background image

Installation Instructions

The 10-175UL should be installed in accordance with article 760 of The National Electrical
Code or NFPA 72 as well as all applicable Local Codes.

See Terminal Identification Chart on page 4 for a description of each terminal function.

1.

Mount the 10-175UL in desired location.

2.

Connect AC power (115VAC 60Hz) to the black and white flying leads of the trans-

former. Secure green wire lead to earth ground. Use 18 AWG or larger for all power
connections (Battery, DC output). Use 22 AWG to 18 AWG for power limited circuits
(trigger inputs, dry outputs).

Keep power limited wiring separate from non-power limited wiring (115VAC/ 60Hz
Input, Battery Wires). Minimum .25” (6.4mm) spacing must be provided.

3.

Set the 10-175UL to the desired DC output voltage by setting switch SW1 to the appro-

priate position (power supply output specification table).

Note: It is good operating practice to measure and verify output voltage before con-
necting devices to ensure proper operation of equipment.

4. 

Connect battery to terminals marked [+ BAT -] (battery leads included). Use two (2)

12VDC batteriesconnected in series for 24VDC operation.

Note: For Access Control applications, batteries are optional. When batteries are
not used a loss of AC will result in the loss of output voltage. When the use of stand-
by batteries are desired, they must be lead acid or gel type.

5. 

Connect appropriate signaling notification devices to AC Fail supervisory relay outputs

marked [N.C., N.O., C].

Note: To meet UL requirements, AC Supervisory outputs must be connected to the
zone of Alarm Control Panel or to visual AC trouble indicator.

6.  For Access Control Device & Fire Alarm Interface connections refer to desired

Application Diagrams (pg. 6-8) and Terminal Identification Chart

Maintenance

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test

:  Under normal load conditions, the DC output voltage should be

checked for proper voltage level (see power supply output specifica-
tions chart).

Battery Test

Under normal load conditions check that the battery is fully charged,

check specified voltage both at battery terminal and at the board ter-
minals marked [- BAT +] to insure there is no break in the battery
connection wires.

Note: Maximum charging current under discharges is 0.40 amps.

Note: Expected battery life is 5 years, however it is recommended changing batteries in

4 years or less if needed.

3

Summary of Contents for 10-175UL

Page 1: ...10 175UL Access Control Power Supply Charger Installation and Specifications Manual 10 175UL Power Supply I N S T A L L A T I O N ...

Page 2: ...t of Buildings 18 98 E NFPA 101 Life Safety Input 115VAC 60 Hz 6 amps Switch selectable 12VDC or 24VDC power limited output 1 75 amps continuous supply current 12VDC or 24VDC Latching fire alarm tie in with manual reset Filtered and electronically regulated output Charge current 0 4 amps Max Aux relay output form C 1 amp 28VDC AC Fail output relay form C 1 amp 28VDC Enclosure Dimensions 15 5 H x 1...

Page 3: ...series for 24VDC operation Note For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries are desired they must be lead acid or gel type 5 Connect appropriate signaling notification devices to AC Fail supervisory relay outputs marked N C N O C Note To meet UL requirements AC Superviso...

Page 4: ... dry Form C contacts Shorting TRG1 and TRG2 together causes these contacts to switch They are typically used for controlling mul tiple 10 175ULs with fire alarm tie in Fig 4 and Fig 5 pg 7 8 AUX Continuous positive DC power output voltage It is not affected by TRG1 TRG2 operation COM Common negative output ground FACP Spare wiring terminal used for fire alarm tie in application Fig 1 pg 6 BAT BAT ...

Page 5: ...2 SW1 CLOSED 24V OPEN 12V NC C NO AC FAIL XFMR Green Lead ground Stand by Battery optional Constant output not affected by trigger Switched DC output trigger control Black Lead White Lead 115VAC input 60 Hz 6 amps AC DC JUMPER Reset Switch AC Power LED AC Molex Connector 5 ...

Page 6: ...m 4 50 114 3mm 1 50 38 1mm 4 50 114 3mm 4 50 114 3mm 1 50 38 1mm 1 25 31 8mm 1 25 31 8mm 4 50 114 3mm 0 94 23 8mm 0 88 22 2mm 0 88 22 2mm 9 88 250 8mm 12 00 304 8mm 15 50 393 7mm Enclosure Dimensions FIG 1 Typical mag lock with fire alarm tie in using aux output installation FIG 2 Multiple 10 175 power supply connections 6 ...

Page 7: ... Typical Single Mag lock or door strike installation with fire alarm tie in using trigger controlled output FIG 4 Typical dual mag lock installation with fire alarm tie in using trigger controlled outputs 7 ...

Page 8: ...om terminals Output voltage is not correct for the con nected equipment Trouble output relay is de energized Relay terminals are labeled shown in the Normal energized no trouble condition Relays are energized when no trouble is detected For Technical Support 1 800 265 6630 or 519 621 7651 www rutherfordcontrols com 2007 RUTHERFORD CONTROLS INT L CORP WWW RUTHERFORDCONTROLS COM USA 2697 INTERNATION...

Reviews: