background image

The switch will have a removable screw terminal plug (green) as shown in the diagram. The 
function of each position will be indicated on a label adjacent to the plug and/or on the 
side of the switch. The absolute minimum and maximum voltages are also indicated. 

 

To meet the UL requirements you must do one of the following: 

A.

 

Install a 3.33 Amp maximum fuse at the input of the switch 

B.

 

Use a Class 2 source to power the switch 

Note:

 The maximum screw torque is 5 in/lb (0.57 Nm). Do not over tighten. 

Connect power to the switch as follows: 

A.

 

Turn off your source power. 

B.

 

Make sure the area is currently nonhazardous (Class I, Div 2 or Zone 2 locations). 

C.

 

Connect a ground wire between the chassis ground screw 

 and your panel. For SL models that don’t 

have a chassis ground screw then use the screw position marked as 

. The SL-6RS has neither and is 

automatically connected to ground when installed on the DIN rail. 

D.

 

Connect your positive input wire to the P1 position. If you have dual power sources then apply your 
secondary positive input wire to the P2 position. 

E.

 

Connect your minus or return wire(s) to the “-“ position. 

F.

 

See the full installation guide for optionally connecting the alarm output on some models. 

G.

 

Turn on your source power and verify that the power LED(s) are on. 

4. Plug in your Ethernet cables and the switch will immediately start to operate and pass data.

5. Now you may configure the switch for more advanced operations. See below for further information.

Unmanaged Switches (ES or EG):

 No configuration is available or necessary. 

Managed Switches (MS or MG): 

To set the IP address so that you can manage the switch via the web interface: 

A.

 

Connect the switch directly to your PC’s Ethernet port using any Ethernet patch cable. The switch’s 
default IP is 10.2.0.1 or 192.168.0.1 (switch shipped after April, 2010). 

B.

 

On your PC, go to Control Panel – Network Connections and access the properties for your LAN’s 
Internet Protocol (TCP/IP).  Record your current settings, then select “Use this IP address” and set the 
IP and subnet to 10.2.0.100 or 192.168.0.100 (see note above). Close and reboot if prompted. 

C.

 

Run a web browser and type 10.2.0.1 or 192.168.0.1 into the address bar and hit enter. Use “admin” 
for both user name and password to access the web interface. 

D.

 

In the Quick Setup screen, enter your desired IP and subnet, or enable DHCP. Click on “Commit 
Changes” to save these new settings to the switch. 

E.

 

Repeat step 4 to return your PC to its original IP address and subnet mask. 

Now you can access your switch using the new IP address. Refer to the full management guide or web interface 
help for details on further configuring the switch. 

Ring Switches (RS): 

The last two ports of a ring switch are pre-configured as the ring ports. Use these ports to form your ring as 
shown in the diagram below. 

Ring Port 2 

Ring Port 1 

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Reviews: