TempTracker mod+ & TempTracker mod+ Extension Installation Manual
17
operatInG settInGs
proGraM cHanGe settInGs
To be able to change the TempTracker mod+ settings the Program/Run Switch must be set to
Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure
Wiring Cover can be securely closed using a lock.
----
----
SYSTEM
A
B
C
D
1 2
RUN
PROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4 5
6
7
8
9 10 11 12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30 31
L N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
----------- SETTINGS ------------
Season
Winter
Set Point
140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
140
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
65
F
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
140
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
220
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
alert
do not turn power off to
the temptracker mod+ when
heating season is over. If
you do so, the battery will
run down and will have to be
replaced. Instead switch to
summer.
season
Winter, Summer
Default: Winter
Button: MENU/Season
• The TempTracker mod+ will turn all boiler relays off when it is in Summer setting.
However, a DHW call will bring boilers back on if needed. The Message Display Line will
display
Summer
to show status.
• When in Winter, the TempTracker mod+ will activate the Sys relay whenever the Outdoor
temperature (OD) falls to or below the Outdoor Cutoff setting. In addition, it will begin
heating whenever the System temperature (SYS) falls below the Set Point Temperature.
• When the heating season is over, it is a good practice to switch the TempTracker mod+ to
Summer setting. This will allow DHW calls to operate the boilers when needed.
set poInt
(not ADjuStAble in eMS MoDe)
Adjustable 70
º
F - 250
º
F
Default: 140
º
F
Button: MENU/Set Point
• The Set point is the temperature value the TempTracker mod+ will use to control the system.
• It only be available when Set Point is selected as the Sensor Type. See page 14.
• The TempTracker mod+ will increase, decrease or hold the modulation of the boilers to
maintain the system temperature around the Set point. The amount of fluctuate around the
set point depends on the Modulation Mode, System Settings, and Stage Settings.
• If the EMS Mode was Enabled, the Set Point will be set by the EMS/BMS system and will
be available to be read but not changed on the display.
----------- SETTINGS ------------
Season
Winter
Set Point
140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
140
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
65
F
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
140
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
220
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
reset ratIo
Adjustable 1.00ºOD : 4.00ºSys to 4.00ºOD : 1.00ºSys
Default: 1.00ºOD : 1.00ºSys
Button: MENU/Set Point
• The Reset Ratio determines how the System water temperature (SYS) will vary with
Outside temperature (OD). With any of the ratios, the colder it becomes outside, the hotter
the temperature of the system water. The ratios are adjustable from 1.00 (OD):4.00 (SYS) to
4.00 (OD):1.00 (SYS). (See Understanding Operation Concept on page 5.)
• With a 1.00 (OD):4.00 (SYS) ratio, the System water temperature (SYS) will increase
rapidly as the outside temperature falls, hitting the maximum of 240°F at 24°F outside
temperature. With a 4.00 (OD):1.00 (SYS) ratio, the System water temperature (SYS) will
increase slowly as the outside temperature falls. Even at -30°F, the system water will only
be 125°F, and at 24°F outside, the system water will be 112°F. Such a low Reset Ratio
might be used with radiant floor heating applications.
----------- SETTINGS ------------
Season
Winter
Set Point
140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
140
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
65
F
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
140
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
220
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
• With most baseboard heating applications, a 1.00 (OD):1.00 (SYS) setting is a good place to
start. With a 1.00 (OD):1.00 (SYS) ratio, for every degree the outside temperature falls, the
system water temperature is increased one degree.
• If required:
Adjust the RESET RATIO in cold weather.
If the ambient building
temperatures are too cold in cold weather, move the ratio to a higher selection. That is,
if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to 1.00 (OD):1.25
(SYS). If the building temperatures are too warm in cold weather, move the ratio to a lower
selection. That is, if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to
1.25 (OD):1.00 (SYS).
Outdoor Temperature
W
at
er
T
em
pe
ra
tu
re
70
40
50
60
130
120
110
100
Outdoor Temperature
W
at
er
T
em
pe
ra
tu
re
70
40
50
60
110
100
90
80
Outdoor Temperature
W
at
er
Te
m
pe
ra
tu
re
70
40
50
60
150
140
130
120
1:4
With a 0° Offset, the
Reset curves begin at
100° Water Temperature.
With a -20° Offset, the
Reset curves begin at
80° Water Temperature.
With a +20° Offset, the
Reset curves begin at
120° Water Temperature.
1:4
1:4
1:1
1:1
1:1
4:1
4:1
4:1
90
100
+20 Offset
-20 Offset
Outdoor Temperature
W
at
er
T
em
pe
ra
tu
re
70
40
50
60
130
120
110
100
1:4
1:1
4:1
Colder
Warmer