PROGRAMMING EXAMPLE
As an example of a programming sequence, the following values, gained from
a temperature-time monitoring application, are programmed into the indicator.
DISPLAY: Display the actual temperature of a liquid solution in °F.
Activate alarm #1 output when temperature falls below 25°F, activate display
alarm. Peak and valley
(max/min)
readings for each cycle to be recorded.
TOTALIZER: When total exceeds 30,000 degree-minutes then latch alarm
#2 which stops the heating process and sounds a process complete bell.
Reset alarm #2 by remote input. Disable totalization when temperature
falls below 250°F. Reset the total from the front panel. Switch the display
from/to temperature and total.
SERIAL: Provide hardcopy printout of total, input and peak/valley when
operator actuates print request. Baud rate 300.
ANALOG RE-TRANSMISSION: Record temperature profile. 4 mA at
100°F and 20 mA at 400°F.
“Pro 1”.....“rtdtyP”
-
Enter 385
“SCALE”
-
Enter F
“dECPNt”
-
Enter 0
“Pro 2”.....“SLOPE”
-
Enter 1
“OFFSEt”
-
Enter 0
“Pro 3”.....“dSP AL”
-
Enter yes
“ENt AL”
-
Enter yes
“dSPHYS”
-
Enter no
“rSt AL”
-
Enter no
“dSPbUF”
-
Enter yes
“rStbUF”
-
Enter yes
“SELdSP”
-
Enter yes
“rSttOt”
-
Enter yes
“dSPOFF”
-
Enter no
“Pro 4”.....“FILter”
-
Enter 0
“E1-CON”
-
Enter 7 (reset alarm #2)
“E2-CON”
-
Enter 14 (print request)
“Pro 5”.....“tbASE”
-
Enter 1
“SCLFAC”
-
Enter 1.000
“Lo-cut”
-
Enter 250
“Pro 6”.....“trAc”
-
Enter no
“dISP”
-
Enter yes
“LAtC-1”
-
Enter no
“ASN-1”
-
Enter input
“AL-1”
-
Enter 250
“HYS-1”
-
Enter 1
“Act-1”
-
Enter LO
“LAtC-2”
-
Enter yes
“ASN-2”
-
Enter total
“AL-2”
-
Enter 30000
“HYS-2”
-
N/A
“Act-2”
-
Enter HI
“Pro 7”.....“bAud”
-
Enter 300
“AddrES”
-
Enter 0
“Print”
-
Enter 6
“FULL”
-
Enter yes
“Pro 8”.....“ASIN”
-
Enter input
“AN-Lo”
-
Enter 100
“AN-HI”
-
Enter 400