SECTION 5 - TROUBLESHOOTING
* Indicates symptom which usually occurs on initial start-up.
MECHANICAL
PROBLEM
CAUSE
SOLUTION
Harmonics, or whining noise
*Debris or restriction in system..............
*Debris in gas line..................................
Low flow.................................................
Heater going on and off
Dirty filter................................................
with Water SW Open
indication on LCD or in
Fault History
Low water level in pool..........................
External bypass setting out of
adjustment............................................
Valve opens but no flame
Manifold pressure too low………………
visible
Flame visible for a split
Ignition not being sensed………………..
second
Liming or scale forming in
Pool water............................................
exchanger
Bypassing too much water...................
Sooting
Low water temperatures.........................
*Air starvation.........................................
*Improper venting...................................
*Insects or debris clogging
burner intake ports...............................
Yellow lazy flame
Air intake clogged or incorrect
fan operation..........................................
*Insects or debris clogging
burner intake ports.................................
Outer jacket very hot
*Broken refractory caused by
(paint blistered)
shipping damage or improper
combustion..........................................
Excessive sooting of heat exchanger....
Hard lighting at startup
Igniter faulty……………………………….
Takes too long to heat
Under-sized heater...............................
pool or spa
Htr. output(BTUH)
Pool gallonage x 8.33
Filter not running long enough.............
Dirty filter..............................................
Gas line or meter undersized...............
Leaking at T&P gauge
Overacid...............................................
Leaking at heat exchanger
Overacid...............................................
Gasket brittle and leaking -
(overheated)
Refractory damage..............................
Sooted heater.......................................
Combustion fan not running
Fan relay...............................................
“Fan 5 min Delay”,
Fan........................................................
“Fan Lockout” or "Fan RPM
Fault" indication
Burned motor .......................................
Motor control failure..............................
Heater turns on for less
Wiring....................................................
than 4 seconds
Incorrect supply wiring..........................
(no display error)
PC Board short.....................................
Ignition not sensed………………….….. Clean igniter with wire brush.
Replace board if no strength signal is being detected.
Replace fan relay.
Loose connection or failed motor.
Incorrect wiring, replace blower.
Replace blower.
Check for loose or broken (verify continuity) wiring/ground/ignition wire.
Check incoming power for correct voltage. There should be
no power on the neutral line.
Check for debris upstream of fan intake. Check intake air filter suction
pressure, replace filter if dirty.
Clean burners with a gentle application of compressed air, do not use
a brush.
Air intake feedback to regulator
disconnected.......................................... Check that tubing between air intake adapter and regulator is connected
and free of obstruction. See Fig. 1.
This does not take into account heat loss due to weather.
Replace igniter
Reset time clock.
Clean filter.
Refer to installation instructions.
Replace T&P gauge and maintain proper water chemistry.
See Water Chemistry on page 2.
Inspect bypass for movement, if no movement, replace.
Maintain water body temperatures above 50ºF (10ºC).
Heating Capacity =
Locate the restriction and remove. Flush system and clean.
Remove debris or blow out gas line.
Scale forming in heat exchanger - clean heat exchanger and
check pool pH and total alkalinity.
Clean or replace filter.
Raise water level.
Determine cause of sooting & correct.
Calculate heating capacity of heater or refer to heater sizing chart.
Replace refractory panels.
Replace refractory.
Determine cause of sooting and correct.
Replace heat exchanger and maintain proper water chemistry.
Clean burners with a gentle application of compressed air, do not use
a brush.
Refer to installation instructions.
Follow recommended installation instructions.
Adjust bypass.
Increase manifold pressure (turn clockwise slightly).
Replace ignition wire. Check connections. Increase manifold pressure
(turn clockwise slightly).