SPECIFICATIONS
Setpoint Output Cards
: Six types of field installable cards
Response Time
: 200 msec. max. to within 99% of final readout value
(digital filter and internal zero correction disabled) 700 msec. max.
(digital filter disabled, internal zero correction enabled)
PAXH only: 1 sec. max. to within 99% of final readout value (digital
filter disabled)
PAXT only: 200 msec. typ.; 700 msec max. (digital filter disabled)
PAXH Isolation For All Four Cards
:
Isolation To Sensor Common: 1400 Vrms for 1 min.
Isolation To User Input Common: 500 Vrms for 1 min.
Dual Relay Card
: PAXCDS10
Type: Two FORM-C relays
Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min.
Contact Rating:
One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive
load).
Total Current With Both Relays Energized not to exceed 5 amps
Life expectancy: 100 K cycles min. at full load rating. External RC
snubber extends relay life for operation with inductive loads
Quad Form A Relay Card
: PAXCDS20
Type: Four FORM-A relays
Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min.
Contact Rating:
One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load).
Total Current With All Four
Relays Energized not to exceed 4 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC
snubber extends relay life for operation with inductive loads
Quad Sinking Open Collector Card
: PAXCDS30
Type: Four isolated sinking NPN transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Not Isolated from all other commons.
Rating: 100 mA max @ V
SAT
= 0.7 V max. V
MAX
= 30 V
Quad Sourcing Open Collector/SSR Drive Card
: PAXCDS40
Type: Four isolated sourcing PNP transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Not Isolated from all other commons.
Rating:
Internal supply: 18/24 VDC (unit dependent) ± 10%, 30 mA max. total
all four outputs
External supply: 30 VDC max., 100 mA max each output
Dual Triac/Dual SSR Drive Card
: PAXCDS50
Triac:
Type: Isolated, zero crossing detection
Voltage: 260 VAC max., 20 VAC min.
Max Load Current: 1 Amp @ 25°C
0.75 Amp @ 50°C
Total load current with both triacs ON not to exceed 1.5 Amps
Min Load Current: 5 mA
Off State Leakage Current: 1 mA max @ 60 Hz
Operating Frequency: 20-400 Hz
SSR Drive:
Type: Two isolated sourcing PNP Transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Not Isolated from all other commons.
Rating:
Output Voltage: 18/24 VDC (unit dependent) ± 10%, 30 mA max.
total both outputs
Quad Form C Relay Card
: PAXCDS60
Type: Four FORM-C relays
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Contact Rating:
Rated Load: 3 Amp @ 30 VDC/125 VAC
Total Current With All Four
Relays Energized not to exceed 4 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC
snubber extends relay life for operation with inductive loads
Internal Supply
(18/24 V unit dependent)
External Supply
(30 V )
max
Quad Sourcing Open Collector Output Card Supply Select
For Quad Sourcing/SSR Drive Option Card (PAXCDS40), set the jumper for
internal or external supply operation before applying power.
ISOLATION
SOURCE OUT
COMM.
InV
NC
Sourcing Output/SSR Drive Logic Card
(Internal Supply)
ISOLATION
SOURCE OUT (+)
InV
(+30 V MAX.)
EXTERNAL SUPPLY
COMMON (-)
(EXTERNAL SUPPLY AND
SOURCE OUT RETURN)
Sourcing Output Logic Card
(External Supply)
ORDERING INFORMATION
MODEL NO. DESCRIPTION
PART NUMBER
PAXCDS
Dual Relay Output Card
PAXCDS10
Quad Form A Relay Output Card
PAXCDS20
Quad Sinking Open Collector Output Card
PAXCDS30
Quad Sourcing Open Collector/SSR Drive
Output Card
PAXCDS40
Dual Triac/Dual SSR Drive Output Card
PAXCDS50
Quad Form C Relay Output Card
PAXCDS60 *
* This card is not suitable for use in older PAX models. For proper installation, a
case knock-out feature must be present on the top surface of the PAX case. This
feature began to be introduced to the standard PAX units in July of 2014 (2614).
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls
China
Unit 302, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113 3688
Fax +86 21 6113 3683
Red Lion Controls
Europe
Softwareweg 9
NL - 3821 BN Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
201-B, 2nd Floor, Park Centra
Opp 32 Mile Stone, Sector-30
Gurgaon-122002 Haryana, India
Tel +91 984 487 0503