F8 - Led bar mode
The red LED shows the current value of the function:
-
if the red LED is lit the LED bar shows the level of the regulated output
-
if the red LED is off the LED bar shows the level of the proportional output
Press
SET
key to set the desired value.
To select following function press
ENTER
key.
F9 - Thermal probe exclusion
The red LED shows the current value of the function:
-
if the red LED is lit the temperature compensation is disabled (the probe is excluded)
-
if the red LED is off the temperature compensation in enabled (the probe is active)
Press
SET
key to set the desired value.
To select following function press
ENTER
key.
It is recommended to exclude the probe when the ambient temperature is between 15° and 25°C or in case
of probe malfunctioning.
F10 - Exit menu saving the data
To return to function F1 press ENTER and SET simultaneously.
To exit the programming menu and save the changes, hold down ENTER for several seconds.
If there are no errors the LED bar lights scroll and the green LED starts flashing again. If errors are
found the LED bar keeps flashing and the changes are not saved. Press SET to stop the flashing, go
back into the programming menu and repeat the calibration. If the error persists, contact the
technical support team.
Reset
To reset the sensor hold down ENTER and SET for several seconds while the sensor is outside the
programming menu
. The LED bar lights will scroll and the function values are returned to the factory
settings.
If the LED bar keeps flashing after a reset, contact the technical support team.
Attention
: If during ultrasonic sensor functioning something goes wrong reset functions and
calibrate the instrument again. Whenever problems do not disappear please get in touch with our
technical assistance office.