if you call for advice Model Number _ _ _ _ _ _ _ _ _ _ _ Serial Number _ _ _ _ _ _ _ _ _ _ _ _ Note You may be charged for a s...

Page 3: ... Wiring Regulations and Part P of the Building Regulations in force at the time of installation Installations outside England and Wales must also conform to any local regulations in effect This appliance is intended to be permanently connected to the fixed electrical wiring of the mains supply with its own dedicated supply Ensure that the mains water supply meets the requirements listed This appli...

Page 4: ...ct flow rate tables on page 14 The unit MUST NOT be mounted upside down diagram 1b BEFORE YOU START Check that the mains electric is capable of supplying the required current See the rating plate for current requirements Check the pressure of the main water supply To operate correctly the unit requires the following running pressures Check the rating plate to see which applies Model Dynamic Water ...

Page 5: ...it either above or below the basin Deciding the wiring route You have a choice of whether to feed the electric cable through the side or through the back of the unit If it going through the side of the unit cut out the plastic lug to expose the grommet diagram 2 If is going through the back of the unit cut through the grommet on the backplate with a sharp knife Take Care Make sure you do not remov...

Page 6: ...VALVE AND A 6 BAR PRESSURE RELIEF EXPANSION VALVE WARNING ENSURE THAT THE MAINS WATER SUPPLY MEETS THE REQUIREMENTS LISTED ON PAGE 4 BEFORE CONTINUING WITH INSTALLATION WARNING BEFORE CONNECTING THE PIPE WORK TO THE POWERSTREAM ECO ENSURE THAT THE PIPE WORK IS FULLY FLUSHED OUT Diagram 4a Plumbing with Non Return Valve Diagram 4b Unit serving Basin and shower ...

Page 7: ...connections The unit comes with a service valve diagram 5 which should be fitted on the inlet of the unit Models have either Ø15mm straight shanks or NPT connections Check to see which applies The valve can be used to turn off the water supply to the unit if it needs servicing or to reduce the main supply flow if it is too high see Powerstream Eco commissioning section on page 9 Fitting the attach...

Page 8: ...e In all cases the outer sheath of the cable MUST project through the grommet diagram 6 if side entry is used This will prevent water getting into the unit Strip back the insulation on the LIVE brown or red and NEUTRAL blue or black mains wires about 8mm Strip back any insulation on the EARTH green yellow or green about 20mm Feed the cable through the side or rear entry grommets as appropriate Con...

Page 9: ...set to High see adjusting power level below Turn the service valve clockwise until the neon light goes out then turn it back until the neon just comes on check the water temperature at the handset and if necessary turn the cold tap on and adjust to get the desired shower temperature ADJUSTING POWER LEVEL The Powerstream Eco has four power levels shown in table below selected by rotating the centra...

Page 10: ...u DO NOT enter the water flow during this time WARNING YOU MAY INITIALLY GET A SHORT BURST OF VERY HOT WATER FROM THE UNIT Turn on the cold or temperature tap if necessary to adjust the temperature of the water Make sure that no other outlets connected to the unit are used whilst you are in the shower or the water flow will drop suddenly When you have finished do not switch off the power if you ar...

Page 11: ...LEAN THE SHOWER HANDSET REGULARLY All water contains particles of lime scale which build up in the shower handset and unit reducing the performance It is therefore important to clean the shower handset by simply rubbing the rubber nozzles or soaking in proprietary lime scale remover and rinsing thoroughly before use The frequency of this will depend on water hardness and experience Diagram 9 Mixer...

Page 12: ... select to High For a shower adjust the spray pattern available on the multi mode handset Rotate power selector to Higher setting Water flow too low or temperature too high The main water supply is too low The hot tap is not fully open Power selector set too high Increase the supply water flow Make sure that the service valve is correctly adjusted Adjust the service valve so that the water is at t...

Page 13: ...nect the main supply to the INLET marked in blue Use a pump to boost the supply from a storage tank Reset it by opening the unit and pushing the button on the cut out diagram 10 Before you do this you must remove the cause of the problem Contact Redring see page 2 Water too cold neon light on The power select is set too low One element is not working The Power Supply Voltage has dropped Change the...

Page 14: ...0 6 0 Power level High Eco Low High Eco Low High Eco Low Summer temp C 58 41 37 51 37 34 46 34 31 Winter temp C 43 26 22 36 22 19 31 19 16 The unit includes a dual thermal cut out diagram 10 which is attached to the heat exchanger tube It will switch off the heater elements if the water flow is reduced too much and the temperature goes above a set limit The first stage cut out is cyclic and will a...

Page 15: ... out manual reset 93 793789 Printed front cover complete 93 794403 Control knob 93 794404 Screw cover set 93 794405 Flow switch assembly 93 794406 Heat exchanger 9 5kW 240V 93 794407 Heat exchanger 10 8kW 240V 93 794408 Power selector Assembly 93 794409 For further details including a comprehensive list off accessories and spare parts Contact Redring After Sales Service see page 2 ADDITIONAL ACCES...

Page 16: ...arts or product ends when the original guarantee period ends EXCLUSIONS This guarantee DOES NOT cover damage or defects arising from poor or incorrect installation improper use or lack of maintenance including the build up of limescale The unit MUST NOT be fitted to any type of thermostatic mixer valve or tap The unit MUST NOT be fitted to a bath or kitchen sink other than for hand washing purpose...

Reviews: