red lion CUB4RT Manual Download Page 3

3

WIRING CONNECTIONS

All conductors should meet voltage and current ratings of the unit. Also,

cabling should conform to appropriate standards of good installation, local
codes and regulations. It is recommended that power supplied to the unit be
protected by a fuse or circuit breaker.

Unit should be mounted in a relatively stable temperature environment. Avoid

drafts and areas subject to radical temperature shifts.

CUB4RT WIRING

Electrical

Connect RTD wires to Terminals EXC (#6), SIG+ (#3) and SIG- (#5) as

shown in the wiring diagram. Place jumper in appropriate position.

To minimize lead resistance effects, the three RTD wires should be the same

length, gauge, and material. Keep wire length to a minimum. Do not run RTD
signal wires with Class 1 wiring.

Connect the 9 to 26 VDC power to terminals VDC (#2) and COMM (#1),

observing the correct polarity. If more than one CUB4RT are powered from the
same supply, the probes must be isolated from each other. Normal operation
does not require use of the PROG terminal. However, a switch may be installed
between PROG (#4) and COMM (#1) if desired.

CUB4TC WIRING

Electrical

Connect thermocouple wires to terminals TC+(#3) and TC-(#5), observing

the correct polarity. Keep wire length to a minimum to reduce lead resistance
errors. Do not run thermocouple wires with Class 1 wiring.

Connect the 9 to 26 VDC power to terminals VDC(#2) and COMM(#1),

observing the correct polarity. If more than one CUB4TC are powered from the
same supply, the probes must be isolated from each other.

Note: Do not connect the power supply COMM terminal (#1) to the TC-

terminal (#5), as erroneous readings will result. Also be aware when using
grounded thermocouple probes that the probes’ protective sheath is electrically
connected to the measuring junction. If the protective sheath is connected to the
power supply common, this will connect terminals 1 and 5 together, which may
result in erroneous readings.

BASIC OPERATION

Normal operation begins with application of power to the meter. The unit will

begin a power up sequence that displays the version of the software and any
diagnostic messages. After approximately four seconds, the unit will begin to
display the temperature of the sensor or the millivolt input, depending upon
input type selected.

A diagnostic message of 

FAIL

may occur on power up. This message

indicates that the stored programming and/or calibration values may have
become corrupted. Pressing the “SEL” button will remove the current message
from the display.

Once the unit is displaying temperature or millivolts, the “SEL” button may

be pressed to display the type of input the unit has been programmed to display.
The display will return to normal indication after three seconds.

DIAGNOSTIC MESSAGES

FAIL

- indicates that a non-volatile memory fault has occurred. The operator

must acknowledge this message by pressing the “SEL” button before
proceeding to normal operation. Once the unit is in normal operation, the
messages 

FLPrG

and or 

FLCAL

will be periodically flashed on the display.

FLPrG

- indicates that non-calibration data is corrupt. This flashing display will

remain active even if power is removed and reapplied, until the unit is
reprogrammed. If the message appears on next power up after the unit has
been reprogrammed, it may indicate a nonfunctional memory component.

FLCAL

- indicates that calibration data is corrupt and nominal values will be used

to calculate the display value. This flashing display will remain active even if
power is removed and reapplied, until the unit is recalibrated. If the message
appears on next power up after the unit has been recalibrated, it may indicate
a nonfunctional memory component. The nominal values used to calculate
the input signal value may cause indication errors of up to 10% of full scale.
The unit should be recalibrated to restore normal display accuracy as soon as
possible.

PROGRAMMING

Programming may be entered at any time during normal operation. Entering

the Program Menu of the meter is accomplished by electrically connecting the
PROGRAM terminal to the COMM terminal with a wire or a switch.

Programming may be exited at any time except during calibration. Exiting the

Program Menu is accomplished by disconnecting the electrical connection
between the PROGRAM terminal and the COMM terminal. During exit of
programming, the unit displays 

SAVE

to indicate that the data is currently being

written to non-volatile memory.

All programming data is stored upon exit of programming. If power is

removed from the meter during exit of the Program Menu, data may not be
saved completely or correctly, and may cause a 

FAIL

message to occur during

the next power-up cycle. If power is removed before exiting the Program Menu,
all changes (including calibration information) will be lost and previous values
will be used upon power-up.

Programming the meter involves using the “SEL” and “blank” buttons to

traverse the Programming Menu and to select values for the corresponding
Programming Menu Items.

SEL: Steps to next Program Menu selection.
Blank: Scrolls through selection variables and enters into programming for

the selected value.

PROGRAM MENU - Selection Variables

typE-pt392

pt385

Ni672

Cu427

(CUB4RT Only)

To select the input type, press the blank button to scroll through the available

input types. Press “SEL” button to enter the choice and return to the main menu.

tYPE

t

E

J

K

r

S

b

n

, or 

LIN

(CUB4TC Only)

To select the input type, press the blank button to scroll through the available

input types. Press the “SEL” button to enter the choice and return to the main
menu.

CJC

YES

NO

(CUB4TC Only)

This program item enables or disables internal cold junction compensation.
Pressing the “blank” button toggles between Yes and No.
For most applications, cold junction compensation should be enabled (

yES

).

Press the “SEL” button to enter the choice and return to the main menu.
This menu item does not appear if 

tYPE

LIN

.

CAUTION

: To maintain the SELV rating of the CUB4TC, the

thermocouple probe should be isolated from any accidental
contact with hazardous voltage or non-SELV circuitry.

Jumper Positions

Summary of Contents for CUB4RT

Page 1: ...TC Backlight version 0 15 C Volt CJC error if powered from other than 12 VDC May be compensated with offset Example 24 VDC supply 24V 12V 0 15 C V 1 8 C Enter 1 8 C user offset 3 TEMPERATURE EFFECTS C...

Page 2: ...o 1400 F 1 9 WHITE YELLOW R 0 to 1768 C 32 to 3214 F 4 5 BLACK WHITE S 0 to 1768 C 32 to 3214 F 4 5 BLACK WHITE B 200 to 1820 C 300 to 3308 F 9 1 540 C 4 5 540 C GREY NONE E 200 to 787 C 328 to 1448 F...

Page 3: ...ges FLPrG and or FLCAL will be periodically flashed on the display FLPrG indicates that non calibration data is corrupt This flashing display will remain active even if power is removed and reapplied...

Page 4: ...ber or press the SEL button to wrap around to the LSD After the desired value is on the display press and hold the SEL button for three seconds to enter the value and return to the main menu CAL YES N...

Page 5: ...lay will read 00 000 to 20 000 ohms All other RTD types with the jumper in position B will cause the display to read 000 00 to 400 00 ohms Apply 105 000 mV wait 5 sec press SEL 105 000 mV IN8 Apply 90...

Page 6: ...reference temperature probe to measuring end of the CUB4TC thermocouple The two probes should be shielded from air movement and allowed sufficient time 15 minutes minimum to equalize in temperature A...

Page 7: ...the hole in the mounting clip 4 Install the unit through the panel cut out until the front bezel flange contacts the panel 5 Slide the mounting clip over the rear of the unit until the mounting clip i...

Page 8: ...after No warranties expressed or implied are created with respect to The Company s products except those expressly contained herein The Customer acknowledges the disclaimers and limitations contained...

Reviews: