A-8

INSTALLATION   

ZR-8

A-8

STANDBY POWER CONNECTIONS

The ZR-8 is suitable for temporary, standby, or emer-
gency power using the engine manufacturer

s recom-

mended maintenance schedule.

The ZR-8 can be permanently installed as a standby
power unit for 240V-3 wire, single phase 38 ampere
service.

(Connections must be made by a licensed electri-
cian who can determine how the 120/240V power
can be adapted to the particular installation and
comply with all applicable electrical codes.) The
following information can be used as a guide by
the electrician for most applications (refer also to
the connection diagram shown in Figure 1.)
-------------------------------------------------------------------------

1. Install a double pole, double throw switch between

the power company meter and the premises dis-
connect.

Switch rating must be the same or greater than the
customer

s premises disconnect and service over-

current protection.

2. Take necessary steps to assure load is limited to

the capacity of the ZR-8 by installing a 38 amp
240V double pole circuit breaker. Maximum rated
load for the 240V auxiliary is 38 amperes. Loading
above 38 amperes will reduce output voltage
below the allowable -10% of rated voltage which
may damage appliances or other motor-driven
equipment.

3. Install a 50 amp 120/240V plug (NEMA type 14-50)

to the Double Pole Circuit Breaker using No. 8, 4
conductor cable of the desired length. (The 50 amp
120/240V plug is available in the optional plug kit.)

4. Plug this cable into the 50 amp 120/240V recepta-

cle on the ZR-8 case front.

WARNING

AUXILIARY POWER WHILE WELDING

Simultaneous welding and power loads are permitted
by following Table I. The permissible currents shown
assume that current is being drawn from either the
120V or 240V supply (not both at the same time).
Also, the 

Output Control

 is set at 

10

 for maximum

auxiliary power.

TABLE I

SIMULTANEOUS WELDING AND POWER

Output Selector

Permissible Power

Permissible Auxiliary

Setting

Watts (Unity Power

Current in Amperes

Factor)

@ 120V 

*

-or- @ 240V

Max. Stick or Wire

Feed Setting

None

0

0

145 Stick Setting

3450

32

16

90 Stick Setting

6000

50

**

25

NO WELDING

9000

76

**

38

*

Each duplex receptacle is limited to 20 amps.

**

Not to exceed 40A per 120VAC branch circuit when  

splitting the 240 VAC output.

Summary of Contents for ZR-8

Page 1: ...safety in mind However your overall safety can be increased by proper installation and thoughtful operation on your part DO NOT INSTALL OPERATE OR REPAIR THIS EQUIPMENT WITHOUT READING THIS MANUAL AND...

Page 2: ...WEARERS SHOULD CONSULT WITH THEIR DOCTOR BEFORE OPERATING Read and understand the following safety highlights For additional safety information it is strongly recommended that you purchase a copy of...

Page 3: ...er for cooling 3 h Never simultaneously touch electrically hot parts of electrode holders connected to two welders because voltage between the two can be the total of the open circuit voltage of both...

Page 4: ...easily go through small cracks and openings to adjacent areas Avoid welding near hydraulic lines Have a fire extinguisher readily available 6 b Where compressed gases are to be used at the job site sp...

Page 5: ...appropri s et non inflammables 4 Des gouttes de laitier en fusion sont mises de l arc de soudage Se prot ger avec des v tements de protection libres de l huile tels que les gants en cuir chemise paiss...

Page 6: ...mportant when identifying the correct replacement parts On Line Product Registration Register your machine with Lincoln Electric either via fax or over the Internet For faxing Complete the form on the...

Page 7: ...ng Shutdown Instructions B 3 Starting the Engine B 3 Safety Precautions B 3 Stopping the Engine B 3 Break In Period B 3 Welding Process B 4 Stick Constant Current Welding B 4 TIG Constant Current Weld...

Page 8: ...40 Volts PHYSICAL DIMENSIONS Make Model Kohler CH23S Description 2 cylinder 4 Cycle Air Cooled Gasoline Engine Aluminum Alloy with Cast Iron Liners Electronic Ignition Operating Speed RPM High Idle 37...

Page 9: ...elder SPARK ARRESTER Some federal state or local laws may require that gasoline engines be equipped with exhaust spark arresters when they are operated in certain locations where unarrested sparks may...

Page 10: ...ner s Manual for specific oil recommendations BATTERY CONNECTIONS Use caution as the electrolyte is a strong acid that can burn skin and damage eyes This welder is shipped with the negative battery ca...

Page 11: ...M 200 255 Ft 61 0 76 2 M 225 Amps 100 Duty Cycle 1 AWG 1 AWG 1 0 AWG HIGH ALTITUDE OPERATION At higher altitudes Welder output de rating may be neces sary For maximum rating de rate the welder output...

Page 12: ...umes are properly vented to an outside area STACKING ZR 8 machines cannot be stacked CONNECTION OF LINCOLN ELECTRIC WIRE FEEDERS Shut off welder before making any electrical connec tions WIRE FEED CON...

Page 13: ...7 69 53 27 175 138 350 275 150 53 42 107 84 46 300 225 600 450 225 91 69 183 137 69 Maximum Allowable Cord Length in ft m for Conductor Size Conductor size is based on maximum 2 0 voltage drop 14 AWG...

Page 14: ...THOUT ADDITIONAL RESISTIVE TYPE LOADS Inductive Single phase induction motors These devices require large drills well pumps grinders small current inrush for starting refrigerators weed and hedge Some...

Page 15: ...um rated load for the 240V auxiliary is 38 amperes Loading above 38 amperes will reduce output voltage below the allowable 10 of rated voltage which may damage appliances or other motor driven equipme...

Page 16: ...NDUCTOR 40 AMP 240 VOLT DOUBLE POLE CIRCUIT BREAKER DOUBLE POLE DOUBLE THROW SWITCH RATING TO BE THE SAME AS OR GREATER THAN PREMISES SERVICE OVERCURRENT PROTECTION 50 AMP 120 240 VOLT PLUG NEMA TYPE...

Page 17: ...e receptacles the engine will accelerate to high speed If no power is being drawn from the receptacles and not welding for 10 14 seconds the idler reduces the engine speed to low idle B 1 OPERATION ZR...

Page 18: ...Polarity switch setting while welding This will damage the switch B 2 OPERATION B 2 ZR 8 CAUTION CAUTION KOHLER 23 H P COMMAND 4 Gallons Hour 1 5 Liters Hour 7 Gallons Hour 2 8 Liters Hour 1 2 Gallon...

Page 19: ...oads and allow engine to run at low idle speed for a few minutes to cool the engine Stop the engine by placing the Engine switch in the OFF position A fuel shut off valve is not required on the ZR 8 b...

Page 20: ...with the ZR 8 on high idle to maintain satisfactory operation It can be used in the AUTO position but the delay going to flow idle after welding is ceased will be increased if the AFTER FLOW CONTROL...

Page 21: ...INTERNAL CONTACTOR contactor closes Welding starts immediately and engine goes to high idle NOTE Output Control must be set above 3 TIG TIG MODULE WITH Yes High Cold Press Arc Start Switch WITH CONTA...

Page 22: ...e head shield with No 12 filter GC300 work clamp and Cooltong 300 electrode holder Cables are rated at 400 amps 100 duty cycle K875 ACCESSORY KIT For Stick welding Includes 20 ft 6 1m 6 electrode cabl...

Page 23: ...des cold electrode until gun trigger is pressed Includes gas solenoid Magnum Gun and Magnum Gun Connector Kit are required for gas shielded welding Innershield Gun is required for gasless welding TIG...

Page 24: ...high temperature and other severe operating conditions Refer to the maintenance section of the Engine Owner s Manual for more information NOTE Engine life will be reduced if the oil and oil filter are...

Page 25: ...ter socket tool to tighten the filter an additional 1 2 to 7 8 turn 5 Refill the crankcase with the specified amount of the recommended oil Reinstall the oil filler cap 6 Start the engine and check fo...

Page 26: ...nd then the positive battery cable before attaching the charger leads Failure to do so can result in damage to the internal charger components When reconnecting the cables connect the positive cable f...

Page 27: ...beled POSSIBLE CAUSE lists the obvious external possibilities that may contribute to the machine symptom Step 3 RECOMMENDED COURSE OF ACTION This column provides a course of action for the Possible Ca...

Page 28: ...en in miscellaneous leads 2 Open lead in flashing or field circuit 3 Faulty rotor 4 Faulty Potentiometer R1 5 Faulty stator Field winding 6 Faulty Field rectifier D2 7 Faulty P C Board 1 Idler switch...

Page 29: ...er Engine will not crank or is hard to crank Engine shuts down Engine does not develop full power Engine is hard to start 1 No voltage signal from the current sensor 2 Auxiliary power load less than 1...

Page 30: ...ce only It may not be accurate for all machines covered by this manual The specific diagram for a particular code is pasted inside the machine on one of the enclosure panels If the diagram is illegibl...

Page 31: ...m moving parts Only qualified personnel should install use or service this or service this equipm equipment M20266 A 02 TO WORK ELECTRODE TO ENGINE WELDER W WORK LN LN 15 OR 25 WIRE F RE FEEDER TO W W...

Page 32: ...OHLER M20267 C 01 26 59 30 27 9 09 9 09 17 00 21 22 8 80 30 00 42 00 22 15 10 33 CENTER OF GRAVITY WITH OIL IN ENGINE AND FULL FUEL TANK 9 31 CENTERLINE OF SHAFT 9 59 10 19 OIL FILTER REMOVAL NOTE CAS...

Page 33: ...electrically live parts or electrode with skin or wet clothing Insulate yourself from work and ground No toque las partes o los electrodos bajo carga con la piel o ropa moja da Aislese del trabajo y...

Page 34: ...e Be und Entl ftung des Arbeitsplatzes Mantenha seu rosto da fuma a Use ventila o e exhaust o para remover fumo da zona respirat ria Turn power off before servicing Desconectar el cable de ali mentaci...

Page 35: ...and Service through Subsidiaries and Distributors Worldwide Cleveland Ohio 44117 1199 U S A TEL 216 481 8100 FAX 216 486 1751 WEB SITE www lincolnelectric com World s Leader in Welding and Cutting Pr...

Reviews: