Raypak Commercial Space Heating and Domestic Water Specification Download Page 6

SHIP

FOOT

MODEL

INPUT   OUTPUT

B

D

E

F

G

H

K

M

P

WGT

PRINT  AMPS

(MBTU)

(MBTU) HEIGHT

NPT

NPT

FLUE

Lbs.

Ft.

2

H 751

750

630

64

38

44-1/2

29-3/4

1-1/2

2

8

17-3/4

41

680

5.4

8

H 1001

999

840

72

46

52-1/2

37-3/4

1-1/2

2-1/2

10

21-1/2

49

720

5.4

10

H 1501

1499

1260

82

56

62-1/2

47-3/4

1-1/2

2-1/2

12

20-1/4

59

780

5.4

12

FEATURES

Advanced Fan-Assisted Burner with Aerodynamically Stabilized Flame

Design Certified ANSI Z21.13 and Z21.10.3

Ultra-Low NOx: Less than 30ppm

Reduced Footprint

Indoor/Outdoor Construction

Thermal Shock Resistant

20 Year Limited Warranty

Natural Gas or Propane 

(except 1501)

STANDARD EQUIPMENT

HEAT EXCHANGER

Bronze Headers 

Integral Finned Tube Heat Exchanger 
Copper For Type H4
Cupro-Nickel For WH1

ASME Inspected and Stamped 150 PSIG

National Board Approved

Factory Installed ASME Relief Valve

Temperature and Pressure Gauge

GAS CONTROL TRAIN

Manual Main Gas Shut-Off Cock

Main Gas Pressure Regulator

Safety Shut-Off Valve, Redundant

Firing Mode: On/Off 

Factory Fire Tested

CSD-1 Compliant Gas Train

CONTROLS

120V, 60Hz, 1ø Power Supply

120/24V Transformer

100% Pilot Safety

Electronic Intermittent Ignition (IID)

High Limit Safeties

Central Point Wiring

• 

Full Boiler Diagnostics

Fan Proving Switch

Flow Switch

Blocked Flue Switch

CONSTRUCTION

Front Controls: Enclosed

Polytuf Powder Coat Finish

Durable Indoor/Outdoor Construction

Right Side or Rear Connections

Dimensions are in inches.  Ratings shown for elevations up to 5000 feet.  For installation at elevations over 5000 feet, please contact manufacturer.
See catalog 2000.27 for complete installation dimensions.

RAYPAK CORPORATE OFFICE AND 
PRINCIPAL MANUFACTURING FACILITY

2151 Eastman Avenue 
Oxnard, CA 93030
(805) 278-5300  FAX: (800) 872-9725

RAYPAK CANADA LIMITED
2805 Slough St., Mississauga 
Ontario, Canada L4T 1G2  
(905) 677-7999  FAX:  (905) 677-8036

Raypak, Inc. reserves the right to make product changes
or improvements at any time without notice

Catalog No. 3400.10G Effective: 07-15-03 Replaces: 07-01-01   Litho in USA ©1998-2001 Raypak, Inc.

www.raypak.com

Summary of Contents for Commercial Space Heating and Domestic Water

Page 1: ... Space Heating and Domestic Water ADB Advanced Design Boiler Up to 97 Thermal Efficiency Ultra low NOx Small Footprint Aerodynamically Stabilized Burner Full Diagnostics Multiple Venting Options Reduced Vent Sizes N e w 1 5 0 0 M B T U TM ...

Page 2: ...to corrosion THIRD GENERATION TECHNOLOGY After two decades of trial and error the boiler industry has finally realized that high efficiency and long product life can only be obtained by preventing condensation from occurring in the combustion chamber Raypak s Advanced Design Boiler is the first of a new generation of boilers that can obtain ultra high efficiencies without compromising product life...

Page 3: ...urbulent mixing action reduces residence time and increas es flue gas recirculation The result is clean effi cient combustion with NOx emissions well within the limits of the most restrictive air quality require ments This is one tough burner and the warranty proves it NOx emissions 0 30 ppm depending on combustion air quality and gas composition ERROR HEAT CENTRAL POINT WIRING AND DIAGNOSTICS Ray...

Page 4: ...rrosion proof coatings for extra protection The headers are bronze the heat exchanger tubes are made of cupro nickel and are coated with a condensate impervious epoxy enamel All non stainless internal fittings are either epoxy coated or are chemically immune The tube bundle casing is fabricated from AL29 4C stainless steel and the outer jacket has an electrostatically applied powder coat finish th...

Page 5: ...rrode or erode and can handle aggressive and hard water with ease SMALL FOOTPRINT The ADB occupies less than 51 2 sq ft of floor space VENT PRESSURE SWITCHES Enhance safety by verifying proper burner operation UP FRONT CONTROLS Easy access to all controls and gas train components ADVANCED BLUFF BODY BURNER Industrial tough solid metal burner head won t clog or burn out and it s backed with a TEN Y...

Page 6: ...ssure Regulator Safety Shut Off Valve Redundant Firing Mode On Off Factory Fire Tested CSD 1 Compliant Gas Train CONTROLS 120V 60Hz 1ø Power Supply 120 24V Transformer 100 Pilot Safety Electronic Intermittent Ignition IID High Limit Safeties Central Point Wiring Full Boiler Diagnostics Fan Proving Switch Flow Switch Blocked Flue Switch CONSTRUCTION Front Controls Enclosed Polytuf Powder Coat Finis...