SmokeSight SS10MAMA V0.5 

Page 2 

 

 

Mounting Base – Top View 

 

Mounting Base – Bottom View 

 

7.

 

Locking Tab 

8.

 

Tamper Clip 

9.

 

Mains Lid 

10.

 

Mains, Loop and 
Interlink  Terminals 

 

Specifications 

Smoke Alarm 

Application 

Residential Smoke Alarm for domestic 
dwellings  

Installation 

Ceiling or wall mounted 

Primary Power 
Supply 

220/240VAC, 50Hz, 30mA 
 

Terminals  

4 Screw Terminals  
Voltage Rating: 300VAC 
Conductor Size: 2 × 1.5 mm2, min cable 
size: 1mm2  

Secondary  
Power Supply 

2 x 1.5VDC AA Batteries 

Sensing Type 

Photoelectric.  The smoke alarm contains 
NO radioactive material 

Environment  
 

Altitude: 0m to 2,000m  
Temperature: 0°C to 40°C 
Humidity: 5% to 95%   

Audible 
Indication 

Alarm: 85dBA at 3m, ISO 8201 
Battery Low: Chirp 

Visual Indication  Mains Supply: Green LED 

Alarm: Red LED 

Interlink 

Wired: 40 alarms over 150 metres 
maximum  

Compliance 

AS 3786:2014, AS/NZS 60065,   
AS/NZS 60950.1, IEC 62599.2 

 

 Option Card 

Application 

Radio Interlink, Auto 
Test, Escape Lighting, 
Clap Silence 

Power Supply 

2 x AA Batteries 

Interlink  

Radio: 24 alarms over 
150 metres free air 
maximum 
Gateway: 5 isolated, 
wired alarm segments 
maximum 

Visual Indication 

Status, Alert, Escape: 
White LED 

Audible Indication 

Alert: 50dBA at 3m 
Battery Low: Chirp 

 

 

10 

Summary of Contents for SmokeSight SS10MAMA

Page 1: ...tages may be present at wires connected to this product Before working on this product isolate the electrical supply Ensure that the product has been correctly installed and tested for safe operation...

Page 2: ...The smoke alarm contains NO radioactive material Environment Altitude 0m to 2 000m Temperature 0 C to 40 C Humidity 5 to 95 Audible Indication Alarm 85dBA at 3m ISO 8201 Battery Low Chirp Visual Indic...

Page 3: ...r the ceiling Alarm Locations to Avoid Within 1 metre of air conditioner ducts ceiling fans and other high air flow areas Smoke may be blown away or diffused in these areas In areas where the temperat...

Page 4: ...ncorporates radio interlinking functionality As such it can operate as a gateway device to connect wired and wireless interlinked alarms Refer to Installation for the interlink connection arrangement...

Page 5: ...e mounting base unless the smoke alarm batteries are installed as damage may result Ready to slide Engages with a click Slide 11 Turn on the mains power and check that the green red and white LEDs fun...

Page 6: ...iguration command success is reported by one long flash beep while command failure is reported by two long flashes beeps The current configuration mode menu is reported every 10secs if no command is r...

Page 7: ...eeps 0 Add Radio Node Build Radio Network Mode Active 5flash 5beep every 10sec 4 Return to Operation Mode Auto Test Configuration Mode Command Taps Description Response White LED Flashes Beeps 0 Radio...

Page 8: ...Interlink Loss Master or Network Lost After 10mins 4 White LED Flashes Beeps Auto Test Fail Replace the smoke alarm Alternatively press the Test Hush button and if the smoke alarm sounds disable Auto...

Page 9: ...s on each smoke alarm eg the smoke alarms are mounted on a high ceiling Return to Factory Defaults would allow the Initial Setup procedure to be repeated It is assumed that the Radio Interlink switch...

Page 10: ...d the network as a slave 4 Once all alarms have been configured they will all be placed into Operation Mode 2mins after the last alarm has joined the network as a slave or by 4Tap of any node s Test H...

Page 11: ...plied with power Continue with the following steps only if you wish to change Auto Test times 2 Select Auto Test Configuration Mode From Operation Mode this can be achieved by 4Tap 2Tap of the Test Hu...

Page 12: ...LED is illuminated when the mains power is applied When the Alarm Sounds 1 Alert small children in the home 2 Leave immediately by your plan of escape Don t waste time getting dressed or picking up va...

Page 13: ...during this period from a smoke or fire event the unit will go into alarm mode Before using the alarm HUSH feature identify the source of smoke and be certain that a safe condition exists Replacing th...

Page 14: ...operation While the Test Hush button is pressed the alarm does not sound The smoke alarm may not be operating correctly Check that the green LED is ON and the red LED flashes once every 5mins If probl...

Page 15: ...has accumulated ALWAYS TEST THE SMOKE ALARM AFTER CLEANING If the smoke alarm is defective in any way do not tamper with the smoke alarm The smoke alarm does not contain any user serviceable parts As...

Page 16: ...SmokeSight SS10MAMA V0 5 Page 16 This page is intentionally left blank...

Reviews: