GND

3

POWER SUPPLY REQUIREMENTS

The G304K requires a 12-28 VDC power supply. Please take care to observe

the following points:

- The wire used to connect the operator interface’s power supply should be

at least 22-gage wire. If a longer cable run is used, a heavier gage wire
should be used. The routing of the cable should be kept away from large
contactors, inverters, and other devices which may generate significant
electrical noise.

- A power supply with a Class 2 or SELV rating is to be used. A Class 2 or

SELV power supply provides isolation to accessible circuits from
hazardous voltage levels generated by a mains power supply due to
single faults. SELV is an acronym for “safety extra-low voltage.” Safety
extra-low voltage circuits shall exhibit voltages safe to touch both under
normal operating conditions and after a single fault, such as a
breakdown of a layer of basic insulation or after the failure of a single
component has occurred.

C

OMMUNICATING

W

ITH THE

G304K

The G304K has two serial ports combined into a single DB9-M connector. 

PC (RS-232)

PIN

SYMBOL

PLC (RS-232)

PC (RS-232)

PLC (RS-485)

4 wire

PLC (RS-485)

2 wire

1

Rx-

Data-

Rx-

2

Rx+

Data+

Rx+

3

Tx-

Tx-

4

Tx+

Tx+

5

GND

Signal Ground

6

TxD

Transmit

7

TxD

Transmit

8

RxD

Receive

9

RxD

Receive

DB9-M

PC CONNECTION

Configuration files are downloaded to the Kadet via the PC port, which can

be connected to a computer via various cables.

USB to Serial

PT# CBLUSB23 (includes CBLSK000)

Cable

PT# CBLSK000

PLC