background image

 

-2-

Bulletin No. G10-F

Released  2017-03-30

Drawing No. LP0909

 

MOUNTING INSTRUCTIONS

PANEL CUT-OUT

For hazardous location installation the following shall be taken into

consideration:

-  When used in a Zone 22 environment, the device shall be panel

mounted in at least Zone 22 IECEx/ATEX-Certified tool accessible
enclosure with a minimum ingress protection rating of at least IP64
as defined in IEC/EN 60529.

-  When used in a Zone 2 environment, the device shall be panel

mounted in at least Zone 2 IECEx/ATEX-Certified tool accessible
enclosure with a minimum ingress protection rating of at least IP54
as defined in IEC/EN 60529.

-  

This device is open-type and must be mounted in a suitable dust-

tight end-enclosure in accordance with articles 500 and 502 of the

NEC and positioned so only the face of the display is exposed.

-  Must be wired using Division 2 wiring methods as specified in article

501-4(b), 502-4(b), and 503-3(b) of the National Electric Code,
NFPA 70 for installation within the United States, or as specified in
section 19-152 of Canadian Electrical Code for installation in
Canada.

CONNECTING TO EARTH GROUND

Each operator panel has a chassis ground terminal on the back of the

unit. Your unit should be connected to earth ground. Steps should be
taken beyond connecting to earth ground to eliminate the buildup of
electrostatic charges.

The chassis ground is not connected to signal common of the unit.

Maintaining isolation between earth ground and signal common is not
required to operate your unit. But, other equipment connected to this unit
may require isolation between signal common and earth ground. 

To

maintain isolation between signal common and earth ground care must
be taken when connections are made to the unit.

 For example, a power

supply with isolation between its signal common and earth ground must
be used. Also, plugging in a USB cable may connect signal common and
earth ground.

1

1

 USB’s shield may be connected to earth ground at the host. USB’s

shield in turn may also be connected to signal common.

.87

(22.1)

2.95 (75)

1.48 (37.5)

2.95

(75)

VESA MOUNT (MIS-D 75) DIMENSIONS

10.197 (259.0)

7.931

(201.4)

4X R.10 (2.5)

MAX.

All tolerances ±.059" (±1.5 mm)

OPERATOR

 

INTERFACE

 

INSTALLATION

or a Limited Power Supply (LPS) according to IEC/EN 60950-1 or
Limited-energy circuit according to IEC/EN 61010-1.
Power connection via removable three position terminal block.

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: -20 to 60 °C, or lowest range among

equipment used in your Graphite system. Consult the user manual
or 

www.redlion.net/OpTemp

 for further details.

Storage Temperature Range: -20 to 70 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g
Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
Installation Category II, Pollution Degree 2 as defined in IEC/EN 60664-1.

CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant

ATEX Approved

 II 3 G Ex ic nA IIC T4 Gc
 II 3 D Ex tc IIIC T135°C Dc

DEMKO 14 ATEX 1387X

EN 60079-0, -11, -15, -31

IECEx Approved

Ex ic nA IIC T4 Gc
Ex tc IIIC T135°C Dc
IECEx UL 15.0035X

IEC 60079-0, -11, -15, -31

UL Listed: File #E302106
UL Hazardous: File #E317425
Type 4X Indoor / IP66 Enclosure rating (Face only) for all models
Type 4X Outdoor Enclosure rating (Face only) for G10Sxxxx models
IP20 Enclosure rating (Rear of unit)

ABS Type Approval for Shipboard Applications

CONNECTIONS

: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: One 14 AWG (1.63 mm) solid, 

two 18 AWG (1.02 mm) or four 20 AWG (0.81 mm)

CONSTRUCTION

: Cast aluminum enclosure with NEMA 4X/IP66 rating

when correctly fitted with the gasket provided. These devices have
only been evaluated for low risk of mechanical impact.

WEIGHT

: 4.8 lb. (2.18 Kg)

FOOT MAY BE REMOVED
FOR THICKER PANEL
INSTALLATIONS

This operator interface is primarily designed for

through-panel mounting. Four VESA mount tapped
screw-holes (M4 x 0.7, 5 mm deep) are present on the
rear of the panels to allow for stand or wall mounting.
Care should be taken to remove any loose material
from the mounting cut-out to prevent that material from
falling into the operator interface during installation. A
gasket is provided to enable sealing to NEMA 4X/IP66
specification. To maintain the IP66 rating of the panel,
an equivalently IP rated enclosure should be used.
Install the fourteen mounting clips provided and tighten
to 6.0 pound-force inch [96 ounce-force inch] (0.68 N m)
evenly for uniform gasket compression. 

Provisions should be made to prohibit the product

from being exposed to UV radiation while in use. Care
should be taken not to rub or buff the touchscreen
surface in a way that might cause the accumulation of
static charges.

Reviews: