RBI FUTERA II 1000 Manual Download Page 5

5

FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS

WARNING: To avoid spillage into the room of 

dangerous flue gas containing carbon monoxide, 

the opening in damper must never face against the 

flow of flue gas.

WARNING: Boiler/Water Heater shall not be 

connected to a chimney flue serving a separate 

appliance designed to burn solid fuel.

VENT SYSTEM OPTIONS

 

The Futera II may be vented the following ways: 

1)  

Direct Vent, Positive Pressure, Category III

 uses a  

vent system certified to UL 1738 for installations in the 
United States, ULC S636 for installations in Canada. 
Combustion air is piped from the outdoors to the 
blower inlet.

2)  

Side Wall Vent, Positive Pressure, Category III

 uses  

a vent system certified to UL 1738 for installations in the 
United States, ULC S636 for installations in Canada. 
Combustion air is obtained from the space in which  
the unit is installed.

3)  

Horizontal Vent, Negative Pressure, Category I

 for 

horizontal vent runs equivalent to more than 

60 ft,

  

18.3 m (use Table 3 for the equivalent lengths per fitting), 
a dedicated wall mounted power venter must be used. 
The vent system can be single wall galvanized steel or 
type B vent pipe. Combustion air is obtained from the 
space in which the unit is installed or from the outdoors.

A power venter including a barometric damper must 
be installed when the horzontal run is longer than 60 
equivalent feet (use Table 3 for the equivalent lengths 
per fitting).  

4)  

Vertical/Chimney Vent, Negative Pressure, 

Category I

 uses an approved metal chimney system  

or masonry chimney. Combustion air is obtained from  
the space in which the unit is installed. A barometric 
damper must be installed near the flue outlet when 
venting vertically.

5)  

Outdoor Installation

 uses the outdoor option kit. 

Barometric damper is not required.

NOTE: All venting, combustion air material supplied by  

installer.

WARNING: The maximum equivalent length 

for the flue outlet vent system for Category III  

conditions is 60 ft, 

18.3 m

. Use Table 3 for the 

equivalent lengths per fitting. Table 3 “Category 

III Equivalent  Length Per Fitting” chart is meant 

as a guideline for preliminary sizing. If vent length 

approaches 75% of maximum length listed an 

engineered vent system calculation must be 

performed, consult factory.

Intake Air Option – Horizontal Guidelines 

The maximum equivalent length for the horizontal  
combustion air pipe on installations that used the Direct  
Vent option is 

60 ft

18.3 m.

 

The maximum equivalent length 

for the horizontal combustion air pipe on installations that 
use the Horizontal Power Vent option is 

100 ft

30.5 m. Each 

90° elbow and the combustion air terminal are equal to 

10 

linear ft

3.1 m of pipe. If horizontal runs exceed 

5 ft

1.5 m 

they must be supported at 

3 ft

0.9 m intervals with overhead 

hangers. The certified combustion air terminal from RBI 
must be used and installed as shown in Figures 3 and 4.

GENERAL VENTING GUIDELINES

 

WARNING: The vent installation must be in 

accordance with Part 7, Venting of Equipment, of 

the National Fuel Gas Code, ANSI Z223.1/NFPA 54- 

latest revision or applicable provisions of the local  

building codes. Canadian installations must  

comply with CAN/CGA B149.1 or .2 Installation Code. 

See Figure A for added Clarity. Improper venting can 

result in excessive levels of carbon monoxide which 

can result in severe personal injury or death!

All vent systems must be fully supported by the building 
structure and not by the boiler/water heater. Appropriate 
thimbles and fire-stops must be used where required.

WARNING: Common vent systems must be 

properly engineered and sized to provide a 

negative draft of 0.01 to 0.08 in, 

0.25 to 2.0 mm

 W.C. 

at the flue outlet. Common positive pressure vent 

systems are not to be used. Improper installation 

can result in excessive levels of carbon monoxide, 

which can cause severe personal injury or death!

NOTE: Multi-story, common venting systems shall be in

accordance with the National Fuel Gas Code, ANSI 

Z223.1/ NFPA 54 and/or the CSA B149.1, Natural Gas 

and Propane Installation Code (Current Editions), 

local codes and vent manufacturer's installation 

instructions. Size the chimney and breeching using 

generally accepted engineering practices. (Consult 

factory for vertical heights beyond 60 ft.)

NOTE: A single acting 

barometric damper

 must be 

installed directly to the boiler/water heater flue outlet, if 

required. This does not apply to outdoor units or direct 

vent positive pressure units. 

NOTE: Some venting applications may require the stop  

to be removed for smooth operation. The barometric  

damper should be located after the flue collector, refer  

to Figures 2, 7A and 8 for proper location. Be sure that 

the damper is mounted horizontally (never vertically). 

Carefully follow the instructions provided with the 

barometric damper.

In Canada, B149 (7.25 Draft Regulators) states the 

damper shall be of double-acting type.

Summary of Contents for FUTERA II 1000

Page 1: ...uction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be op...

Page 2: ...as Fired Low Pressure Steam and Hot Water Boilers ANSI Z21 56 CSA 4 7 Gas Fired Pool Heaters Canada Only Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160...

Page 3: ...er heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water heater...

Page 4: ...st be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of 1 4 in 6 4 mm If the free area through a louver or grill is not known ducts should be sized p...

Page 5: ...the horizontal combustion air pipe on installations that used the Direct Vent option is 60 ft 18 3 m The maximum equivalent length for the horizontal combustion air pipe on installations that use the...

Page 6: ...61 cm from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter re...

Page 7: ...3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening C Clearance to permanently closed window D Vertical clearance...

Page 8: ...or balcony is fully open on a minimum of two sides beneath the floor NOTES 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z...

Page 9: ...meters gas meters regulators and relief equipment and not less than 7 ft 2 1 m from any adjacent public walkway The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air in...

Page 10: ...10 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 1 Air Intake Vertical or Thru Wall Figure 2 Venting Thru Wall Vertical...

Page 11: ...gle or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wal...

Page 12: ...AND OPERATION INSTRUCTIONS Figure 5 Vertical Air Intake and Venting for Direct Vent System Figure 6 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5 FT...

Page 13: ...venter for the boiler water heater see Table 4 Follow the power venter manufacturer s installation instructions Table 4 Power Venter Sizes VERTICAL CHIMNEY VENT NEGATIVE PRESSURE CATEGORY I The Futer...

Page 14: ...ingle wall vent connection with at least 3 corrosion resistant sheet metal screws Always provide a minimum clearance of 6 in 152 mm between single wall vent pipe and any combustible materials Type B1...

Page 15: ...15 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 8 Vertical Venting with a Metal Chimney System...

Page 16: ...r window or gravity air inlet into any building and at least 3 ft 1 m from any overhang unless local codes dictate differently Avoid locations where wind deflection off of adjacent walls buildings or...

Page 17: ...marche Suivre les instructions d allumage R gler le thermostat de fa on que l appareil fonctionne de fa on continue e Test for spillage at the draft hood relief opening after 5 minutes of main burner...

Page 18: ...water mix that prevents foaming Air entrapped within foam significantly decreases heat transfer and can result in damage to the heat exchanger Products such as DOWFROST DOWTHERM UCARTHERM or an equiva...

Page 19: ...4 C The adjustable pump delay turns the pump on each time the burner fires and runs the pump for 6 to 600 seconds after the call for heat is satisfied CAUTION A temperature rise outside of the range...

Page 20: ...econdary systems In order to prevent boiler s short cycling the system flow must be equal to or higher than the boiler s local flow Low Return Water Temperatures To prevent the problems associated wit...

Reviews: