INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

SYDNEY  |  MELBOURNE  |  BRISBANE  |  PERTH  |  AUCKLAND

Australia

   1300 788 778   www.rba.com.au   |

   New Zealand

   0800 722 111  www.rbagroup.co.nz

3 of 4

Installation 

1.  Check rough-in drawings against supplied product.
2.  Anchor water cooler to wall through anchor clips on the bottom of the base [provide 102mm minimum clear space on 

fixture sides to allow for proper ventilation through cabinet louvers].

3.  Remove the front panel from the water cooler by taking out the screws on each side at the bottom front, press the panel 

sides together at the bottom so that front panel clips disengage from the housing sides and carefully pull forward and 
down. Set panel aside in a safe place where it will not be damaged.

4.  Make up trap waste connection.
5.  Flush the supply line to remove all foreign debris.
6.  Connect water supply to water cooler with 1/2” BSP.
7.  Turn on building water supply and check all connections for leaks. 
8.  Air within the water supply will cause an irregular bubbler outlet stream until purged out by incoming water. Covering the 

bubbler with a clean cup [or similar object] is recommended when first activating water cooler. Depress push button until 
steady water stream is achieved.

9.  Adjust bubbler to the site requirements;

10.  Plug water cooler into electrical outlet and make sure unit begins to function.
11.  Re-attach bottom cover to water cooler with screws furnished. 

Troubleshooting

Before making any of the repairs listed, make sure the water cooler is disconnected from the electrical supply and the water 
supply valve is shut off. 

Problem 

Probable cause

Compressor Does Not Run

Check the electrical receptacle for power and correct voltage. The incoming voltage 
must be within 10% of the rated voltage on the serial nameplate.
The cold thermostat is accessible by removing the bottom access cover. If the cold 
thermostat capillary bulb loses its charge or becomes kinked it will fail in the open 
position causing a disruption of power to the compressor. Unplug the water cooler and 
using an ohm meter check for continuity across the two electrical terminals on the 
thermostat. Install a new thermostat if there is no continuity.
Check for loose wires within the compressor box. The incoming power leads must be 
connected to the overload and relay.

Compressor Runs – 
Water Is Warm

The most common cause for a water cooler to run without producing cold water is a 
loss of refrigerant. The water cooler must be taken to a certified refrigerant technician 
for repairs.
Make sure the condenser fan motor is operative. The fan blade must turn freely to 
help remove the heat of compression.
An incorrect refrigerant charge, restriction or defective compressor [not pumping] 
will also cause the compressor to run without producing cold water. All these signs 
indicate a problem within the refrigeration system and the water cooler must be 
checked by an authorised service company

9a. If water flow requires adjustment, insert a narrow slotted screwdriver in the center of the button actuator.    

           

      Turning clockwise will increase flow and turning counterclockwise will decrease flow.
9b. The water temperature can be adjusted using a slotted screwdriver in the cold water thermostat and turning  

 

      clockwise to make colder and counterclockwise to make warmer.
9c. Bubbler can be rotated slightly to direct the stream backwards or forwards.

Summary of Contents for RBA2770 Series

Page 1: ...A2777 Series Stainless Series MODEL WALL MOUNTED COMPACT WATER COOLERS As improvements in the design and performance of RBA products are continuous specifications may be subject to change without notice The illustrations and descriptions herein are applicable to production as of the date of this Installation Instructions Sheet Revised 08 22 2022 by RBA Group II rba2770 series rba2777 series 0822 R...

Page 2: ...cessive condensation Hydraulic Requirements Operating pressure 200 500kPa Inlet G1 2B Outlet 40mm BSP Waste Water Temp 4o 32o Provide 102mm minimum clear space on fixture sides to allow for proper ventilation through cabinet louvers Rough in and Dimensions Prior to roughing in consult with local state and federal codes for proper mounting height Installation to be done in accordance with AS NZS 35...

Page 3: ...ff Problem Probable cause Compressor Does Not Run Check the electrical receptacle for power and correct voltage The incoming voltage must be within 10 of the rated voltage on the serial nameplate The cold thermostat is accessible by removing the bottom access cover If the cold thermostat capillary bulb loses its charge or becomes kinked it will fail in the open position causing a disruption of pow...

Page 4: ...e sure it is within 10 of the serial nameplate rating A restriction or moisture in the system will also cause intermittent cycling A certified refrigeration mechanic should be contacted in this situation Change the overload or relay if defective Cleaning Maintenance 1 Motors have lifetime lubrication and do not require scheduled maintenance 2 Excess dirt or poor ventilation will cause the compress...