For example, DSC panel input #88 would be mapped to IOC address #10 input
#8. This input would be located in one of eight partitions in the Paradox panel
programmed through the Paradox keypad.
Dipswitch Setting
To allocate a block of IOC addresses for use by the DSC alarm panel you must
first determine how many inputs you will need. For example if you need to
monitor the first 64 inputs you will need 64÷
16 (inputs per IOC) = 4 IOC‟s. The
first IOC address will be # 5 representing inputs 1-16 and the last IOC address
will be #8 representing inputs 49-64. Use the
to determine the dipswitch settings.