background image

TTDM-128  Installation Instructions

4

Connect the alarm relays.

The TTDM has three relays, for service 

ck

, leak 

bt

, and fault 

bs

Each relay provides two Form-C relay contacts, and normally open 

and normally closed contacts are both provided. The relays are 

de-energized to indicate an alarm

condition. The illustration shows 

the relay status in the alarm (de-energized) state.

The illustrations that follow show how relays can be jumpered together

to allow remote monitoring of the TTDM status with only a single pair of

wires. The TTDM 

de-energizes

its relays to signal an alarm condition.

Therefore, loss of power, as well as any other type of alarm, would signal 

the remote alarm.

Note:

The relay plugs can accept wires 10 AWG (4.7 sq. mm) or smaller.

We recommend 18 AWG (1.0 sq. mm) wires. Cable should have a

temperature rating of 65°C.

Note:

Maximum load for relays is 5 A.

Test after supplying power.

Close and latch the enclosure door.

Supply power to the unit. When power is supplied, the green LED illu-

minates, and the unit goes through a series of self-tests. After the

start-up sequence is complete, the module should report a fault alarm

(this is normal; there is no sensing cable attached). Press the red

Silence key to silence the audible alarm. Verify that the display appears

similar to the one shown here (the time and date may be different):
If anything other than the above occurs, check all connections. 

If unit still does not appear to operate properly, contact a TraceTek 

representative for assistance.

• P

ress the Test button. The module conducts a number of self-tests.

If the tests are successfully completed, record this on the installation

record.

• T

urn off the power supply to the unit.

Test with TTDM test plug.

• T

o conduct a more complete test, use the TraceTek TTDM-CTP test plug

(packed in a plastic bag in the TTDM packaging). Insert the plug into the
sensing cable socket 

cn

on the sensor interface board 

9

.

Close and latch the enclosure door.

Supply power to the unit. When power is supplied, the unit will again go

through a series of self-tests. If the test plug is in the sensing cable socket, after

the module completes the start-up sequence it should sound and display a leak

alarm. Press the Silence key to silence the audible alarm. The red Leak LED and

green Monitoring LED should both be illuminated, and the screen display

should appear similar to the one shown here (depending on the setting).

If anything other than the above occurs, check all connections. If unit still does

not appear to operate properly, contact a TraceTek representative for assistance.

If the test is successfully completed, record this on the installation record.

• T

urn off the power supply to the unit.

Remove the TTDM-CTP test plug and store it in a secure place for future use.

If not immediately connecting the sensing cable, or TraceTek network, close

and latch the enclosure.

CH01

Leak 538 ft

14:37  02-Jan-03

Depending on the units selected, the leak distance should 

be within the values below:

feet: 

527 to 548 ft

meters:  160 to 168

zones: 11

CHO1

Cable Break

14:23  02-Jan-03

Testing the Module

SERVICE RELAY

5A 250V

J6

LEAK RELAY

5A 250V

J25

FAULT RELAY

5A 250V

J9

1

1

1

NC NO COM NC NO COM

15

16

17

18

19

20

NC NO COM NC NO COM

21

22

23

24

25

26

NC NO COM NC NO COM

27

28

29

30

31

32

Monitoring circuit

(alarm on open circuit)

Relays wired

in series

Alarm on open circuit

SERVICE RELAY

5A 250V

J6

LEAK RELAY

5A 250V

J25

FAULT RELAY

5A 250V

J9

1

1

1

NC NO COM NC NO COM

15

16

17

18

19

20

NC NO COM NC NO COM

21

22

23

24

25

26

NC NO COM NC NO COM

27

28

29

30

31

32

Monitoring circuit

(alarm on closed circuit)

Relays wired

in parallel

Alarm on closed circuit

bs

bt

ck

bs

bt

ck

15 16 17

20

19

18

21 22 23

26

25

24

27 28 29

32

31

30

LEAK RELAY

SERVICE RELAY

FAULT RELAY

NC NO COM NC NO COM

NC NO COM NC NO COM

NC NO COM NC NO COM

bs

bt

ck

Reviews: