Catalog No.: 2000.364A
Effective: 8-15-07
Replaces: 6-15-07
MVB™ – Type H
Models H7 504-2004
Model
Dimensions (in.)
MBTUH
B D
E F G H K M N P
R
V
Model
(H7-)
Input Output Height
NPT
NPT
Flue Ø
C/A Ø
Ship
Weight
(Lbs.)
Foot-
(Ft
2
)
Amps*
504 500 420 43 30
35
23-3/4 1 2
8 14-1/8
6 36
6
2 600 5.4 12
754 750 630 49 36
41
29-3/4 1 2 10 16
6 42
6
2 670 5.4 12
1104 1100
924
55
43 47 35-3/4 1-1/4 2-1/2
10
16
6
49 6 2 720
5.4
12
1504 1500 1260
61
50 53 41-3/4 1-1/4 2-1/2
12
18-1/8
8
53 6 2 780
5.4
12
2004 1999 1679
75 61
65
53-3/4 2 2-1/2 14 20-1/8 8 69
9 5 940
5.4
18
-
Ratings shown are for elevations up to 4,500 feet. For installations at elevations
above 4,500 feet, please consult the factory for additional instructions.
-
For direct vent applications, please contact the factory about relocating the pump.
* Current draw is for heater only.
(Supply breaker must have delayed trip.)
RATES OF FLOW AND PRESSURE DROPS
20°F
∆
T 30°F
∆
T 40°F
∆
T*
Maximum Flow
Minimum Flow*
Model
(H7-)
GPM
∆
P (ft.)
GPM
∆
P (ft.)
GPM
∆
P (ft.)
GPM
∆
P (ft.)
∆
T (°F) GPM
∆
P (ft.)
∆
T (°F)
504 42 2.7 28 1.4 N/A N/A 100
11.3 8 25 1.1 34
754 63 6.0 42 2.9 32 1.7 100
13.8 13 32 1.7 40
1104 92 13.3 62 6.7 46 4.1 113 18.6 16 46 4.1 40
1504 N/A N/A 84 13.3 63 8.0 113 22.2 22 63 8.0
40
2004 N/A N/A 112 26.9 84 16.0 113 27.2 30 84 16.0 40
* Closed systems only
Raypak,
Inc.
2151 Eastman Avenue, Oxnard, CA 93030
(805) 278-5300
Fax (800) 872-9725
www.raypak.com
Raypak
Canada
Ltd.
2805 Slough St., Mississauga, Ontario, Canada L4T 1G2
(905) 677-7999
Fax (905) 677-8036
www.raypakcanada.com
CLEARANCES
Certified
Minimum
Recomm.
Service
Front 24”
24”
Rear 12”
24”
Right 1”
--
Left 1”
--
Top 0” 10”
Floor 0”
--
Vent 1”
--
PUMP HP – AMPS*
Water Hardness
Model
(H7-)
Soft Medium Hard
504
1/4 - 6
1/4 - 6
3/4 - 11
754
1/4 - 6
1/2 - 7
3/4 - 11
1104
1/4 - 6
1/2 - 7
1 - 14
1504
1/2 - 7
1 - 14
1 - 14
2004
1 - 14
1-1/2 - 15
1-1/2 - 15
* Current draw is for pump only