RBH Access Technologies UNC100 Manual Download Page 1

1  2  3  4  5  6  7  8

TX       RX

A+ 

FG 

B-  

Input 1(RTE)

C

Input 2 (DC)

RTE

 “A”- Request to Exit

DC

 “A” - Door contact

RTE

 “B”- Request to Exit

DC

 “B” - Door contact

Input 3

C

Input 4

Reader B

GRN

BUZ

D0

D1

S

0V

12V

LED 

(For single LED readers)

Buzzer

Data 0 

Data 1

0V, Power, Data Ground

+12VDC

Reader A

LED 

(For single LED readers)

Buzzer

Data 0

Data 1

0V, Power, Data Ground

+12VDC

GRN

BUZ

D0

D1

S

0V

+12V

1NO 1NC 1C 2OC

Output 

Lock “A”

Output 

2

Output 

Lock “B”

Output 

4

Lock

Lock

 

Power Supply

12-24 VDC

-

+

0V     IN    [email protected] A
+V   OUT  12V@500 mA

THIS DOCUMENT IS FOR QUICK REFERENCE ONLY, REFER TO HARDWARE & SOFTWARE MANUALS FOR FULL DETAILS

Panel LEDs

Run

Trouble

Host Comm

TX

RX

Function

Heartbeat

Trouble

Com to 

software

RS-485 

transmitting

RS-485 

receiving

Off Malfunction

Normal

No com

No com

No com

Solid Malfunction

Trouble

No Com

Malfunction

Malfunction

Blinking

Normal

Trouble

Red/Green = 

Normal

Normal

Normal

Panel LEDs

Cycle power for DIP-switch changes to take effect!

Switch 1

2

3

4

5

Panel 

1

On

Panel 

2

On

Panel 

3

On On

Panel 

4

On

Switch 1

2

3

4

5

Panel 

9

On

On

Panel 

10

On

On

Panel 

11

On On

On

Panel 

12

On On

Switch 1

2

3

4

5

Panel 

13

On

On On

Panel 

14

On On On

Panel 

15

On On On On

Panel 

16

On

Switch 1

2

3

4

5

Panel 

5

On

On

Panel 

6

On On

Panel 

7

On On On

Panel 

8

On

Switch 6

7

9.6 K

38.4 K On

57.6K

On

115.2 K On On

Switch 8: Always OFF!

DIP SWITCH SETTINGS : DIP-Switch:  UP = ON  /  DOWN = OFF

Lock

Lock

 

Power Supply

12-24 VDC

+

-

Link up to 1

5 additional

 

panels

 

via RS-485

Belden 8723 

20-22 AWG Twisted,

 

Shielded Pair. 4,000’ Max

To 12 VDC 7 Ah UL Listed

 

Rechargeable Battery (REQUIRED)

0VDC @ 2A

+12VDC @ 2A

PS-1224 Power Supply

BA

T. TEST

16.5VAC 40Va
16.5VAC 40Va

Press “BAT. TEST” button on 

PS-1224 for battery test, Yellow 

LED will go ON if test failed

Power Supply (PS-1224) LEDs

LED

On

Off

Green LED

Power On

Power Off

Red LED

Shorted

OK

Yellow LED Battery Fail Battery OK

For Support Call :

 

01386 425810

All software and hardware manuals are included 

on software DVD in “Documents” folder

!

Web site : www.rbh

securitygroup.com

  E-mail : support

.uk

@rbh-access.com

UNC100

U

niversal 

N

etwork 

C

ontroller

 

with ENCL1 enclosure

and PS-1224 power supply

RUN

TROUBLE

HOST COM

CANADA

ETHERNET

PoE

RS-485

(max 100ma)

LOCK 1

3NO 3NC 3C 4OC

(max 100ma)

LOCK 2

Firmware, use Axiom Lite

software to check 

firmware version.

Verify it matches your 

software, up/downgrade 

as needed via firmware 

upgrade utility.

REMEMBER TO REMOVE THE PAPER FROM THE BATTERY CONTACT PRIOR TO INSTALLATION

Belden 9538 20-22 AWG

8 core screened for 

readers.

Belden 9538 20-22 AWG

8 core screened for 

readers.

Reviews: