Catalog No.:  2000.24O 

Effective:  04-15-10 

Replaces:  12-01-07

 

Raytherm - Type H 

 

 

Hydronic Heating Boilers 

Model 

           

 

 
 

  

11 3/4

14 1/2

5

A/2

A

L

1 1/8

COMBUSTIBLE FLOOR SHIELD

14

11 1/8

5 1/8

2 1/2

G

GAS

ELEC.

CONN.

27 3/4

C

J

B

11 1/4

6

32 1/2

(J-BOX)

 

 

(OPTIONAL)

H

IN

OUT

K

H - INLET

(OPPOSITE SIDE)

7-7/8

15-1/4

H - OUTLET

OPTIONAL ONE PASS

DRAFT HOOD

(OPTIONAL)

19 1/2

(OPTIONAL)

 PUMP

       

 

 

 

 

 

 

 

 

 

 

 

MODELS 962 THRU 1826

  

Dimensions 

(Inches) 

Approx. 

 MBTUH  

Overall 

Jacket 

Gas 

Water 

 

Flue 

 

Shipping 

Model Natural 

Gas Width 

Height 

Height 

Conn. 

Conns.  Dia. 

  Weight 

Size 

Input 

Output 

G  

K  

(Lbs.) 

H-962  961.7  788.6  52-3/8 76-1/8 

(a) 33-1/2 

1  2-1/2 

(c) 23-5/8  14  28 

705 

H-1125 

1124.7 

922.0 

59-1/4 

78-1/8 (a) 

33-1/2 

1 (b) 

2-1/2 (c) 

23-5/8 

16 

32 

745 

H-1223 

1222.5 

1002.4 

63-5/8 

78-1/8 (a) 

33-1/2 

1 (b) 

2-1/2 (c) 

23-5/8 

16 

32 

805 

H-1336 1336.6  1096.0  68-5/8 80-1/8 

(a) 33-1/2  1-1/4 2-1/2 

(c) 23-5/8  18  36 

875 

H-1468 1467.0  1203.0  74-7/8 80-1/8 

(a) 33-1/2  1-1/4 2-1/2 

(c) 23-5/8  18  36 

945 

H-1631 1630.0  1336.6  81-1/8 83-1/8 

(a) 36-1/2  1-1/4 2-1/2 

(c) 23-5/8  18  36 

985 

H-1826 1825.6  1497.0  89-3/8 85-1/8 

(a) 36-1/2  1-1/4 2-1/2 

(c) 23-5/8  20  40 

1035 

NOTE:  Ratings shown are for elevations up to 2,000 feet. For 
elevations over 2,000, reduce ratings at the rate of 4% for each 
1,000 feet above sea level. 

(a) Add 1-1/8" to overall height for combustible floor shield option 
(b) 1" or 1-1/4" contingent on boiler type or code requirements 
(c) 3" NPT on single-pass option 
(d) Propane input/output is 92% of standard values 

 

Raypak, Inc.  

ƒ

  2151 Eastman Avenue, Oxnard, CA  93030  

ƒ

  (805) 278-5300  

ƒ

  Fax (800) 872-9725  

ƒ

  www.raypak.com 

BOILER RATE OF FLOW AND PRESSURE DROP

10º 

Δ

T 20º 

Δ

T 30º 

Δ

T 40º 

Δ

Minimum Flow 

Maximum Flow 

 

Model 

No. 

GPM 

Δ

FT 

GPM 

Δ

FT 

GPM 

Δ

FT 

GPM 

Δ

FT 

GPM 

Δ

FT 

Δ

T GPM 

Δ

FT 

Δ

H-962 

80 8.8 53 3.8 40 2.2  40  2.2  38  90 11.0 18 

H-1125 

 

90 12.0 61 5.5 47 3.3 45  3.1  40  90 12.0 21 

H-1223 

76 7.0 51 4.0 51  4.0  40  90 12.5 22 

H-1336 

73 8.6 55 4.9 55  4.9  40  90 13.2 25 

H-1468 80 

11.0 

61 

6.4 

61  6.4  40  90 14.0 27 

H-1631 

Exceeds Maximum Flow

 

90 14.8 68 8.3 68 8.3 40  90 8.3 30 

TWO-
PASS 

H-1826 

 

76 10.8 76 10.8 40  90 15.4 34 

H-962 157  6.1 

 90 

2.1 

18 

200 

9.7 

H-1125 184  8.8  92  2.3 

90 2.3 20 200 10.3 9 

H-1223 200  11.0  100  2.9 

90 2.4 22 200 

11.0 10 

H-1336 110 

3.7 

90 

2.5 

24 

200 

11.7 

11 

H-1468 120 

4.5 

90 

2.7 

27 

200 

12.2 

12 

H-1631 134 

6.0 

Less than Minimum Flow

90 2.8 30 200 

13.0 13 

ONE-
PASS 

H-1826 

 

150 8.0 100 3.7 

 90 

3.0 

33 

200 

14.7 

15 

NOTES: 

 

Values represent maximum flows and pressure drops for closed heating systems 

 

Maximum acceptable flow through heat exchanger tubes is 90 GPM (two-pass); 200 GPM (one-pass) 

 

Single-pass heat exchangers are to be used only when flow rates exceed the allowable for two-pass 