B.  VENTING SYSTEM

. The venting system consists of a chimney connector and a chimney, these 

get extremely hot during use. To protect against the possibility of a house fire, the chimney connector 
and chimney must be properly installed and maintained. A thimble must be used when a connection 
is made through a combustible wall to a chimney. A chimney support package must be used when a 
connection is made through the ceiling to a prefabricated chimney. These accessories are necessary 
to provide safe clearances to combustible wall and ceiling material.

C. CHIMNEY CONNECTOR

. The chimney connector must be 6” 

in diameter, 24-gauge minimum carbon steel. Do not use alu-
minum or galvanized steel. They cannot properly withstand the 
extreme temperatures of a coal fire. Do not use chimney connec-
tor pipe as a chimney. You must connect your stove to a chimney 
comparable to those illustrated in this manual.  
Chimney connector sections must be attached to the stove and 
to each other with the crimped end toward the stove [See Figure 
10:1.] All joints should be secured with three sheet metal screws.
For proper operation, the chimney connector should be as short 
as possible. Horizontal lengths of chimney connector should 
have an upward slope from the stove of ¼” per foot.
Maintain 18” clearances between the chimney connector and the 
wall and ceiling unless a wall protection system is installed.

Toward

Stove

Flue Gas

Direction

PREVENT HOUSE FIREW

INSTALL AND USE ONLY IN ACCORDANCE WITH THE

MANUFACTURES INSTRUCTIONS AND LOCAL BUILDING CODES

READING STOVE COMPANY

POTTSVILLE, PA 17901

1-800-654-7792

STOkER STOVES

 

MODEL: 

RS-96-S 

FUEL: ANTHRACITE RICE COAL

 

 

 

RS-96-S

 

 

 

RS-96-S

U.S. ENVIRONMENTAL PROTECTION AGENCY

THIS HEATER IS ONLY FOR BURNING COAL.  USE OF ANY OTHER SOLID FUEL

EXCEPT FOR COAL IGNITION PURPOSES IS A VIOLATION OF FEDERAL LAW.

CONAM Inspection, Inc., Auburn, MA 01501 

STL-002

CHIMNEY TYPE: MINIMUM & INCH DIAMETER APPROVED LOW HEAT RESIDENTIAL TYPE ALL FUEL – CHIMNEY

CONNECTOR: 6 INCH DIAMETER 24 GAUGE BLUE OR BLACk STEEL.  INSTALL AT LEAST 18 INCHES FROM CEILING.

SPECIAL METHODS ARE REQUIRED WHEN PASSING THROUGH WALLS OR CEILING.  SEE INSTRUCTIONS AND BUILDING CODES

SERIAL 

N

O. 

6618

FREESTANDING MODE

INSTALL WITH MINUMUM CLEARANCE TO WALLS AS SHOWN (IN INCHES)

CONTACT YOUR LOCAL BUILDING OR FIRE OFFICIALS ABOUT

RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA

REAR WALL

FRONT

STOVE

18”

18”

18”

18”

18”

18”

8”

8”

CORNER INSTALLATION

FRONT

STOVE

FR

ONT

ST

OVE

USE APPROVED

FLOOR PROTECTION

FLOOR PROTECTION

Fig. 10:1 Chimney Connector sections

Summary of Contents for Swatara CS-85

Page 1: ...ANTHRACITE COAL STOVE CS 85 Owners Manual...

Page 2: ...e 8 Reduced Wall Clearances 9 Floor Protector 9 Venting system 9 Chimney Connector 9 Connection to a Masonry Chimney 10 Connection to a Masonry Fireplace 10 Connection to a Metal Prefabricated Chimney...

Page 3: ...nd through 1 3 8 B THE CS 85 CUT AWAY VIEW 1 PRIMARY AIR 2 SECONDARY AIR 3 ASH COLLECTION CHAMBER 4 ASH PAN 5 GRATES 6 SHAKER HANDLE 7 LOADING DOOR TRANSPARENT 1400 F WINDOW 8 FIREBRICK 9 FLUE COLLAR...

Page 4: ...of genuine Reading Stove Company parts may compromise the performance the warranty and even the safety of your stove Grates The grate system of the Reading Stove Company CS85 consists of two cast iron...

Page 5: ...hat there is sufficient capture and radiation of heat to maintain combustion It is also important that the coal bed is of constant thickness A hole or thin area will allow combustion air to bypass the...

Page 6: ...nstall and does not require a draft gauge and tire for set up The 6 Model R C will fit in the side leg of a standard single wall black tee connector See Figure 5 1 The tee may be positioned anywhere w...

Page 7: ...See Figure 6 2 Setting R C Barometric Dampers Turn the ad justment weight counter clockwise to loosen and slide it along the slotted channel to the proper position and tighten The bracket is marked 2...

Page 8: ...fe chimney installation Use only components manufactured for the chimney FLOOR PROTECTOR 1l4 Mineral board or equivalent Measurements 8 beyond the sides and back 18 beyond the front Total Dimensions 4...

Page 9: ...allow for neces sary clearance Review Figures 8 1 and 8 2 for MINIMUM clearances MINIMUM CLEARANCES SHOWN IN FIGURES 8 1 and 8 2 ARE TO PREVENT WALLS AND CEILINGS FROM CATCHING FIRE Keep furniture dra...

Page 10: ...tal lengths of chimney connector should have an upward slope from the stove of per foot Maintain 18 clearances between the chimney connector and the wall and ceiling unless a wall protection system is...

Page 11: ...is manual Local building authorities may be consulted or NFPA 211 may be used for additional methods of chimney connection Also listed prefabricated metal thimbles can be bought for use with coal stov...

Page 12: ...ce through the ceiling and the roof See Figures 17 1 and 17 2 The other method is to install an exterior chimney that runs up the outside of the residence See Figures 18 1 and 18 2 The com ponents ill...

Page 13: ...ction 18 Fig 17 1 Metal Chimney Installation throughg the Ceiling and Roof Fig 17 2 Detail of Connection Install an attic insulation shield to main tain specified clearance to insulation In sulation i...

Page 14: ...Cap Storm Collar Roof Flashing Floor Protection 18 Maintain 2 Clearance Fig 18 1 Metal Chimney Installation throughg the Ceiling and Roof This method of installation requires at a minmum a wall pass t...

Page 15: ...1 When the dial is turned all the way to the right the setting is high burn When the dial is turned all the way to the left allowing just the slightest opening the setting is low burn A 1 The Shaker...

Page 16: ...ing add more layers of coal without exceeding maximum capacity B 10Choke back air to create slower burn and heat C Refueling It is recommended that you wear gloves whenever working with a hot stove C...

Page 17: ...out door E 3 d Carry the ash pan out of the house Remember it contains hot ashes and most likely some red hot coals Place the ashes in a metal container away from combustibles E 3 e Re open the ash cl...

Page 18: ...s Reading Stove Company assumes no responsi bility for any labor expenses for service removal or reinstallation If defective in material or workmanship and if removed by the owner within the warranty...

Page 19: ...ential damages for breach of any written or implied warranty is disclaimed and excluded here from Some states do not allow the exclusion or limitations of incidental or consequential damages so the ab...

Page 20: ...NIT INFORMATION Model Number CS 85 Swatara Purchase Date Serial No Important Notice This registration information must be on file for this warranty to be valid Please mail this information within thir...

Page 21: ......

Reviews: