Redlion CUB4I Manual Download Page 4

4

VOLTMETER SCALING

In many industrial applications, a voltmeter is required to display a reading

in terms of PSI, RPM, or some other unit of measure. The signal voltage being
measured is normally generated by a transducer which senses the variable and
delivers a linear output voltage. To provide the desired readout at the specified
voltage, the voltmeter must be scaled. The Scale switch, when in the “ON”
position, enables the Scale Potentiometer. The Scale Potentiometer is used with
a voltage range to provide a method of scaling the unit. The voltage DIP
switches are used to select one of the four coarse Division Factor ranges and the
Scale Potentiometer is a fine scale adjustment within the selected range. The
chart below shows the division factor range associated with each range
selection switch.

DIVISION FACTOR RANGE SELECTION CHART

S1:  0-199.9 mVDC  (0.1  D.F.  1.2)
S2:  0-1.999 VDC  (1.2  D.F.  10.5)
S3:  0-19.99 VDC  (10.5  D.F.  100.5)
S4:  0-199.9 VDC  (100.5  D.F.  1300)

Note: Enabling the Scale Potentiometer does NOT affect the calibration of 

the unit.

To determine the proper voltage range for an application requiring scaling,

the “Division Factor” required to provide the proper display reading must first
be determined by using the following formula.

USING THE FORMULA:

D.F  =  VT x D.D.P.

D.R.

WHERE:

VT

=

Maximum Transducer Output

D.D.P. =

Display Decimal Point

D.F.

=

Division Factor

D.R.

=

Desired Reading

D.D.P.
0.000

=

1

The DISPLAY DECIMAL POINT (D.D.P.)

00.00

=

10

is determined by the desired decimal

000.0

=

100

point placement in the readout.

0000

=

1000

After the Division Factor for the application has been calculated, the proper

voltage range switch that will provide for the Division Factor is set to the “ON”
position. Use the “Division Factor Range Selection Chart” to choose the proper
DIP switch setting.

Note: Only one voltage DIP switch should be turned on. Set the switch before

the voltage signal is applied.

EXAMPLE:

A relative humidity transducer delivers a 7.0 VDC voltage at a

relative humidity of 75%.

D.F.  = VT x D.D.P. = 7.0 x 1000 =  93.3

D.R.                  75

This Division Factor is between 10.5 and 100.5, therefore DIP switch

position S3 is set to the “ON” position. The Scaling Potentiometer is then
adjusted for the desired readout at a known relative humidity.

CUB4I SIGNAL INPUT

The CUB4 Current Meter has four current ranges that are selected by

positioning the jumper in the proper location on the male header strip.

The SCALE DIP switch (S1) and the Scaling Potentiometer are used

when it is necessary to scale the display to indicate other engineering units.
The Scale switch should be left in the “OFF” position when the application
requires direct current readout on the display.

When the power supply is floating (unreferenced) to the desired

measurement points, the (-) signal input and the power supply common
should be connected. If the power supply is not floating (referenced), the
common mode voltage between the (-) signal input and power supply
common terminal must not be greater than 1.0 V peak. A common mode
voltage higher than 1.0 V peak will result in a measurement error.

The Calibration Potentiometer has been set at the factory and should not be

adjusted unless the unit is being re-calibrated with an accurate current source.

Caution: The Maximum Current for each jumper position must not

be exceeded or the unit may be damaged (See Specifications).

BLOCK DIAGRAM CUB4V

CURRENT METER SCALING

The CUB4 Current Meter display can be scaled to almost any lower

numerical value. Setting the Scale switch to the “ON” position enables the
Scale Potentiometer, which is used with the current range selection jumper to
scale the unit. The Scale potentiometer can be set to divide the normal current
reading by a division factor between 1 and 13.

EXAMPLE: 

The CUB4 Current Meter has been connected to measure a circuit

current to 120.0 mA maximum. However, in this application, the display is to
indicate percent of load current with 120.0 mA equivalent to 100.0 percent.
The scale potentiometer is adjusted to reduce the normal 120.0 mA signal input
display reading of 120.0 to indicate the desired reading of 100.0 on the display.
Scaling to obtain a numerical readout higher than the normal value of the

current can also be accomplished in most cases by selecting a lower current
range. However, the maximum current for the range must not be exceeded.
(See Specifications for maximum input currents.)

BLOCK DIAGRAM CUB4I

Summary of Contents for CUB4I

Page 1: ...the instrument or equipment connected to it If equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired SPECIFICATIONS 1 DISPLAY 3 digit 1999 to 1999 0 6 15 2 mm high digits Minus sign is displayed when voltage or current is negative 2 DECIMAL POINTS DIP switch selectable decimal points allow the display to be read in tenths hundredth...

Page 2: ...ized Component File E179259 UL3101 1 CSAC22 2 No 1010 1 Recognized to U S and Canadian requirements under the Component Recognition Program of Underwriters Laboratories Inc Type 4X Enclosure rating Face only UL50 IECEE CB Scheme Test Certificate UL2356A 179259 USA CB Scheme Test Report 98ME60090 000098 Issued by Underwriters Laboratories Inc IEC 1010 1 EN 61010 1 Safety requirements for electrical...

Page 3: ...uppression Cores for signal and control cables Fair Rite 0443167251 RLC FCOR0000 TDK ZCAT3035 1330A Steward 28B2029 0A0 Line Filters for input power cables Schaffner FN610 1 07 RLC LFIL0000 Schaffner FN670 1 8 07 Corcom 1VR3 Note Reference manufacturer s instructions when installing a line filter 6 Long cable runs are more susceptible to EMI pickup than short cable runs Therefore keep cable runs a...

Page 4: ...tch position S3 is set to the ON position The Scaling Potentiometer is then adjusted for the desired readout at a known relative humidity CUB4I SIGNAL INPUT The CUB4 Current Meter has four current ranges that are selected by positioning the jumper in the proper location on the male header strip The SCALE DIP switch S1 and the Scaling Potentiometer are used when it is necessary to scale the display...

Page 5: ...tiometer for the desired reading ORDERING INFORMATION TYPICAL VOLT CURRENT MEASUREMENT APPLICATIONS CURRENT METER APPLICATION Analog Meter Replacement A manufacturer wants to replace several 1 mA DC analog meter movements with easy to read CUB4 Current Meters with backlighting One application involves measuring the flow rate of a liquid to indicate 0 to 250 gallons per minute Since 1 mA of current...

Page 6: ...6 This page intentionally left blank ...

Page 7: ...7 This page intentionally left blank ...

Page 8: ...d based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warran...

Reviews: