Reason Tecnologia S.A.
14
4
Installation
4.1
Mounting
RT411 has been designed to be mounted in a standard 19-inch rack using four M6x15 screws to affix. Allow
adequate clearance for all connections.
In particular, the optical fiber cables should be installed respecting a minimum bend radius of 30 mm.
For more information about dimensions of the equipment, see Chapter
4.2
Environment
Temperature and relative humidity should not exceed the limits stated in Chapter
. We recommend providing
appropriate heating or cooling measures to ensure that these limits are respected at all times.
4.3
Power Supply
The equipment can be powered from DC or AC power within the limits specified in Chapter
All power connections should use insulated flameproof flexible cable (BWF type) with a 1.5 mm
2
cross section,
70
◦
C thermal class, and 750 V insulation voltage.
To reduce the risk of electrical shock, pre-insulated tubular pin terminals should be used in the ends of power
connections.
Figure 5: Pre-insulated tubular pin terminals
The pin terminals should be completely inserted into the connectors supplied with the equipment, so that no
metallic parts are exposed. Refer to the figure below to insert it correctly.
A 1.5 mm
2
ground lead shall be connected to the terminal marked with the protective earth symbol for safety.
For optimal electromagnetic compatibility, ground the equipment by using a 10 mm wide grounding strap to
connect the frame of the equipment to a good ground point on the mounting rack.
RT411 - User Manual
[rt411-manual-en rev 1.1]