red lion APLCL Manual Download Page 3

3

CALIBRATION

Direct calibration in the signal loop is usually not practical due to the

difficulty in varying the measured parameter and the confusing interaction that
occurs between span and offset adjustments. However, the APLCL can be
quickly and easily bench calibrated using a commercially available current
calibrator or the calibration set-up shown below.

CALIBRATION PROCEDURE

The procedure outlined below, minimizes span/offset interaction and

simplifies calibration. In Steps 1, 2 and 3 the unit is 

“nulled”

to zero readout

with zero input signal current. In Steps 4 and 5, the span adjustments are made
to establish the required slope of the transfer curve.Then in Step 6, the transfer
curve is shifted up or down as required by setting the offset adjustments. In Step
7, the final 

“tweaking”

adjustments are made at minimum and maximum signal

current. Setting the decimal points in Step 8 completes the calibration.

Before calibrating, the READOUT SPAN (R

S

), SWING CURRENT (I

S

)

must be determined.

R

S

(Max. Numerical Display)

(Min. Numerical Display)

(Disregard Decimal Points)

I

S

(Current @ Max. Display)

(Current @ Min. Display)

Example

: Readout is to be 5.00 @ 4 mA and 15.00 @ 20 mA.

READOUT SPAN (R

S

) = 1500 

500 = 1000

SWING CURRENT (I

S

) = 20 mA 

4 mA = 16 mA

ADJUSTMENTS

1. Turn off all coarse offset and span adjustment switches 

(S2-S10 down)

.

S1 has no effect when zeroing and can be in either position.

2. Apply zero current by opening the external zero current switch. Adjust

the indicator to read zero using the fine offset adjustment 

(R.H. side,

front panel)

.

3. Close the external zero current switch and set the SWING CURRENT,

I

S

(16 mA in the example) 

by adjusting the power supply voltage and

the external fine adjust pot. Then, turn the fine span control 

(front, left)

to get a near zero reading 

(Adjustment fully CCW)

4. With the SWING CURRENT I

S

, applied to the input, set up a

combination of coarse span adj. switches 

(S6-S10)

to obtain a display

readout closest to the READOUT SPAN desired 

(1000 in the example)

.

Set the exact READOUT SPAN with the fine span adj. 

(front, left)

.

5. Repeat Step 2 to see if the zero value has shifted. If it has, re-zero with

fine offset 

(front, right)

, then repeat Step 3 and 4.

6. After the span has been adjusted, set the signal current to the minimum

level 

(4 mA in example)

. Then set the offset add/subtract switch 

(S1)

,

the coarse offset switches 

(S2-S5)

and the fine offset control 

(front,

right)

to obtain the readout corresponding to this minimum current

value 

(500 in the example)

.

7. Adjust the input signal current to its maximum value to see if the proper

readout is obtained 

(1500 @ 20 mA in the example)

. If the readout is

slightly off, adjust the fine span 

(front, left)

to obtain the true reading.

Then, recheck the reading at minimum input current 

(4 mA)

and

readjust fine offset 

(front, right)

if necessary. Repeat the maximum and

minimum readout adjustments until the unit displays the proper readout
at both extremes.

8. Set decimal points as desired using the three switches on the side of the

case and replace the front panel sealing screws. The unit can now be
installed.

APPLICATION EXAMPLES

Example 1:

An APLCL is to be calibrated to match a flow transducer whose

output is 10 mA @ 0 GPM and 50 mA @ 1375 GPM.

READOUT SPAN (RS) = 1375 

0 = 1375

SWING CURRENT (IS) = 50 mA 

10 mA = 40 mA

ADJUSTMENTS (Refer to the transfer curve below)

A Null the unit to zero readout @ 0 current per Steps 1, 2, and 3 of the

calibration procedure.

B  Set the coarse and fine span adjustments to get a readout of 1375 @ 40

mA per Steps 4 and 5. 

Note: With the full standard swing of 40 mA, the

coarse span switch reference markings can be used to determine
settings as follows:

S7 ON (1050) + S9 ON (260) = 1310 Span set with switches.
375 (needed) - 1310 (with SW’s) = 65 w. fine span adj.

C  Set offset to readout 0 @ 10 mA per

Step 6. 

Note: The readout observed

when the 10 mA min. current is first
applied can be used to determine the
offset switch settings.)

In this

example the readout will be 

(+)

344

when the 10 mA min. current is first
applied. Applying -344 offset then
reduces the readout to zero @ 10 mA.

D  Check readout at max. 

(50 mA)

and

min. 

(10 mA)

and fine tune 

(tweak)

as required per Step 7.

Example 2 (Negative Slope):

A level measuring device puts out 6 mA when

a storage tank is full and 15 mA when the tank is empty. The APLCL is to
readout 90.0 tons at full tank and zero when empty.

READOUT SPAN (RS) = 900 

0 = 900    (Disregard Decimal Points)

SWING CURRENT (IS) = 6 mA (@ max rdg) - 15 mA (@ min rdg) = -9 mA

In this case, the signal current is reverse [Term 3 

(-)

with respect to Term

(+)

] causing the readout to go 

“down” (increasingly negative)

as the

negative current increases.

ADJUSTMENTS

A  Null the unit per Steps 1, 2 and 3.
B  Set slope of transfer curve with span

adjustments to get readout of -900 @
-9 mA per Steps 4 and 5.

C  Move transfer curve up by applying

(+)

offset per Step 6 until readout is

+900 @ -6 mA.

D  Check extreme readings per Step 7,

0 readout @ -15 mA and +900
readout @ -6 mA.
Set D.P. Switch S1 and replace front
panel sealing screws.

Example 3 (± Display):

A differential pressure transducer has a range of

±1500 PSI with a 4 to 20 mA output 

(-1500 @ 4 mA, +1500 @ 20 mA)

.

READOUT SPAN (RS) = +1500 

(

1500) = 3000

SWING CURRENT (IS) = 20 mA(max) - 4 mA(min) = 16 mA

Note: Since the display readout is limited to 1999 numerical indication,

the full READOUT SPAN of 3000
cannot be obtained during zero
based span adjustment. However,
dividing both the READOUT SPAN
and SWING CURRENT by two, i.e.
1500 readout @ 8 mA, allows the
span adjustment to be made for the
proper transfer curve slope.

ADJUSTMENTS

A  Null the unit per Steps 1, 2, and 3.
B  Set transfer curve slope with span

adjustments per Steps 4 and 5, to get
a readout of +1500 @ 8 mA.

C  Apply 

(-)

offset per Step 6 to get a

reading of -1500 @ 4 mA.

D  Check min. and max. extremes and

tweak if required to get desired
readout @ 4 and 20 mA per Step 7.

MAX/MIN CHK.             OFFSET                SP

AN                      SETTING ZERO

Reviews: