R
EVISED
2016-01-19
15
Assigned_Name
Set STRINGI
This is the user assigned switch name.
17
Geographic_Location
Set STRINGI
This is the user assigned switch location.
The table below defines fault bits within the Status attribute of the Identity object.
Bit
Called
Definition
8
Minor Recoverable Fault
Power supply 1, Power supply 2, N-Ring Full, System, Port
utilization, Temperature, N-Link partner is down, N-Link
integrity fault
9
Minor Unrecoverable Fault
Configuration device error
10
Major Recoverable Fault
N-Ring partial low, N-Ring partial high, N-Ring multiple
managers, Boot loader version, N-Link partner port unknown,
N-Link multiple masters, N-Link control fault, N-Link
configuration fault
11
Major Unrecoverable Fault
none
N-Tron® Series 700/7000 Switch CIP™ Manual