Calculating battery size for PA systems

Total amplifier power in watts

Battery Size  =

x 1.5 = 

Volts

500

=

x 1.5 = 31.25AH

24

Required

amps for 

1 hour

Therefore a 40AH battery would be suitable Please note: This calculation
assumes 100% duty cycle at full power output  into full rated load.

500W amplifier

Battery Size

Connecting batteries in series

+

12V Battery

+

12V Battery

To C

To Charger -

2 x 12V batteries = 24V total battery voltage.

+

6V Battery

+

6V Battery

To C

To Charger -

4 x 6V batteries = 24V total battery voltage.

+

+

6V Battery

6V Battery

It is common practice to connect 6V or 12V batteries in series to
create a 24V battery source. 

Equalising batteries

Connect in parallel overnight (10-12 hours
minimum) prior to connecting them to the
charger. Failure to do this can cause a severe
inbalance in the charging of the batteries causing
permanent damage.

+

12V Battery

12V batteries connected

in parallell.

+

12V Battery

6V batteries connected

 in parallell.

+

6V Battery

+

6V Battery

+

6V Battery

+

6V Battery

5.0 Battery Characteristics

Before connecting batteries to the charger it is recommended that the batteries be equalised as shown in Fig 4.

Batteries should also be connected in series to create a 24V battery source as shown in Fig 5.

** PLEASE NOTE: The A 4506 and A 4512 are 24V battery charging systems. **

Fig 3

Fig 5

4.0 Calculating Battery Size

Before wiring any batteries to the charger it is important to calculate the battery size required for the PA system you are 
installing. Figure 3 demonstrates the formula to calculate the required battery size. 

Fig 4

Summary of Contents for A 4506

Page 1: ...ort circuit protection Electronic reverse polarity protection 2 stage charging 2 switched 50 amp outputs Automatic boost and float voltages Precision control of boost and float voltage settings Batter...

Page 2: ...ult condition Boost charge mode Solid orange LED Absorb charge mode Flashing orange LED Trickle charge mode Solid green LED Fault Mode Solid red LED 4 Auxiliary 24V Out Indicator This LED indicates wh...

Page 3: ...he load s A maximum load of 50 amps per set of load terminals 8 Battery Isolate Reset This breaker can be used as an isolator to quickly disengage the batteries without having to disconnect leads It a...

Page 4: ...nnect in parallel overnight 10 12 hours minimum prior to connecting them to the charger Failure to do this can cause a severe inbalance in the charging of the batteries causing permanent damage 12V Ba...

Page 5: ...d load 1 ve and if required to load 2 ve and load 2 ve Note the load current is limited to 50 amps maximum per load Model A 4506 A4512 AC Fuse M205 5A 5A RISK OF ELECTRIC SHOCK OPEN BY QUALIFIED PERSO...

Page 6: ...ur Should mains power fail the unit will automatically switch the connected load s to the battery When mains power is restored the load s will be disconnected from the battery LED s on the front panel...

Page 7: ...y voltage Check that you have connected a lead from the battery to the terminals labelled Battery Voltage Unit will not charge battery Check connections to To battery terminals and to the battery Make...

Page 8: ...isplay Battery Voltage 3 5 Digit LCD Battery Current 3 5 Digit LCD Trickle charge Green LED Float charge Flashing Yellow LED Boost Charge Yellow LED Mains Power Green LED Battery Power Yellow LED Low...

Reviews: