red lion IRMA DC Manual Download Page 4

4

Field Calibration with an Accurate Adjustable Resistance Source

Note: The nominal output value for the various output ranges are designated in the 

following order:  (0 to 20 mA, 4 to 20 mA, 0 to 10 VDC)

1.1  Connect resistance source to the RTD input terminals using a third sense wire. 

(For 2 wire sensors, short terminal #7 to terminal #8.)

1.2  Set the type and Range for the RTD or resistance used in your application. (DIP 

switches #4, #6, #7 & #8). (RTD alpha = 0.00385, Range 0 shown). APPLY 
OPERATING VOLTAGE and allow 45 minute warm-up period.

1.3  Set the FIELD CAL switch (#2) ON. [Output goes to -0.8 mA, 3.5 mA, or -0.4 V 

nominal]

1.4  Set the input resistance to the value intended to generate the analog low endpoint 

(For 2 wire sensors, add the system lead resistance to the desired value.)

1.5  Set the OUTPUT CAL switch (#1) ON. [Output stays at -0.8 mA, 3.5 mA, or -0.4 

V nominal]

1.6  Adjust the input signal up until the analog output equals desired low value.[0 mA, 

4 mA, or 0 V]

1.7  Set the OUTPUT CAL switch (#1) OFF. [Output increases to 22.9 mA, 22.5 mA, 

or 11.5 V nominal]

1.8  Set the input resistance to the value intended to generate the analog high endpoint. 

(For 2 wire sensors, add the system lead resistance to the desired value.)

1.9  Set the OUTPUT CAL switch (#1) ON. [Output decreases to 21.1 mA, 20.7 mA, 

or 10.6 V nominal]

1.10 Adjust the input signal down until the output equals desired high value. [20 mA, 

20 mA, or 10 V]

1.11 Set the OUTPUT CAL switch (#1) OFF. 

1.12 Set the FIELD CAL switch (#2) OFF.

1.13 Disconnect the resistance source from the IRMA and connect the actual sensor to 

be used in the application.

DIP SWITCH SETTINGS:

ON = 1

OFF = 0

9-32 VDC

V+

I+

VDC+

RTD(S)

POWER

RTD(-)

RTD(+)

VDC-

9

ERROR

7

8

12

10

11

6

3

4

1

5

2

V-

I-

5

1

4
3
2

8
7
6

RANGE

RANGE

OHMS/RTD

FIELD CAL

BASIC CAL

OUTPUT CAL

392

     SEN UP/DN

MODEL IRMA

ERROR

POWER

VDC+

10

RTD(S)

7

V+

4

I+

1

VDC-

RTD(+)

12

11

9

8

6

5

V-

3

2

I-

POWER SUPPLY

9 to 32 VDC

VOLTAGE METER

OR

CURRENT METER

MONITORING INSTRUMENT

RTD(-)

ADJUSTABLE
RESISTANCE

SOURCE

-

+

S

Field Calibration Wiring

1.0 Field Calibration

CALIBRATION PROCEDURES

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

Step 1.11

Step 1.12

Step 

1

.

2

Step 1.3

Step 1.5

Step 1.7

Step 1.9

Field Calibration scales the selected output to a temperature or resistance 

input. This procedure assigns an input value to the low end and an input value 
to the high end. The microprocessor handles configuring the output so it is 
linear to the temperature or resistance input. The Field Calibration procedure is 
described below.

Note: The unit needs to have the Field Calibration completed by the operator 

before normal operation. To abort this calibration and reset to the previous 
settings, set the FIELD CAL switch OFF prior to the final OFF setting of the 
OUTPUT CAL switch (Step 1.11) and turn off power. Wait 5 seconds and then 
turn on power and the previous settings will be loaded.

RTD temperature to resistance conversion table

195.80

194.09

250

177.23

175.85

200

173.48

172.17

190

158.36

157.33

150

139.20

138.5

100

119.75

119.40

50

100.00

100.00

0

79.96

80.30

-50

59.55

60.25

-100

38.64

39.71

 -150

34.38

35.53

-160

alpha 

0.00392

alpha 

0.00385

Temperature 

°C

333.90

329.54

650

330.68

326.38

640

317.66

313.63

600

314.38

310.41

590

301.13

297.42

550

284.30

280.92

500

267.18

264.13

450

253.28

250.49

410

249.77

247.05

400

232.07

229.69

350

214.08

212.03

300

alpha 

0.00392

alpha 

0.00385

Temperature 

°C

Summary of Contents for IRMA DC

Page 1: ...er the protection provided by the equipment may be impaired SPECIFICATIONS 1 POWER 9 to 32 VDC 1 75 W 200 mA max current The power supply must have 400 mA for 200 msec surge capacity 2 INPUT RTD 2 3 o...

Page 2: ...nstallation Listed below are some EMC guidelines for successful installation in an industrial environment 1 Use shielded screened cables for all Signal and Control inputs The shield screen pigtail con...

Page 3: ...used at a time The unit is factory set for a 4 to 20 mA output The voltage output will track the current output linearly within 2 5 deviation of range endpoints To select 0 to 20 mA output you must o...

Page 4: ...I VDC RTD S POWER RTD RTD VDC 9 ERROR 7 8 12 10 11 6 3 4 1 5 2 V I 5 1 4 3 2 8 7 6 RANGE RANGE OHMS RTD FIELD CAL BASIC CAL OUTPUT CAL 392 SEN UP DN MODEL IRMA ERROR POWER VDC 10 RTD S 7 V 4 I 1 VDC R...

Page 5: ...s using a third sense wire Set the RANGE 7 8 TYPE 4 OUTPUT CAL 1 and FIELD CAL 2 switches OFF Set the BASIC CAL switch 3 ON 2 2 Apply operating power and allow a 45 minute warm up period Current goes...

Page 6: ...ail Installation To install the IRMA on a G style DIN rail angle the module so that the upper groove of the foot catches under the lip of the top rail Push the module toward the rail until it snaps in...

Page 7: ...7 This Page Intentionally Left Blank...

Page 8: ...yer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any pers...

Reviews: