Revised 03 2020

Drawing No. LP1117

Line Filters for input power cables:

Schaffner # FN2010-1/07 (Red Lion #LFIL0000)

6. To protect relay contacts that control inductive loads and to 

minimize radiated and conducted noise (EMI), some type of 

contact protection network is normally installed across the 

load, the contacts or both. The most effective location is 

across the load.

a. Using a snubber, which is a resistor-capacitor (RC) network or 

metal oxide varistor (MOV) across an AC inductive load is very 

effective at reducing EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled 

by a transistor switch, care must be taken not to exceed the 

breakdown voltage of the transistor when the load is 

switched. One of the most effective ways is to place a 

diode across the inductive load. Most Red Lion products 

with solid state outputs have internal zener diode 

protection. However external diode protection at the load is 

always a good design practice to limit EMI. Although the 

use of a snubber or varistor could be used.

Red Lion part numbers: Snubber: SNUB0000

   

Varistor: ILS11500 or ILS23000

7. Care should be taken when connecting input and output 

devices to the instrument. When a separate input and output 

common is provided, they should not be mixed. Therefore a 

sensor common should NOT be connected to an output 

common. This would cause EMI on the sensitive input 

common, which could affect the instrument’s operation.
Visit 

https://www.redlion.net/emi

 for more information on EMI 

guidelines, Safety and CE issues as they relate to Red Lion products.

INSTALLATION

Converter DIN Rail Mounting

The DIN rail should be 

mounted horizontally so that 

the unit’s ventilation holes are 

vertical in relation to installation 

orientation. A minimum 

clearance of 1 inch (25.4 mm) 

should be maintained above 

and below the unit in order to 

ensure proper thermal 

regulation. For environments 

with vibration or impacts, DIN 

rail clamps are recommended.

For hazardous location 

installation, the following shall 

be taken into consideration: 

— The equipment shall only 

be used in an area of at least pollution degree 2, as defined in 

EN/IEC 60664-1.

— The equipment shall be installed in an enclosure that provides 

a minimum ingress protection of IP54 in accordance with EN/

IEC 60079-0. The enclosure shall be accessible only with the 

use of a tool.

— Transient protection shall be provided that is set at a level not 

exceeding 140% of the peak rated voltage value at the supply 

terminals to the equipment.

Recommended DIN Rail Mounting Steps:

1. Ensure the DIN rail lock latch is in the outward most position 

(unlocked). Hook the top back of the DA50D DIN rail clip on 

the unit over the DIN rail.

2. Push the bottom of the unit towards the DIN rail until the 

unit is flush with the rail.

3. Push the DIN rail lock latch to the latched (in) position.

Recommended DIN Rail Removal Steps:

1. Move the DIN rail lock latch to the unlatched (out) position.

2. Unhook the top of the unit and remove it from the DIN rail.

SLED INSTALLATION 

1. Prior to installing the Sled for your DA50D Converter 

application, ensure that the Converter is not receiving power.

2. Disconnect and remove your DA50D from the DIN rail.

3. Remove the DA50D Converter’s front cap by squeezing the 

sides and pulling.

4. Slide out the sled holder.

5. Install a sled into the sled holder and hand tighten the captive 

fasteners, or use a screwdriver.

6. Re-install the sled holder containing the sled into the 

Converter. Make sure it is fully seated.

7. Replace the front cap. 

POWER SUPPLY REQUIREMENTS

The DA50D Converter requires a 12-24 VDC power supply. Your 

unit may draw considerably less than the maximum rated power 

depending upon the configuration and features being used. Your 

unit will draw increased power with a sled installed. Items that 

could cause increases in current are microSD card, communications 

sleds, and other features programmed through software.

To ensure you do not exceed the capacity of your DA50D 

Converter host power supply, calculate the total power 

consumption required for all planned accessories.

It is very important that the power supply meets the following 

requirements and is mounted correctly if the unit is to operate 

reliably. Please take care to observe the following points:

 

– The power supply must be mounted close to the unit, with 

usually not more than 6 feet (1.8 m) of cable between the 

supply and the Converter. Ideally, the shortest length possible 

should be used.

 

– The wire used to connect the Converter power supply should 

be at least 22-gauge wire. If a longer cable run is used, a 

heavier gauge wire should be used. The routing of the cable 

should be kept away from large capacitors, inverters, and 

other devices which may generate significant electrical noise.

 

– Use a power supply with an NEC Class 2 or Limited Power 

Source (LPS) and SELV (safety extra-low voltage) rating. This 

type of power supply provides isolation to accessible circuits 

from hazardous voltage levels generated by a mains power 

supply due to single faults. Safety extra-low voltage circuits 

shall exhibit voltages safe to touch both under normal 

operating conditions and after a single fault, such as a 

breakdown of a layer of basic insulation or after the failure of 

a single component has occurred.

 

– Peak efficiency (DA50D) occurs at the low side of the voltage 

range (approx. 12 V), recommended for high temperature 

applications.

Visit www.redlion.net for a complete list of our NEC Class 2 

power supplies.

DIN RAIL LOCK LATCH

Unlock

Lock

CAUTION

: Follow standard ESD precautionary 

procedures.

ATTENTION

: Suivez les procédures de précaution 

standard de décharge électrostatique.

CAUTION

: Failure to properly align the sled holder 

can result in damage to the connector pins.

ATTENTION: 

Si le tiroir n’est pas correctement 

aligné, les broches du connecteur du tiroir risquent 

d’être endommagées.

Summary of Contents for DA50D

Page 1: ...ll safety related regulations local codes and instructions that appear in this document or on equipment must be observed to ensure personal safety and to prevent damage to either the device or equipment connected to it Do not use these products to replace proper safety interlocking No software based device or any other solid state device should ever be designed to be responsible for the maintenanc...

Page 2: ...ON Polycarbonate enclosure with IP30 rating For use only in an approved enclosure 9 MOUNTING REQUIREMENTS Mounts onto standard DIN style top hat T profile mounting rails according to EN50022 35 x 7 5 mm and 35 x 15 mm 10 WEIGHT 13 oz 404 3 g 3 40 86 29 2 03 51 60 6 00 152 40 6 86 174 34 6 86 174 34 5 11 129 75 DIMENSIONS In Inches mm EMC INSTALLATION GUIDELINES Although Red Lion Controls products ...

Page 3: ...he latched in position Recommended DIN Rail Removal Steps 1 Move the DIN rail lock latch to the unlatched out position 2 Unhook the top of the unit and remove it from the DIN rail SLED INSTALLATION 1 Prior to installing the Sled for your DA50D Converter application ensure that the Converter is not receiving power 2 Disconnect and remove your DA50D from the DIN rail 3 Remove the DA50D Converter s f...

Page 4: ...lacing an image file on the SD card The card is then inserted into the target DA50D and powered Refer to the Crimson 3 1 User Manual for more information on the proper names and locations of this file DA50D Cellular Connectivity Cellular connectivity is achieved using the DA 4G LTE CAT4 Modem Sled Refer to the documentation shipped with your DA 4G LTE CAT4 Modem Sled for installation and setup inf...

Page 5: ...ng the microSD instructions in the Crimson 3 1 User Manual INSTALL THE microSD CARD Insert the microSD card into the slot on the front of the Converter with the card oriented as shown The card is inserted properly when the card clicks into place in the card holder To remove the microSD card push in slightly on the card DA50D CONVERTER BATTERY TIME KEEPING A battery is used to keep time when the un...

Page 6: ...000 802 11n Wi Fi Sled DA S00 WF10N0 AM000 1 Port USB 2 0 Host Sled DA S00 PN40U4 00000 Dual RS232 Ports Sled Isolated DA S00 PN2221 IS000 Dual RS485 Ports Sled Isolated DA S00 PN2442 IS000 Mixed RS232 RS485 Ports Sled Isolated DA S00 PN2245 IS000 Spaces in listed part numbers are shown to improve readability do not include when searching for or ordering these parts Note Battery orientation MUST M...

Reviews: