background image

3

WIRING

WIRING CONNECTIONS

All conductors should meet voltage and current ratings 

for each terminal. Also, cabling should conform to 

appropriate standards of good installation, local codes and 

regulations and be suitably rated for the temperatures of 

the environment to which it is being installed. When wiring 

the module, use the numbers on the label to identify the 

position number with the proper function. Strip the wire, 

leaving approximately 1/4" (6 mm) of bare wire exposed. 

Insert the wire into the terminal, and tighten.

EMC INSTALLATION GUIDELINES

Although Red Lion Controls Products are designed with a high degree of 

immunity to Electromagnetic Interference (EMI), proper installation and wiring 

methods must be followed to ensure compatibility in each application. The type 

of the electrical noise, source or coupling method into a unit may be different 

for various installations. Cable length, routing, and shield termination are very 

important and can mean the difference between a successful or troublesome 

installation. Listed are some EMI guidelines for a successful installation in an 

industrial environment.

1. A unit should be mounted in a metal enclosure, which is properly connected 

to protective earth.

2. Use shielded (screened) cables for all Signal and Control inputs. The shield 

(screen) pigtail connection should be made as short as possible. The 

connection point for the shield depends somewhat upon the application. 

Listed below are the recommended methods of connecting the shield, in order 

of their effectiveness.

a. Connect the shield to earth ground (protective earth) at one end where the 

unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually when 

the noise source frequency is over 1 MHz.

c. Connect the shield to common of the module and leave the other end of the 

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC 

power lines, conductors, feeding motors, solenoids, SCR controls, and 

heaters, etc. The cables should be run through metal conduit that is properly 

grounded. This is especially useful in applications where cable runs are long 

and portable two-way radios are used in close proximity or if the installation 

is near a commercial radio transmitter. Also, Signal or Control cables within 

an enclosure should be routed as far away as possible from contactors, control 

relays, transformers, and other noisy components. 

4. Long cable runs are more susceptible to EMI pickup than short cable runs. 

Therefore, keep cable runs as short as possible.

5. In extremely high EMI environments, the use of external EMI suppression 

devices such as Ferrite Suppression Cores for signal and control cables is 

effective. The following EMI suppression devices (or equivalent) are 

recommended:

Fair-Rite part number 0443167251 (RLC part number FCOR0000)

TDK part number ZCAT3035-1330A

Steward part number 28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (Red Lion Controls # LFIL0000)

Schaffner # FN670-1.8/07

Corcom # 1 VR3

Note: Reference manufacturer’s instructions when installing a line filter.

6. To protect relay contacts that control inductive loads and to minimize radiated 

and conducted noise (EMI), some type of contact protection network is 

normally installed across the load, the contacts or both. The most effective 

location is across the load.

a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide 

varistor (MOV) across an AC inductive load is very effective at reducing 

EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor 

switch, care must be taken not to exceed the breakdown voltage of the 

transistor when the load is switched. One of the most effective ways is to 

place a diode across the inductive load. Most RLC products with solid state 

outputs have internal zener diode protection. However external diode 

protection at the load is always a good design practice to limit EMI. 

Although the use of a snubber or varistor could be used.

RLC part numbers: Snubber SNUB0000

  

        Varistor ILS11500 or ILS23000

Note: Reference manufacturer’s instructions when installing any EMI 

suppression device.

7. Also care should be taken when connecting input and output devices to the 

instrument. When a separate input and output common is provided, they 

should not be mixed. Therefore a sensor common should NOT be connected 

to an output common. This would cause EMI on the sensitive input common, 

which could effect the instrument’s operation.

Visit RLC’s web site at www.redlion.net for more information on EMI 

guidelines, Safety and CE issues as they relate to Red Lion Controls products.

Terminals 13 to 18
Terminals 7 to 12
Terminals 1 to 6

V-

I-

V+

6

V-

V+

I+

2

5

4

3

2

1

1

12

9

8

7

11

10

V-

I-

I+

2

I-

V+

I+

3

18

15

13 14

17

16

I-

V-

V+

4

N/

C

I+

N/

C

HARDWARE INSTALLATION

Modules must be installed beginning with slot 1 (left-most slot), with no 

empty slots between the modules, and the order must match the modules order 

in Crimson. Torque screws to 6.0 pound-force inch (96 ounce-force inch) 

REMOVE RUBBER

MODULE PLUG

WARNING: Disconnect all power 

to the unit before installing or 

removing modules.

WARNING - EXPLOSION HAZARD - DO NOT 

CONNECT OR DISCONNECT CABLES WHILE 

POWER IS APPLIED UNLESS AREA IS KNOW 

TO BE NON-HAZARDOUS.

Summary of Contents for Graphite Series

Page 1: ...y to use graphical interface that provides a means of communication configuration as well as commissioning and calibration of new systems SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a ...

Page 2: ...wer supply 500 V 50 60 Hz for 1 minute between any of the outputs and the Host power supply input 6 ENVIRONMENTAL CONDITIONS Operating Temperature Range 40 to 75 C limited to host Storage Temperature Range 40 to 85 C Operating and Storage Humidity 85 max relative humidity non condensing from 40 to 75 C Altitude Up to 2000 meters 7 CERTIFICATIONS AND COMPLIANCES CE Approved EN 61326 1 to Industrial...

Page 3: ...s short as possible 5 In extremely high EMI environments the use of external EMI suppression devices such as Ferrite Suppression Cores for signal and control cables is effective The following EMI suppression devices or equivalent are recommended Fair Rite part number 0443167251 RLC part number FCOR0000 TDK part number ZCAT3035 1330A Steward part number 28B2029 0A0 Line Filters for input power cabl...

Page 4: ...r any affirmation promise or representation with respect to the products The customer agrees to hold Red Lion Controls harmless from defend and indemnify RLC against damages claims and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its e...

Reviews: