Red Arrow Slimline POLO POL14LEDEMS Installation Instructions Manual Download Page 5

Red Arrow Trading

Elsworth House, Herries Road South, Sheffield, S6 1QS

T:

 0800 195 0006     

F:

  0870  043  3946      

E:

 [email protected]      

www.redarrowtrading.com

14W LED Emergency 
Slimline POLO Bulkhead 
with Microwave Sensor 

Installation Instructions p.5

For models: POL14LEDEMS

The LED setting indicator will flash to indicate the setting selected as follows: 

3.

 

LUX

Rotate the dial to control the ambient light level at which the sensor will allow the lamps to switch on. This range from 
two lux minimum (fully anti-clockwise) to only switch on when very dark, through to 2000 lux maximum (fully clockwise) 
to always switch on regardless of ambient light. Note that the fully clockwise setting should be used to check functionality 
on initial installation. 

No. of Flashes Setting Length
1

10 seconds

2

1 minute

3

2 minutes

4

5 minutes

5

8 minutes

6

10 minutes

7

15 minutes

8

20 minutes

9

25 minutes

10

30 minutes

Ratings

Power supply 

220-240V AC 5/60Hz

Transmission Power  <10mW
Rated  Load  

1200W

Power Consumption  0.9W approx. 

Fault Finding

If you are experiencing a problem please check through the following before making contact with our Customer Services 
Department:

Fault - Load does not come on

 Check to see if the live supply to the circuit is working. 

 If the supply & wiring are good, check the LUX setting. Increase the LUX level setting to allow the sensor to turn on at 

   a higher ambient light level (rotate dial clockwise).

Fault - Load does not go off

 Ensure that the area is left unoccupied for longer than the selected timer setting.

 Make sure that the sensor is not adjacent to circulating air, heaters or lamps. 

 If the unit “false triggers” reduce the DISTANCE level to narrow the area of detection (rotate dial anti clockwise).

Summary of Contents for Slimline POLO POL14LEDEMS

Page 1: ...il it locks into position Reconnect power supply check for correct operation Luminaires fitted with electronic ballasts are exempt from insulation resistance tests as this may cause damage to the ballast Red Arrow Trading Elsworth House Herries Road South Sheffield S6 1QS T 0800 195 0006 F 0870 043 3946 E sales redarrowtrading com www redarrowtrading com Description of Microwave Sensor The microwa...

Page 2: ... any high voltage or insulation resistance testing otherwise irreparable damage will occur to luminaire components When the lamp operates from the battery supply it will be at a reduced light level so ensure cleanliness of luminaires is maintained so as not to affect performance To maintain full operational status spare lamps should be held for immediate changing in case of failure TESTING FOR EME...

Page 3: ...s for the annual test at all stages of equipment life TESTING LOG BOOK Luminaire Type Luminaire Location No 14W LED Emergency Slimline POLO Bulkhead with Microwave Sensor Installation Instructions p 3 For models POL14LEDEMS Month Test Year 1 Year 2 Year 3 Year 4 Year 5 signed date signed date signed date signed date signed date 1 FUNCTIONAL 2 FUNCTIONAL 3 FUNCTIONAL 4 FUNCTIONAL 5 FUNCTIONAL 6 FUN...

Page 4: ...n front of the sensor head These sensor kits are capable of switching controlling more than one luminaire in a master slave set up This is done by linking non sensored fittings slaves to the one with the sensor fitted master using the live output from the sensor NOTE DO NOT link other fittings containing MW sensors together in this way as it can cause false triggering of the sensors 14W LED Emerge...

Page 5: ...es Setting Length 1 10 seconds 2 1 minute 3 2 minutes 4 5 minutes 5 8 minutes 6 10 minutes 7 15 minutes 8 20 minutes 9 25 minutes 10 30 minutes Ratings Power supply 220 240V AC 5 60Hz Transmission Power 10mW Rated Load 1200W Power Consumption 0 9W approx Fault Finding If you are experiencing a problem please check through the following before making contact with our Customer Services Department Fa...

Page 6: ...king environment or installation not according to the current edition of the I E E Wiring Regulations BS7671 The guarantee is also invalidated if the luminaire has been Mega tested Should this product fail during the guarantee period it will be replaced free of charge subject to correct installation and return of the faulty unit We do not accept responsibility for any installation costs associated...