POWER SUPPLY REQUIREMENTS 

NEW AND EXISTING INSTALLATIONS

The XCRS option card draws all of its power from the main board of the

Modular Controller Master or Data Station Plus. The specifications of the
Modular Controller Master or Data Station Plus account for the power needs of
an option card.

COMMUNICATING WITH THE XCRS OPTION CARD

CONFIGURING A XCRS OPTION CARD

The XCRS is configured using Crimson software. Crimson is available as a

free download from www.redlion.net, or it can be ordered on CD. Updates to
Crimson for new features and drivers are posted on the website as they become
available. By configuring the XCRS using the latest version of Crimson, you are
assured that your unit has the most up-to-date feature set. Crimson software can
configure the XCRS through the RS232 PGM port, USB port, Ethernet port, or
CompactFlash socket on your Modular Controller Master or Data Station Plus.
Additional information can be found in your Modular Controller Master or
Data Station Plus hardware bulletin and the Crimson user manual.

CABLES AND DRIVERS

Red Lion has a wide range of cables and drivers for use with many different

communication types. A list of these drivers and cables along with pin outs is
available from www.redlion.net. New cables and drivers are added on a regular
basis. If making your own cable, refer to the “XCRS Port Pin Outs” for wiring
information.

RS232 PORTS

The XCRS option card has one RS232 port. The port can be used for either

master or slave protocols with any Modular Controller Master or Data Station
Plus configuration. The RS232 port and RS422/485 port on the XCRS option
card are multiplexed because they share the same hardware. Both ports can be
used with master protocols. However, when the RS232 port is used with a slave
protocol, the RS422/485 port is not available.  For examples of RS232
communications refer to your Modular Controller Master or Data Station Plus
literature.

RS422/485 COMMS PORT

The XCRS option card has one RS422/485 port. This port can be configured

to act as either RS422 or RS485.

The RS422/485 port and RS232 port are multiplexed because they share the

same hardware. Both ports can be used with master protocols. However, when
the RS422/485 port is used with a slave protocol, the RS232 port is not
available.

Note: All Red Lion devices connect A to A and B to B, except for Paradigm

devices. Refer to www.redlion.net for additional information.

For examples of RS422/485 communications refer to your Modular Controller

Master or Data Station Plus literature.

DH485 COMMUNICATIONS

The XCRS option card's RS422/485 port can also be used for Allen Bradley

DH485 communications. When this port is configured to communicate DH485,
the RS232 port can not be used because the ports share the same hardware and
the XCRS option card multiplexes the ports to communicate via two protocols.

WARNING

: DO NOT use a standard DH485 cable to connect this port to Allen

Bradley equipment doing so may cause irreparable damage to the equipment
connected. A cable and wiring diagram are available from Red Lion.

Modular Controller Master or Data Station Plus to AB SLC

500 (CBLAB003)

SOFTWARE/UNIT OPERATIONS

XCRS PORT PIN OUTS

LEDS

The transmit LED(TX) will flash when information is transmitted from the

XCRS card. The receive LED(RX) will flash when information is received.

CRIMSON SOFTWARE

Crimson 2.0 software is available as a free download from www.redlion.net

or it can be purchased on a CD, see “Ordering Information” for part number.
The latest version of the software is always available from the web site, and
updating your copy is free.

TROUBLESHOOTING YOUR XCRS OPTION CARD

If for any reason you have trouble operating, connecting, or simply have

questions concerning your new XCRS option card, contact Red Lion's technical
support. For contact information, refer to the back page of this bulletin for
phone and fax numbers.

EMAIL: [email protected]
Web Site: http://www.redlion.net

3

RS422/485 4-WIRE

CONNECTIONS

RS485 2-WIRE

CONNECTIONS

Connections

RJ45: RLC

Name

RJ45: A-B

Name

1

TxB

1

A

2

TxA

2

B

3, 8

RxA

-

24V

4, 7

RxB

-

COMM

5

TxEN

5

TxEN

6

COMM

4

SHIELD

4, 7

TxB

-

COMM

3, 8

TxA

-

24V

Summary of Contents for XCRS

Page 1: ...RMATION 1 Contact your Red Lion distributor or visit www redlion net for complete selection 2 Red Lion offers RJ modular jack adapters Refer to DR literature for complete details 3 Use these part numbers to purchase Crimson 2 0 on CD with a printed manual USB cable and RS 232 cable Otherwise download free of charge from www redlion net SPECIFICATIONS 1 POWER REQUIREMENTS Power is supplied to the o...

Page 2: ...fy that the option card knobs are in the unlocked position as shown in Figure 2 4 Carefully insert the option card into the expansion port opening while aligning the card edge connector on the option card with the main board s header as shown in Figure 3 Once aligned gently press on the front of the card until it is flush with the front of the case 5 Turn the option card knobs to the locked positi...

Page 3: ... has one RS422 485 port This port can be configured to act as either RS422 or RS485 The RS422 485 port and RS232 port are multiplexed because they share the same hardware Both ports can be used with master protocols However when the RS422 485 port is used with a slave protocol the RS232 port is not available Note All Red Lion devices connect A to A and B to B except for Paradigm devices Refer to w...

Page 4: ...d based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warran...

Reviews: