Documentation RM-BV4 Micro DP
RDN 10000662
15
24.01.2014
7 Troubleshooting
Fault
Possible causes
Recommended action
No display text message
-
No mains voltage
-
Check the power supply
-
Fuse in device defective
-
Replace fuse
-
System EMERGENCY-STOP
actuated
-
Check EMERGENCY-STOP
No valve activity and text
message "Alarm valve #"
-
Wiring to valves interrupted
-
Check cables and electrical
connections
-
Solenoid defective
-
Replace coil
No valve activity and text
message "Cleaning stop"
-
Cleaning stopped via the
"Start / Stop" input
(terminals7, 8).
-
Input „Start / Stop“ bridge
terminals 7, 8.
No downtime cleaning
-
Parameter 04 = 0
(downtime cycles)
-
Set parameter 04
"Downtime cycles" to another
value
-
No signal from the fan control
present
-
Apply signal to input „Start /
Stop“ terminals 7, 8.
Cleaning not effective
-
Interval too long
-
Set parameter 03 "Interval 1"
to a lower value
-
Pressure too low
-
Pressure to 6 ... Set pressure
to 8 bar (min. 5 bar)
-
Set parameter 03 "Interval 1"
to a higher value
-
Valve defective
-
Check / replace valves
-
Pulse time too short
-
Set parameter 02 “Pulse
time” to higher value