FEATURES & SPECIFICATIONS
HeatNet Control V3
Page 9
Specifications
Control
Microprocessor based PID modulating control (
NOT a safety limit
)
Environment
-40 °F to 140 °F, <90% RH non-condensing
Input Power
24 VAC, 500 mA
Relays
1 System Pump (Lite version), 2 System Pumps (Full Version), Damper, Circulator, Alarm, DHW
Pump (v2.x), 8A 250 VAC resistive* -
Refer to wiring diagram for application specific ratings
K8 on J4.2 &.6 for Base Loading
AC Interlocks
24 VAC – 120 VAC input
Control Inputs
AA, Heat Demand, 4-20mA Enable, OA override, T1-T2 (dry contact inputs)
4-20mA, 0-10 VDC
Dimensions
9” wide: 6” high: 2” deep
Temperature Sensors
NTC thermistor, 10K @ 77 °F, 335.67K @ -40 °F, 185 @ 150 °F ,+/- 1
F
USB
1.0
RS485 MODBUS
Modbus RTU
Boiler-to-Boiler
HeatNet (H-Net)
Network
Optional LonWorks, BACnet available bridge to MODBUS port