RCF PL 68EN User Manual Download Page 4

6

ENGLISH

RCF S.P.A. THANKS YOU FOR PURCHASING THIS PRODUCT, WHICH 
HAS BEEN DESIGNED TO GUARANTEE RELIABILITY AND HIGH 
PERFORMANCE. 

DESCRIPTION

PL 68EN is a ceiling loudspeaker in compliance with EN 54-24 standard. 
It is equipped with a fire protection steel dome and can be installed into 
false ceilings (flush-mounted).

Main features:

 

-

High quality voice reproduction.

 

-

Steel construction with metal protection grille.

 

-

Fire protection dome with an attachment system that ensures quick 
installation.

 

-

Dual cone 6” loudspeaker.

 

-

Transformer for connection to 100 V (/ 70 V) constant voltage lines.

 

-

Power selection among three values.

 

-

Ceramic terminal strip.

 

-

Thermal fuse that prevents damage to the audio line due to heat on 
the loudspeaker.

WARNING:

 Make sure that the loudspeaker is installed in a stable and secure 

way in order to avoid any conditions that may be dangerous for persons or 
structures.
Ensure the support surface (e.g. the false ceiling) has the necessary mechanical 
characteristics to support the weight of the loudspeaker.
Before installing the loudspeaker, carefully check all components to be used 
and make sure there is no damage, deformation, corrosion and/or missing or 
damaged parts that could reduce the safety of the installation.
In outdoor use, avoid installing the loudspeaker in places exposed to harsh 
weather conditions.
The PL 68EN is designed for flush-mount installation (into false ceilings).
Before installing loudspeakers, make sure there is sufficient space behind 
the false ceiling: with respect to the support surface of the loudspeaker front 
flange, at least an empty space 130 mm (about 5”) deep is necessary.

Loudspeaker connections should be only made by qualified and experienced 
personnel having the technical know-how or sufficient specific instructions to 
ensure that are made correctly and prevent any electrical danger.
To prevent any risk of electric shock, do not connect loudspeakers when the 
amplifier is switched on. Before turning the system on, check all connections 
and make sure there are no accidental short circuits. The entire sound system 
shall be designed and installed in compliance with the current local laws and 
regulations regarding electrical systems. 

INSTALLATION AND CONNECTIONS

Summary of Contents for PL 68EN

Page 1: ...USER MANUAL MANUALE D USO PL 68EN FLUSH MOUNT CEILING LOUDSPEAKER IN COMPLIANCE WITH EN 54 24 STANDARD DIFFUSORE ACUSTICO PER CONTROSOFFITTO CONFORME ALLA NORMA EN 54 24...

Page 2: ...stepped on or crushed by objects 5 Make sure that no objects or liquids can get into this product as this may cause a short circuit 6 Never attempt to carry out any operations modifications or repairs...

Page 3: ...d levels is being used it is necessary to wear ear plugs or protective earphones See the technical specifications in the instruction manual for the maximum sound pressure the loudspeaker is capable of...

Page 4: ...loudspeaker Before installing the loudspeaker carefully check all components to be used and make sure there is no damage deformation corrosion and or missing or damaged parts that could reduce the saf...

Page 5: ...e hole previously drilled and then release its springs to fix it to the false ceiling 1 2 2 Insert the cable into the fire dome and connect both the 100 V 70 V line and the earth wire to the ceramic t...

Page 6: ...1 5 W at 100V on the loudspeaker transformer by linking the red wire to the proper terminal If the line is 70 V the power will be halved Connect the black wire to the transformer COM terminal 5 Link t...

Page 7: ...sure a correct sound reproduction Always use cables having wires with an adequate cross section considering the cable length and the total loudspeaker power Loudspeaker lines must be kept separated fr...

Page 8: ...E COLOUR CONNECTOR FALSE CEILING CUTOUT SIZE NET WEIGHT OPERATING TEMPERATURE DIMENSIONS 100 V 70 V 6 W 3 W 1 5 W power values are halved at 70 V 1 67 k 3 33 k 6 67 k 130 Hz 20 kHz 10 dB 94 dB 1 W 1 m...

Page 9: ...anzio 13 42124 Reggio Emilia ITALY 14 1488 CPR 0486 W EN 54 24 2008 PL 68EN Type A DoP 012_14 Other technical data see operational manual Loudspeaker for voice alarm systems for fire detection and fir...

Page 10: ...RCF Germany tel 49 2203 925370 e mail germany rcf it RCF Spain tel 34 91 817 42 66 e mail info rcfaudio es RCF Belgium tel 32 0 3 3268104 e mail belgium rcf it RCF USA Inc tel 1 603 926 4604 e mail i...