START UP

Relief Valve

A new combination temperature and pressure (T&P) re-

lief valve, complying with the Standard for Relief Valves

and Automatic Gas Shut-Off Devices for Hot Water Sup-

ply Systems, ANSI Z21.22, is supplied by the installer.

It must be installed in the opening provided and marked

for the purpose on the water heater. No valve of any

type should be installed between the relief valve and the

tank. Local codes shall govern the installation of relief

valves.

The pressure rating of the relief valve must not exceed

150 PSI, or the maximum working pressure of the water

heater as marked on the rating plate.

The BTUH rating of the relief valve must equal or ex-

ceed the BTUH input of the water heater as marked on

its rating plate.

Position the outlet of the relief valve above a suitable

open drain to eliminate potential water damage. Piping

used must be of a type approved for hot water distribu-

tion.

The discharge line must be no smaller than the outlet

of the valve and must pitch downward from the valve to

allow complete gravity drainage of the relief valve and

discharge line.

The end of the discharge line should not be threaded or

concealed, and must be protected from freezing. No

valve of any type, restriction, or reducer coupling may

be installed in the discharge line.

Purging the System

Purge the system of air and check for leaks at all of the

connections.

Flushing the System

Flush the system completely. It is important to clear any

debris and residues from inside the piping and tank be-

fore the water heater will be put to use by the customer.

To flush the system, open one of the hot water valves

at the point of use after the water heater. Allow enough

water to flow through the tank to change the water vol-

ume at least two times.

Checking Circulator

Check that the circulator or zone valve operates when

there is a call for heat. When a call for heat is initiated,

water should begin to flow through the indirect water

heater’s coil. 

Set the Thermostat to the 

Desired Temperature

For normal water heating installations, Raypak recom-

mends  an  operating  temperature  of  120ºF  or  49ºC.

Other temperatures may be required by the particular

installation. To minimize burns and scalding, Raypak

recommends that the water temperature be verified at

the point of use (see 

Verify the Water Temperature

below). 

For VERSA-equipped Raypak boilers, the indirect water

heater’s  setpoint  is  controlled  by  the  boiler  and  the

10k Ohm thermistor installed in the water heater’s ther-

mal well. To adjust the water heater setpoint, please

refer to the equipped boiler, read the VERSA IC Instal-

lation & Operating Manual, Cat. 5000.72.

For installations with an aquastat control, the tempera-

ture is adjusted at the aquastat control located on the

tank thermowell. To adjust the setpoint temp, rotate the

dial on the aquastat to the desired setpoint.

Verify the Boiler Functionality

When a call for heat is initiated, the boiler should come

on and begin heating. The boiler should also shut off

when the tank has reached its setpoint. If the boiler does

not heat, please check that water circulator is function-

ing and that the wiring is correct.

Verify the Water Temperature

Raypak recommends that the water temp be verified at

the point of use. First, let the indirect water heater come

to temperature. The water heater has reached its set-

point when the boiler heating water has stopped flowing

through the heat exchanger. To verify the water temp,

open the shutoff valve at the point of use. Let the water

run for several minutes until the temperature has stabi-

lized. Measure this stabilized water temperature.

Summary of Contents for RSIT115

Page 1: ...not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas s...

Page 2: ...2 Rev 1 Changes to New Additions New Deletions None...

Page 3: ...cation 8 Boiler and Circulator Sizing 8 Temperature Pressure Relief Valve 8 Plumbing 8 Controls 11 START UP 13 Purging the System 13 Flushing the System 13 Checking Circulator 13 Set the Thermostat to...

Page 4: ...es not answer please contact your local Raypak representative or visit our website at www raypak com Keep this manual with the water heater after installation Local plumbing and electrical codes must...

Page 5: ...will be re placed in kind only per Raypak s standard warranties Scalding Water Temperature Setting DANGER Safety and energy conservation are factors to be considered when selecting the water temperatu...

Page 6: ...cial Products 5th ed b The pressure of the heat transfer medium must be limited to a maximum of thirty 30 psig 207kPa by an approved safety or relief valve Freeze Protection The water heater and water...

Page 7: ...al L First Hour Rating gal hr L hr Continuous Draw Rating gal hr L hr Standby Loss F hr C hr Minimum Boiler Ouptut BTUH kw Coil Length ft m Heating Surface Area Sq ft m2 Heating Coil Flow GPM L min Co...

Page 8: ...ing should terminate in a safe location This discharge piping must comply with local and national plumbing codes The piping must be rated for 120 F and 150 PSI Plumbing A tempering valve may be requir...

Page 9: ...BALL VALVE DRAIN TO BOILER COLD INLET HOT OUTLET FROM SYSTEM 12 MAX APART MIX OUTLET MAKE UP WATER TO SYSTEM COLD INLET S5 IND TANK SENSOR FROM BOILER INDIRECT FIRED STORAGE WATER HEATER DRAIN DRAIN F...

Page 10: ...VALVE T P GAUGE UNION INLET OUTLET UNION UNION MIXING VALVE BALL VALVE PRV BALL VALVE S6 IND SUPPLY SENSOR BOILER PUMP EXPANSION TANK DHW PUMP DRAIN CHECK VALVE PRESSURE GAUGE BALL VALVE UNION BALL V...

Page 11: ...SA control is pre configured to handle an indirect storage water heater The VERSA control can also be configured to give priority to the domestic hot water or to space heating To connect the unit to a...

Page 12: ...r always remember that in principle an indirect water heater operates as another heating zone The difference is that when the indirect water heater calls for heat the indirect water heater cir culator...

Page 13: ...ugh the tank to change the water vol ume at least two times Checking Circulator Check that the circulator or zone valve operates when there is a call for heat When a call for heat is initiated water s...

Page 14: ...g Replace zone valve Circulator pump not working Check power supply Replace circulator Tank thermostat Thermostat set too low Check thermostat wiring Scale build up Check coil for scale build up Desca...

Page 15: ...15 Below is a list of the replacement parts for the Stainless Steel Indirect Water Heater IPL diagram showing replacement parts 2 M 1 M 3 M PARTS...

Page 16: ...lfunctions or failures resulting from failure to install the indirect water heater in accordance with applicable building codes ordinances or good plumbing and electrical trade practices c Damages mal...

Page 17: ...tion for an in warranty indirect water heater replacement you must provide Raypak with at Raypak s option either the indirect water heater replaced in warranty with the original rating label and all t...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Reviews: