2

Drawing No. LP1137

Effective 07 2020

Operating Temperature Range for CUB5VB00 depends on 

display color and intensity level as per below:

INTENSITY LEVEL

TEMPERATURE

Red Display

1 & 2

-35 to 75°C

3

-35 to 70°C

4

-35 to 60°C

5

-35 to 50°C

Green Display

1 & 2

-35 to 75°C

3

-35 to 65°C

4

-35 to 50°C

5

-35 to 35°C

Storage Temperature: -35 to 85°C

Operating and Storage Humidity: 0 to 85% max. relative 

humidity (non-condensing)

Vibration to IEC 68-2-6: Operational 5-500 Hz, 5 g

Shock to IEC 68-2-27: Operational 30 g

Altitude: Up to 2000 meters

Installation Category I, Pollution Degree 2

7. CERTIFICATIONS AND COMPLIANCES:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

IEC/EN 61010-1

RoHS Compliant

UL Listed: File # E137808

Type 4X Indoor/Outdoor Enclosure rating (Face only)

IP65 Enclosure rating (Face only)

IP20 Enclosure rating (Rear of unit)

8. CONNECTIONS:

 Wire clamping screw terminals

Wire Strip Length: 0.3" (7.5 mm)

Wire Gage: 30-14 AWG copper wire

Torque: 3.5 inch-lbs (0.395 N-m) max.

9. 

CONSTRUCTION:

 This unit is rated for Type 4X/IP65 

requirements for indoor/outdoor use. High impact plastic case 

with clear viewing window. Panel gasket and mounting clip 

included.

10. WEIGHT:

 3.2 oz (100 g)

INSTALLING THE METER

Installation

The meter meets NEMA 4X/IP65 requirements when properly 

installed. The unit is intended to be mounted into an enclosed 

panel. Prepare the panel cutout to the dimensions shown. 

Remove the panel latch from the unit. Slide the panel gasket over 

the rear of the unit to the back of the bezel. The unit should be 

installed fully assembled. Insert the unit into the panel cutout.

While holding the unit in place, push the 

panel latch over the rear of the unit so that 

the tabs of the panel latch engage in the 

slots on the case.

The panel latch should be engaged in the farthest forward slot 

possible. To achieve a proper seal, tighten the latch screws evenly 

until the unit is snug in the panel (Torque to approx. 28 to 36 in-oz 

[0.202 to 0.26 N-m]). Do not over-tighten the screws.

Installation Environment

The unit should be installed in a location that does not exceed 

the operating temperature and provides good air circulation. 

Placing the unit near devices that generate excessive heat should 

be avoided.

The bezel should only be cleaned with a soft cloth and neutral 

soap product. Do NOT use solvents. Continuous exposure to 

direct sunlight may accelerate the aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) 

to operate the keypad of the unit.

SETTING THE JUMPERS

Input Range Jumper

This jumper is used to select the proper input range. The input 

range selected in programming must match the jumper setting. 

Select a range that is high enough to accommodate the maximum 

input to avoid overloads. To access the jumper, remove the rear 

cover of the meter.   

WARNING: 

Exposed line voltage exists on the circuit 

boards. Remove all power to the meter and load circuits 

before accessing inside of the meter.

Remove/Replace The Rear Cover

To remove the rear cover, locate the cover locking tab below 

the 2nd and 3rd input terminals. To release the tab, insert a small, 

flat blade screwdriver between the tab and the plastic wall below 

the terminals. Inserting the screwdriver will provide enough 

pressure to release the tab locks. To replace the cover, align the 

cover with the input terminals and press down until the cover 

snaps into place.   

PANEL 

GASKET

BEZEL

PANEL

MOUNTING SCREW

NUT FASTENER

MOUNTING CLIP

2.68

(68        )

+.8

1.30

-.0

(33      )

-.000

+.6

-.0

-.000

+.024

+.025

INPUT RANGE JUMPER

MAIN CIRCUIT 

BOARD

200VDC

2VDC

INPUT RANGE

JUMPER LOCATION

200mV/

20V/

Summary of Contents for CUB 5V Series

Page 1: ...FICATIONS 1 POWER Input voltage range is 9 to 28 VDC with short circuit and input polarity protection Must use an RLC model MLPS or an NEC Class 2 or Limited Power Source LPS rated power supply MODEL NO DISPLAY COLOR INPUT CURRENT 9 VDC WITHOUT CUB5RLY0 INPUT CURRENT 9 VDC WITH CUB5RLY0 CUB5VR00 10 mA 40 mA CUB5VB00 Red max intensity 85 mA 115 mA CUB5VB00 Green max intensity 95 mA 125 mA 2 DISPLAY...

Page 2: ...t the tabs of the panel latch engage in the slots on the case The panel latch should be engaged in the farthest forward slot possible To achieve a proper seal tighten the latch screws evenly until the unit is snug in the panel Torque to approx 28 to 36 in oz 0 202 to 0 26 N m Do not over tighten the screws Installation Environment The unit should be installed in a location that does not exceed the...

Page 3: ...t common must be suitably isolated from hazardous live earth referenced voltage or input common must be at protective earth ground potential If not hazardous voltage may be present at the signal or user inputs and input common terminals Appropriate considerations must then be given to the potential of the user and input commons with respect to earth ground and the common of the plug in cards with ...

Page 4: ...RRANTY OF MERCHANTABILITY B WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE OR C WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY WHETHER EXPRESS OR IMPLIED BY LAW COURSE OF DEALING COURSE OF PERFORMANCE USAGE OFTRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable loc...

Reviews: