Optional PVC vent system installation instructions supplement

2

O

Th ese instructions are specifi c to using schedule 40 PVC pipe as the 
vent system for the RBI Fusion. Th e instructions contained in the 
Fusion Installation and Operation Manual, including all applicable 
Combustion Air & Ventilation and Venting instructions must be 
followed.

  Venting of the Futera Fusion with PVC material 

requires the factory supplied PVC adapter kit. Th e vent 
system must conform to local codes and/or the latest 
edition of the National Fuel Gas Code ANSI Z223.1/
NFPA 54. Failure to properly vent this product can 
result in CO poisoning causing severe personal injury 
or death!

  The return water temperature entering the Futera 

Fusion using the PVC venting option must not exceed 
155°F. Higher return water temperatures will result in 
a reduction of the fi ring rate.  

The PVC vent adapter, Figures 1 and 2, comes fitted with a flue 
temperature sensor and flue temperature high limit switch. This 
system provides redundant over-temperature protection for the PVC 
vent system. Th e fl ue temperature sensor continuously monitors the 
temperature of the fl ue gas exiting the Fusion. If the return water 
temperature exceeds 155°F the HeatNet Control, via the flue 
temperature sensor, will recognize the resultant increase in flue 
temperature and reduce the fi ring rate of the Fusion. Should the 
sensor fail, the manual reset high limit switch will trip and shut down 
the Fusion before the fl ue temperature can exceed a safe limit.

Figure 1 

PVC Vent Horizontal Adaptor

 

Summary of Contents for Futera Fusion FTF-PVCVO-2

Page 1: ... damage Do not use the boiler during construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be operated with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation wit...

Page 2: ... The return water temperature entering the Futera FusionusingthePVCventingoptionmustnotexceed 155 F Higher return water temperatures will result in a reduction of the firing rate The PVC vent adapter Figures 1 and 2 comes fitted with a flue temperature sensor and flue temperature high limit switch This systemprovidesredundantover temperatureprotectionforthePVC ventsystem Thefluetemperaturesensorco...

Page 3: ...access to the Fusion s economizer cabinet With the PVC vent adaptor positioned at the rearoftheunitcarefullyinsertthemanualresethighlimitthroughthe flue pipe opening in the rear cabinet panel Mount the high limit to the economizer bracket as shown in Figure 3 Donotkinkordamagethehighlimitcapillarytubeorthe limit may be ruined voiding the manufacturer s warranty Placethesmallendoftheventadaptorthro...

Page 4: ...nding a chimney liner gas vent special gas vent or plastic piping installed within a masonry chimney shall not be used to vent another appliance The PVC vent adapter has been engineered to directly accept PVC ventpipe Theinternalgasketintheventadaptorwillformagasand watertightseal Nogluesorsealantsarerequiredatthisconnection Slide the required horizontal length of PVC pipe into the vent adaptor an...

Page 5: ...e Do not store them near heat sparks or flames Keep containers closed when not in use Wear imperviousclothingwhilehandling Donotsmoke eat ordrinkwhilehandlingprimers cleanersandcements Wash thoroughly after handling and before eating Wear eye protection when handling The harmful vapors can be absorbed through the skin and may irritate eyes and skin If inhaled get fresh air and seek medical attenti...

Page 6: ...rd screeninsertsasshownbelow Theminimumdistancefromthe wall must be maintained as shown in the Figures below Figure 4 Horizontal PVC TEE Terminal Figure 5 Horizontal PVC 45 Elbow Terminal Figure 6 Horizontal PVC 90 Elbow Terminal Figure 7 Horizontal PVC Coupling Terminal 10 Min 1 4 SS Bird Screen In Opening 8 Min 1 4 SS Bird Screen In Openings 8 Min 1 4 SS Bird Screen In Openings 10 Min 1 4 SS Bir...

Page 7: ...ertical PVC Terminal TheinputoftheunitmustbesetperTable2ornuisanceshutdowns may occur under strong wind conditions Table 1 Turn Down vs Combustion Air Source When vented vertically the vent and air intake systems should be terminated using standard 45 and 90 PVC Elbow fittings with a 1 4 in stainless steel bird screen insert as shown below TherestoftheapplicableCombustionAir VentilationandVenting ...

Page 8: ...ht 2008 Mestek Inc 260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwaterheaters com ...

Reviews: