NT24k Compact Series - Hardware Manual (Revised 06-02-2015)
89
Ethernet Cable
2.7
Ethernet Cable
If you are connecting to the unit via the copper port, you will need a straight or crossover cable with two 8-pin RJ45
connectors on each end.
To visually confirm that Ethernet cabling was done properly, check the LED indication on the Ethernet port of the unit. The
link LED should be on when the correct cable is used.
Note:
A shielded cable is required to fully meet EMC standards.
When using shielded cables, it is generally recommended to only connect the shield at one end to prevent ground loops
and interference with low level signals (i.e. thermocouples, RTD, etc.). CAT5e cables manufactured to EIA-568A or 568B
specifications are required for use with Red Lion Series switches.
In the event all CAT5e patch cables are short (i.e. All Ethernet devices are located in the same local cabinet and/or refer-
enced to the same earth ground), it is permissible to use fully shielded cables terminated to chassis ground at both ends in
systems avoid low level analog signals.
RJ45 Connector Crimp Specifications