Redlion LD Plug Manual Download Page 5

Revised 08 2021

Drawing No. LP0673

5

RS232 Communications

RS232 is intended to allow two devices to communicate over 

distances up to 50 feet. Data Terminal Equipment (DTE) transmits data 

on the Transmitted Data (TXD) line and receives data on the Received 

Data (RXD) line. Data Computer Equipment (DCE) receives data on the 

TXD line and transmits data on the RXD line. The LD emulates a DTE. 

If the other device connected to the meter also emulates a DTE, the TXD 

and RXD lines must be interchanged for communications to take place. 

This is known as a null modem connection. Most printers emulate a DCE 

device while most computers emulate a DTE device.

Some devices cannot accept more than two or three characters in 

succession without a pause in between. In these cases, the meter 

employs a busy function.

As the meter begins to transmit data, the RXD line (RS232) is 

monitored to determine if the receiving device is “busy”. The receiving 

device asserts that it is busy by setting the RXD line to a space condition 

(logic 0). The meter then suspends transmission until the RXD line is 

released by the receiving device.

RS485 Communications 

The RS485 communication standard allows the connection of up to 32 

devices on a single pair of wires, distances up to 4,000 ft. and data rates 

as high as 10M baud (the LDA is limited to 38.4k baud). The same pair 

of wires is used to both transmit and receive data. RS485 is therefore 

always half-duplex, that is, data cannot be received and transmitted 

simultaneously.

3.4  SERIAL WIRING

TBD

A

COMM

RXD

TXD

4

2
3

1

B

5

232

485

5

LD METER

RECEIVING DEVICE

+5V

4

47K

47K

3

B (-)

A (+)

COMM.*

Transmit

Enable

* OPTIONAL

Terminal Block Connection Figure

1

1

TXD

RXD

COMM.

LD METER (DTE)

RECEIVING DEVICE

2

RXD

TXD

3

3

2

7

5

5

DTE

3

2

DB9

2

2

3

3

DTE

DCE

DB25

DB25

Terminal Block Connection Figure

4.0 r

evIeWIng

 

the

 F

ront

 B

uttons

 

and

 d

Isplay

BUTTON DISPLAY MODE OPERATION

PROGRAMMING MODE OPERATION

PAR

Access Programming Mode

Store selected parameter and index to next parameter

RST

SEL

Resets display

Index display through selected displays

OPERATING MODE DISPLAY DESIGNATORS

MAX

 

- Maximum display capture value

MIN

 

- Minimum display capture value

“1” - To the left of the display indicates setpoint 1 output activated.

“2” - To the left of the display indicates setpoint 2 output activated.

Pressing the 

SEL

 button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically 

every four seconds between the enabled display values. 

Advance through selection list/select digit position in 

parameter value
Increment selected digit of parameter value

The serial connections are made via terminal block TBD located 

inside the unit on the left side for the LD2 and on the right side for the 

LD4.

Summary of Contents for LD Plug

Page 1: ... VDC 100 mA if input voltage is greater than 50 VAC VDC 24 VDC 50 mA if input voltage is less than 50 VDC Isolation 3000 Vrms for 1 min to all inputs and outputs 3 INPUT RANGES Jumper Selectable D C Voltages 200 mV 2 V 20 V 200 V 10 V INPUT RANGE ACCURACY 23 C LESS THAN 85 RH INPUT IMPEDANCE MAX INPUT SIGNAL RESOLUTION TEMP COEFFICIENT 200 mV 0 1 of span 1 033 MΩ 75 VDC 10 µV 70 ppm C 2 V 0 1 of s...

Page 2: ...stallation Category II Pollution Degree 2 11 CERTIFICATIONS AND COMPLIANCES CE Approved EN 61326 1 Immunity to Industrial Locations Emission CISPR 11 Class B Safety requirements for electrical equipment for measurement control and laboratory use EN 61010 1 General Requirements EN 61010 2 030 Particular Requirements for Testing and Measuring Circuits RoHS Compliant UL Listed File E137808 E179259 Ty...

Page 3: ...istor when the load is switched One of the most effective ways is to place a diode across the inductive load Most RLC products with solid state outputs have internal zener diode protection However external diode protection at the load is always a good design practice to limit EMI Although the use of a snubber or varistor could be used RLC part numbers Snubber SNUB0000 Varistor ILS11500 or ILS23000...

Page 4: ...N O 2 COMM 2 Sinking Logic Sourcing Logic USER COMM 6 5 CURRENT EXC 4 3 2 1 TBC VOLT ANALOG COMM USER RANGE SELECT JUMPERS 2 mA 20 V 200 V 10 V 200 mV 2 V 200 mA 20 mA 200µA Current Signal self powered Terminal 3 ADC Terminal 2 ADC Voltage Signal self powered Terminal 1 VDC Terminal 2 VDC Current Signal 2 wire requiring excitation Terminal 4 EXC Terminal 3 ADC 1 2 200 VDC MAX VOLT ANALOG COMM INPU...

Page 5: ... high as 10M baud the LDA is limited to 38 4k baud The same pair of wires is used to both transmit and receive data RS485 is therefore always half duplex that is data cannot be received and transmitted simultaneously 3 4 SERIAL WIRING TBD A COMM RXD TXD 4 2 3 1 B 5 232 485 5 LD METER RECEIVING DEVICE 5V 4 47K 47K 3 B A COMM Transmit Enable OPTIONAL Terminal Block Connection Figure 1 1 TXD RXD COMM...

Page 6: ...d proceed through each module in sequence When programming is complete it is recommended to record the parameter programming and lock out parameter programming with the user input or programming security code FACTORY SETTINGS Factory Settings may be completely restored in Module 2 This is useful when encountering programming problems ALTERNATING SELECTION DISPLAY In the explanation of the modules ...

Page 7: ... the decimal location for the Input Value For Apply APLY style the meter shows the previously stored Input Value To retain this value press the SEL button to advance to the next parameter To change the Input Value press the RST button and apply the input signal to the meter Adjust the signal source externally until the desired Input Value appears Press the SEL button to enter the value being displ...

Page 8: ...ut 8 seconds 6 When the display reads the selected range connect the positive lead of the DC current source to the current input and apply full scale input signal for the range Note For 200 mA range apply 100 mA as indicated on the display Press PAR Display reads CALC for about 8 seconds 7 Repeat steps 3 through 6 for each input range to be calibrated When display reads CAL NO press the PAR button...

Page 9: ...gramming parameters This code can be used along with the Program Mode Lock out P Loc in the User Input Function parameter Module 1 Two programming modes are available Full Programming mode allows all parameters to be viewed and modified Quick Programming mode permits only the Setpoint values to be modified but allows direct access to these values without having to enter Full Programming mode Progr...

Page 10: ...en the setpoint is a control output usually balanced hysteresis is used For alarm applications usually unbalanced hysteresis is used For unbalanced hysteresis modes the hysteresis functions on the low side for high acting setpoints and functions on the high side for low acting setpoints Note Hysteresis eliminates output chatter at the switch point while time delay can be used to prevent false trig...

Page 11: ...igger point per the Setpoint Action shown in Setpoint Output Figures Latch means that the output can only be turned off by the front panel RST button or user input manual reset serial reset command or meter power cycle When the user input or RST button is activated momentary action the corresponding on output is reset immediately and remains off until the trigger point is crossed again Previously ...

Page 12: ...BREVIATED PRINTING This parameter determines the formatting of data transmitted from the meter in response to a Transmit Value command or a Block Print Request Select NO for a full print transmission consisting of the meter address mnemonics and parameter data Select YES for abbreviated print transmissions consisting of the parameter data only This setting is applied to all the parameters selected...

Page 13: ...minator Received First Character of Reply Reply Transmission NO REPLY FROM METER RESPONSE FROM METER Time Timing Diagram Figure Receiving Data From The Meter Data is transmitted from the meter in response to either a transmit command T a block print request command P or a User Input print request The response from the meter is either a full field transmission or an abbreviated transmission dependi...

Page 14: ...rity bit is sent The transmitter sets the parity bit to a zero or a one so that the total number of ones contained in the transmission including the parity bit is either even or odd This bit is used by the receiver to detect errors that may occur to an odd number of bits in the transmission However a single parity bit cannot detect errors that may occur to an even number of bits Given this limitat...

Page 15: ...1 d d S S P P 1 1 I I N N P P 2 2 U U A A S S N N User Input Assignment L L O O E E n n Min Display Enable Max Capture Delay Time Max Display Enable H H I I E E n n H H I I t t 2 2 S S E E C C Min Capture Delay TIme L L O O t t Factory Service Operations F F C C S S Access Code For Service Operations C C o o d d E E P P A A r r Parity Bit Baud Rate b b A A U U d d Data Bit d d A A t t A A 5 5 S S ...

Page 16: ...W COURSE OF DEALING COURSE OF PERFORMANCE USAGE OFTRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal law b The Company shall not be liable for a breach of the warranty set forth in paragraph a if i the defect is a result of Customer s failure to store install commission...

Reviews: