Pulling the “L.S. CNT.” Input to Common with a mechanical or solid-state

switch increments the counter. The low pass filter (2.2 M

resistor and 0.0068

µf capacitor) used with a Schmidt trigger circuit debounces mechanical switch
signals. The switch load is 6 µA (max. voltage drop 0.5 V) when ON. The
OFF-state leakage current must be less than 2 µA.

Motor starter contacts, tungsten contacts, and brush-type contacts should

not be used.

The “H.S. CNT.” Input allows the CUB70 to operate at speeds up to 10 KHz

when driven by bi-polar outputs or external circuits having an output
impedance of 3.3 K

or less. Input drive voltage must be limited to 3 V

maximum to avoid damage to the counter. CMOS and TTL Logic outputs can
be loaded with a resistor (R

L

) to limit drive voltage, or a voltage divider can

be used as shown for the PNP O.C. Transistor output.

Note: The PSMA Power Supply and Interface Module

used for powering RLC sensors with CUB
Counters, has the proper interface output for direct
drive to the H.S. CNT.

CUB70 HIGH SPEED COUNT INPUT, 10 KHz MAX.

R values for

Fig 2 & 3

+V

R

+5 V

2.2 K

+12 V

10 K

+18 V

16 K

+24 V

24 K

TTL OR CMOS

PNP O.C. TRANSISTOR

NPN O.C.

OUTPUT

OR BI-POLAR OUTPUT

TRANSISTOR

FIG 1

FIG 2

FIG 3

7.

CERTIFICATIONS AND COMPLIANCES:

SAFETY

IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for

measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529
Type 4X Enclosure rating (Face only), UL50

ELECTROMAGNETIC COMPATIBILITY

Notes:

1. Burst to DC backlight power had a power line filter installed RLC

#LFIL0000 or equivalent at the unit.

2. Self-recoverable loss of performance during EMI disturbance at 10 V/rms

to backlight power lines.

LCD segments may flicker during EMI disturbance.

For operation without loss of performance:

Install power line filter RLC #LFIL0000 or equivalent at the unit. 

Refer to the EMC Installation Guidelines section of this bulletin for

additional information.

8. 

CONSTRUCTION:

High impact plastic case with clear viewing window.

The front panel meets NEMA 4X/IP65 requirements for indoor use when
properly installed. Installation Category I, Pollution Degree 2. Panel gasket
and mounting clip included.

9. 

WEIGHT:

2 oz. (57 grams) [with battery]

CUB7W L. S. INPUT, 30 CPS MAX.

The CUB7W accepts most machine control voltage signals. The input
accepts AC (50/60 Hz) or DC control voltages from 10 to 300 V at count
speeds up to 30 cps. The unit counts on the positive going edge of the input
signal.

WARNING

: Any lead may be at hazardous live input potential.

External wiring and devices connected to the unit must be

rated the same as applied signal input voltage and be

properly isolated from Class 2 or SELV circuitry.

EN 61000-4-2

Enclosure class B
Power mains class B

EN 55011

RF interference

Emissions to EN 50081-1

150 KHz - 80 MHz

Level 3; 10 V/rms 

2

EN 61000-4-6

RF conducted interference

Level 3; 2 Kv power

Level 4; 2 Kv I/O 

1

EN 61000-4-4

Fast transients (burst)

80 MHz - 1 GHz

Level 3; 10 V/m 

EN 61000-4-3

Electromagnetic RF fields

Level 3; 8 Kv air

Level 2; 4 Kv contact 

Electrostatic discharge

Level 4; 30 A/m
Level 3; 10 V/m

EN 61000-4-8
ENV 50204

Power frequency magnetic fields
Simulation of cordless telephone

200 Hz, 50% duty cycle

Immunity to EN 50082-2

900 MHz 

±

5 MHz

CUB70 LOW SPEED COUNT INPUT, 30 Hz MAX.