68
11 - INSTALLATION - CATEGORY IV: Vent and combustion air
11.8.1 - Polypropylene air
intake connection
Combustion Air Intake connection
(see Figure 11-13 Item “M”) is used to
provide combustion air directly to the
appliance from outdoors. Combustion
air piping must be supported per
guidelines listed in the National
Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
To connect a polypropylene pipe to
the air intake connection proceed as
follows while referring to Figure 11-13:
1.- Install appliance adapter “P” (Field
provided) above exit “M” using
gasket “D” and bolts “E”;
2.- Insert vent pipe “N”, into adapter
“P”, following instruction of
polypropylene pipe manufacturer.
11.8.2 - Polypropylene
vent connection
Vent connection (Figure 11-13 item
“C”) is used to provide a passageway
for conveying combustion gases
to the outside. Vent piping must be
supported per the National Building
Code, Section 305, Table 305.4 or as
local codes dictate.
To connect a polypropylene pipe
to the vent connection proceed as
follows while referring to Figure 11-13:
1.- Install appliance adapter “B” (Field
provided) above exit “C” using
gasket “D” and bolts “E”;
2.- Insert vent pipe “G”, into adapter
“B”, following instruction of
polypropylene pipe manufacturer.
WARNING!!!
Do not
cover with thermal insulation
polypropylene exhaust pipe nor
install into an enclosure, closet,
alcove or any other obstruction
thereby preventing the cooling
of the exhaust pipe. Failure to
follow this warning could result
in excessive levels of carbon
monoxide or a fire, which can
result in severe personal injury
or death!
Figure 11-13 - Polypropylene
air intake/vent connection
Figure 11-14 - Polypropylene
air intake/vent connection
correctly in place
Extend the
flue exhaust
pipe to
outside
building
020010.01.016
Extend the
air intake
pipe to
outside
building
A = MOMENTIVE - RTV 106
high temperature silicone (or
equivalent) (Field provided)
B = Flue exhaust adapter for
PVC/CPVC pipe
C = Flue exhaust connection
D = Gasket
E = Fixing screws
F = Mechanically secure clamp
G = PVC/CPVC exhaust pipe
(Field provided)
H = Combustion analization
probe (Field installed)
L = Cap (Field provided)
N = PVC/CPVC air inlet pipe
(Field provided)
P = Air intake adapter for PVC/
CPVC pipe
C
M
D
A
B
F
D
A
E
P
F
H
G
L
N
020010.01.010_PP
Combustion
air intake
Flue
exhaust
020010.01.039
CAUTION!!!
Apply a liberal
even coat of MOMENTIVE -
RTV 106 high temperature
silicone (or equivalent) to the
internal side of the appliance
adapter (item “B” and “P”
fig.11-13)